Plugging a connector
■ Installation procedure
(1)
■ Removal procedure
Loosen the two connector screws and pull out the connector from the module straight.
Precautions
• Crimp or solder the connector for an external device (A6CON) correctly.
• Connect the A6CON to the module securely and tighten the two connector screws.
• Tighten the connector screws within the specified torque range.
Screw
Connector screw (M2.6)
• Place the cables in a duct or clamp them. If not, dangling cable may swing or inadvertently be pulled, resulting in damage to
the module or cables or malfunction due to poor contact.
• Use copper wire with a temperature rating of 75 or higher for the connector.
• Use UL listed connectors if necessary for UL compliance.
To ensure that the connector used maintains EMC and Low Voltage Directives, please refer to the following.
Page 172 EMC and Low Voltage Directives
Even when compliance with the EMC Directive and Low Voltage Directives is not required, configuring the
system that complies with the EMC Directive may reduce external noise.
5 INSTALLATION AND WIRING
130
5.7 Wiring
(1)
1.
Plug the connector into the slot on the module.
2.
Tighten the two connector screws (M2.6) (1).
Tightening torque range
0.20 to 0.29Nm