ABB PSTX370 Service Manual page 56

Hide thumbs Also See for PSTX370:
Table of Contents

Advertisement

8.
Connect bypass contactor cable and CT
cables to PCBA
When reconnecting cables; read markings on the
PCBA bracket.
1
Thread the bypass contactor cable, and the
three CT cables, through the cable inlets on the
PCBA bracket.
2
Connect the bypass contactor cable to its
terminal on the PCBA.
3
Connect the three CT cables, according to
previously made markings (1, 2 or 3), to their
terminals on the PCBA.
9.
Connect SCR cables to PCBA
When reconnecting cables; read markings on the
4
PCBA bracket.
1
Thread all three SCR cables through the cable
inlets on the PCBA bracket.
2
Connect the three SCR cables, according
to previously made markings (1, 2 or 3), to their
terminals on the PCBA.
10.
Place new PCBA and PCBA bracket
1
Place the new PCBA (mounted to bracket) on
the unit. Make sure cables do not get stuck in
between the bracket frame and Softstarter when
mounted.
11.
Place front cover
Place the front cover on the unit and align it to the
plastic screw sleeves located on lower housing.
1
Fasten the front cover with (4x)
x80/10 (1,6Nm).
2
Fasten (1x)
on the HMI bracket.
REASSEMBLE THE SOFTSTARTER
Connect main power cables and control
cables
Connect the main power cables and the control
cables as described in chapter 4.3.4, step 1-2.
Procedures after PCBA replacement
Set the ID of the Softstarter after changing the
PCBA, as described in chapter 4.2.2, step 1-6.
Firmware needs to be updated when changing
the HMI. Please contact your ABB sales office for
information.
Service PSTX470...570 | Service Manual |
56
Torx 20 4,0
Torx 15 M3,5x12 (0,5 Nm)
1SFC13105M0201
8
2
1
9
1
10
11
2
3
4.4.1_8
2
4.4.1_9
1
4.4.1_10
Tx 15 (0,5 Nm)
Tx 20 (1,6 Nm)
M3,5 x 12
M4 x 12
1
4.4.1_11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pstx210Pstx470Pstx570