Hitachi EH-150 Applications Manual page 123

Ethernet module 2 eh-eth2
Hide thumbs Also See for EH-150:
Table of Contents

Advertisement

- When you use a set of PLC with EH-ETH2 and host computer.
[Test content]
The UDP message is returned between EH-ETH2 of test mode and application software which supports
communication specification.
[Communication specification]
-
Communication protocol is UDP/IP.
-
The application software return the massage which the EH-ETH2 of test mode sends to it.
[Test procedure]
(a) Set communication parameter according to the Figure 10.2.
(b) Execute the application that supports the communication specifications.
(c) When you reset the EH-ETH2, the sending and receiving test will start.
EH-ETH2 (test object)
(Setting except Dip switch is factory setting.)
- Dip switch setting
Bit 5, 6 ON, Others OFF
- Own IP address
192.168.0.1
- Send/receive test other station IP address
192.168.0.254
- Send/receive test logical port number(Own station, other station)
4000
(Dec)
Figure 10.2
Send / Receive test abends in case that test object EH-ETH2 does not receive the reply in 20 seconds
from one sent the test data.
Table 10.2 shows lighting pattern of EH-ETH2 LED on the test.
POW
Blinking
System configuration of communication test (2)
Table 10.2
Result of communication test
STS
ERR
OFF
OFF
ON
OFF
OFF
ON
10-9
Chapter 10 Troubleshooting
Other station
- Own IP address
192.168.0.254
- EH-ETH IP address
192.168.0.1
- Send/receive test logical port number(Own station, other station)
4000
(Dec)
result
On testing
Normal end
Abend