Mitsubishi Electric MELSEC iQ-R Series Configuration Manual page 77

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Assigning I/O numbers in the slave station
Network systems such as CC-Link IE Field Network can be controlled by assigning input "X" and output "Y", which are in the
device of the CPU module, to the I/O modules and intelligent function modules in the slave station.
Ex.
Controlling a module connected to the head module on CC-Link IE Field Network
16
20
to
2F
CC-Link IE Field Network
16
(3)
1000
to
100F
■ Available I/O numbers
In the slave station, assign the I/O numbers following the I/O numbers assigned to the modules in the master station.
■ Precautions
• The same I/O numbers cannot be used for the refresh destination (device on the CPU module side) on CC-Link IE Field
Network and for the CC-Link remote station.
• If there is a possibility of connecting more I/O modules and intelligent function modules to the CPU module, reserve I/O
numbers for modules to be added.
Input/output (X/Y)
X/Y0
·
X/Y3FF
X/Y400
·
X/YFFF
X/Y1000
For a CC-Link IE Field
Network slave station
Empty
For a CC-Link
remote station
·
X/Y2FFF
(1)
16
16
16
30
40
50
to
to
to
3F
4F
5F
(2)
16
1010
to
101F
I/O numbers used for an I/O module or
intelligent function module
For the future extension
I/O numbers that can be used for a slave station
(1) Master station
(2) Slave station
(3) Head module
2 ASSIGNMENT FOR MODULES
2.2 I/O Numbers of Modules
2