Module status register (MDSR)

Bit
15
14
-
-
+0
Bit 15-7: Reserved
These bits are reserved bits. Usually "0" are set.
Bit 6: Operation mode bit (OPM)
The status of DIP-switch 1 is reflected on this bit.
Bit6: OPM
0
Normal operation mode
1
The other mode.
Bit 5: Reserved
This bit ais reserved bit. Usually "0" are set.
Bit 4: Ethernet information configuration error bit (EIE)
Illegal Ethernet parameters are set. In the case of this bit set "1", IER LED turns on.
Bit4: EIE
0
There is no error.
1
The illegal Ethernet parameters configuration (set-up) is detected.
Bit 3: Existence response bit (AVR)
The result of general working check for EH-ETH2. The data (IAV bit of Control Register) will be reflected here.
Bit3: AVR
0
The data set in Existence confirmation request bit (IAV) of Control Register are reflected.
1
Bit 2: Automatic Sending/Receiving enable bit (ATR)
This bit shows the current specified status of Automatic Sending/Receiving function is disable or enable.
Bit2: ATR
0
Automatic Sending/Receiving function is disable.
1
Automatic Sending/Receiving function is enable.
Bit 1: IER LED lighting condition bit (IERR)
This bit shows the current condition of IER LED.
Bit1: IERR
0
IER LED is turned off.
1
IER LED is turned on.
Bit 0: ERR LED lighting condition bit (ERR)
This bit show the current condition of ERR LED.
Bit0: ERR
0
ERR LED is turned off.
1
ERR LED is turned on.
13
12
11
10
9
-
-
-
-
-
8-2
Chapter 8 Register Structure
8
7
6
5
4
-
-
OPM
-
EIE AVR ATR IERR ERR
Description
Description
Description
Description
Description
Description
3
2
1
0