Mitsubishi Electric GOT2000 Series User Manual page 380

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

Error
code
Too high frequency of data collection.
317
Review conditions.
The sound data with the specified
318
number does not exist.
Specified object does not exist or out
320
of range.
Dedicated device is out of range.
322
Confirm device range.
The data type of labels/tags do not
326
match. Please check the settings.
Label names have not been
327
resolved. Resolve label names
again.
Label/tag settings error. Please
328
check the label/tag settings.
Station numbers cannot be switched
329
when label/ tag devices are used.
Insufficient memory media capacity.
330
Confirm M-card capacity.
Memory card not installed or M-
331
CARD switched OFF
332
Memory media is not formatted.
Unable to overwrite. Memory card is
333
write-protected.
Memory media error. Replace
334
memory media.
The target file size is too large to be
336
accessed.
File output failed. Confirm output file
337
path.
8 - 6
8.2 Error Codes and System Alarm List
Error message
Data of an object, to which [Collect data only when trigger conditions are satisfied]
is set, are collected too frequently, or the number of objects has exceeded the
number of objects collectable simultaneously.
• Set a longer cycle for trigger occurrence to each object.
• Make the settings so that 257 or more display triggers of objects, to which
[Collect data only when trigger conditions are satisfied] is set, do not occur
simultaneously.
Review the specified number.
Register a sound file to the specified number.
The part file does not exist.
Create the part file and download to GOT.
The monitored device No. is out of the permissible area of the targeted PLC CPU.
Set the device within the range that can be monitored by the monitored PLC CPU
and parameter settings.
• The data type of the device assigned to the label or tag is incorrect.
For the available data type, refer to the following.
• The data type of object devices or others and that of labels or tags set on the
PLC side are inconsistent.
Correct the data type of the objects or others according to that of the labels or
tags set on the PLC side.
• A 64-bit device is assigned to the label or tag.
Do not use a 64-bit label and tag in the device setting.
Check the connection status of the PLC and execute the label name resolution
again.
• The label or tag is set for the PLC which does not support labels.
Correct the network No. and station number.
• The label name or tag name specified in the project data does not exist on the
PLC side.
Check if the label name or tag name specified in the project data exists on the
PLC side.
• The GOT access the label or tag inaccessible from external devices.
Enable the access from external devices in the label/tag setting on the PLC side.
• When a global label of structure has members to which devices are manually
assigned, the GOT fails to perform the label name resolution.
Perform operations so that the devices are automatically assigned to the
members, or directly set the manually assigned devices as monitor devices.
Do not perform the station No. switching to the station using labels or tags.
The available space of the memory card is insufficient.
Check the available space of the memory card.
For the checking method, refer to the following.
The memory card is not installed in the drive, or the SD card cover is opened.
• Install the memory card in the specified drive.
• Close the SD card cover to make the SD card accessable.
Memory card (build-in SD card) is not formatted or formatted incorrectly.
Format the memory card.
Memory card (build-in SD card) is write-protected.
Cancel the write-protection of memory card.
Memory card (build-in SD card) is faulty.
Replace the memory card.
• Check if the size of the file that the GOT attempts to access is larger than 2 GB.
• Check that the size of the image file is 300 KB or smaller.
Either of the following folder or file with the name same as the file to be created
exists in the storage destination SD card or USB memory.
• Folder storing data
• Write-protect file
Delete the above folder or file, or change the name of the file to be created.
GT Designer3 (GOT2000) Screen Design Manual
GT Designer3 (GOT2000) Screen Design Manual
GT Designer3 (GOT2000) Screen Design Manual
Action
Channel
No. storage

Advertisement

Table of Contents
loading

Table of Contents