Toshiba MML-AP0124H2UL Service Manual page 31

Carrier
Hide thumbs Also See for MML-AP0124H2UL:
Table of Contents

Advertisement

7-2. Functions at test run
Cooling/Heating test run check
The test run for cooling/heating can be performed from either indoor remote control or outdoor interface P.C.
board.
1. Start/Finish operation of test run
Test run from indoor remote control
Wired remote control: Refer to the below item of "Test run" of the wired remote control.
Wireless remote control: Refer to the next page item of "Test run" of the wireless remote control.
In case of wired remote control
Procedure
Push [TEST] button for 4 seconds or more.
1
[TEST] is displayed at the display part and
the mode enters in TEST mode.
2
Push [ON/OFF] button.
Change the mode from [COOL] to [HEAT] using [MODE] button.
• Do not use [MODE] button for other mode except
3
[COOL]/[HEAT] modes.
• The temperature cannot be adjusted during test run.
• The trouble detection is performed as usual.
4
After test run, push [ON/OFF] button to stop the operation.
(Display on the display part is same to that in Procedure
5
Push [TEST] button to clear the TEST mode.
([TEST] display in the display part disappears and
status becomes the normal stop status.)
Note)
The test run returns to the normal operation after 60 minutes.
<RBC-AMT32UL>
TEMP.
TIMER SET
TIME
FILTER
1,
RESET
TEST
SET
5
Operation contents
ON / OFF
FAN
MODE
SAVE
VENT
CL
SWING/FIX
UNIT LOUVER
1
.)
– 31 –
2,
4
3
TEST
TEST

Advertisement

Table of Contents
loading

Table of Contents