Alarm verification concept (AVC)

Attendance check
7 Alarm verification concept (AVC)
28
Building Technologies
Fire Safety
The 'Alarm Verification Concept' serves the purpose of delayed alarm transmission
and takes into account the interaction of the operating personnel in the alarming
sequence.
Operating personnel are able to examine the indicated fire location in the event of
a fire alarm. In the event of a false alarm or minor incident the intervention of the
fire brigade can be avoided.
Information flow of 'ALARM' and 'Pre-ALARM'
D
'Detection tree'
AVC
Alarm verification concept
1
'Area'
The 'Area' receives 'Pre-ALARMS' or 'ALARMS' from 'Zones'. Alarm verification
takes place at 'Area' level.
Configuration for 'Pre-ALARMS' and 'ALARMS' is not related within 'AVC'. The type
of verification and alarming can be separately configured for the 'Manned
operation' and 'Unmanned operation' operation modes.
'ALARMS' from 'Manual zones ' and 'Automatic zones' 'Zones' as well as
'Degraded FIRE ALARM' can be configured differently.
A maximum of one 'AVC' is possible per 'Area'.
AL
'Pre-ALARM'/'ALARM'
GS
Danger levels
009310_i_en_--
2013-11-14