ABB REJ601 Product Manual

ABB REJ601 Product Manual

Relion 605 series feeder protection and control / feeder protection
Hide thumbs Also See for REJ601:

Advertisement

®
Relion
605 series
Feeder protection and control / Feeder
protection
REF601 / REJ601
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB REJ601

  • Page 1 ® Relion 605 series Feeder protection and control / Feeder protection REF601 / REJ601 Product Guide...
  • Page 2: Table Of Contents

    13. Local HMI .............. 7 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document.
  • Page 3: Description

    The standard signal configuration can be altered utility substations and industrial power systems, by LHMI (local human-machine interface). in primary and secondary distribution networks. REF601/REJ601 is a member of ABB’s Relion ® Further, the configuration functionality of the product family and part of its 605 series.
  • Page 4: Protection Functions

    ● ● = Included Protection functions 255-3 and ANSI C37.112, Normal Inverse (NI), REF601/REJ601 offers three-stage overcurrent Very Inverse (VI), Extremely Inverse (EI), Long- and two-stage earth-fault protection functions. time Inverse (LI) respective Moderate inverse, The transformer inrush detector function is Normal Inverse, Very inverse, Extremely inverse incorporated to prevent unwanted tripping’s due...
  • Page 5: Application

    Figure 1. Functionality overview for REF601 standard configuration E with current transformer inputs Application The relay additionally offers thermal overload The REF601/REJ601 is a protection relay aimed protection for feeders, cables and transformers, at protection and control of incoming and phase discontinuity (signle phasing) protection outgoing feeders in MV distribution substations.
  • Page 6: Control

    Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A Control Recorded data The relay offers control of one circuit breaker The relay stores fault records of analogue values with dedicated push-buttons and guidance on for last five trip events in non-volatile memory.
  • Page 7: Local Hmi

    Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2FP2 Issued: 2017-05-09 Revision: A for the operator, engineer and administrator The relay has six output contacts, two power level. There is availability of 2 different password outputs and four signalling outputs.
  • Page 8: Technical Data

    Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A 17. Technical data Table 5. Dimensions Relay type Description Value frame 130.0 mm Width case 121.5 mm frame 160.0 mm Height case 151.5 mm...
  • Page 9 Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2FP2 Issued: 2017-05-09 Revision: A Table 8. Binary input Description Value Rated voltage 24...240 V AC / DC 85...110% of Un for AC and Operating range 70...120% of Un for DC Current drain 2...20 mA...
  • Page 10 Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A Table 11. Signal output and IRF output (XK2 : BO3, BO4, BO5, BO6) Description Value Rated voltage 240 V AC/DC Continuous contact carry Make and carry for 3.0 s...
  • Page 11 Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2FP2 Issued: 2017-05-09 Revision: A Table 14. Environmental tests Description Type test value Reference Dry heat test (humidity < 50% ) IEC 60068-2-2 IEC 60068-2-48  Working ...
  • Page 12 Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A Table 16. Electromagnetic compatibility tests, continue Description Type test value Reference Power frequency magnetic field immunity IEC 61000-4-8 test:  Continuous 100 A/m ...
  • Page 13 Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2FP2 Issued: 2017-05-09 Revision: A Table 18. Mechanical tests Description Type test value Reference Vibration tests IEC 60255-21-1, class I 10...150 Hz, 0.035 mm / 1.0g,  Response 1 sweep / axis 10...150 Hz, 2.0 g,...
  • Page 14: Protection Functions

    Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A 18. Protection functions Table 23. Low-set phase overcurrent protection, stage 3I> / 51 Parameter Value (Range) Setting range of pick-up current ‘I >’...
  • Page 15 Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2FP2 Issued: 2017-05-09 Revision: A Table 26. Low-set earth-fault protection, stage Io> / 51N Parameter Value (Range) Setting range of pick-up current ‘Io>’ External earth measurement : 0.05...2.0 x In in steps 0.001, infinite Internal earth measurement : 0.5...2.0 x In in steps 0.001, infinite...
  • Page 16 Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A Table 28. Transformer inrush detection, 3I2f> / 68 Parameter Value (Range) Inrush threshold value 0.5...25 x In, in steps of 0.01 Ratio Setting 30%...50%, in steps of 5%...
  • Page 17 Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2FP2 Issued: 2017-05-09 Revision: A Table 31. Negative sequence overcurrent protection, I2> / 46 Parameter Value (Range) Start value, ‘I2>” 0.1…1.5 x In, in steps of 0.01 Operate delay time, ‘tI2>’...
  • Page 18 Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A Table 34. Counter Parameter Value (Range) Initial value of the counter at the start of IED, ‘Value’ 0…65535, in steps of 1 1…4 (1=BI1, 2=BI2, 3=BI3, 4=BI4)
  • Page 19: Dimensions And Mounting

    The REF601/REJ601 have been equipped with With appropriate mounting accessories the in-built press-fit mechanism. Without using any REF601/REJ601 can be mounted on the circuit additional mounting accessories, the breakers type VD4 /HD4. The panel cut-out for REF601/REJ601 can be easily flush mounted on flush mounting: the panel.
  • Page 20: Selection And Ordering Data

    Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2 FP2 Issued: 2017-05-09 Revision: A 20. Selection and ordering data The relay type and serial number label identifies The serial number and order number label is the protection relay.
  • Page 21: Terminal Diagram

    Feeder protection and control / Feeder protection 1MDB07221-YN REF601 / REJ601 Product version: 2.2FP2 Issued: 2017-05-09 Revision: A 22. Terminal diagram Figure 4. Terminal diagram of REF601/REJ601...
  • Page 22: References

    Web page helps you find the documents by the document category and You will find the latest relevant information on language. the REF601/REJ601 protection relay on the product page. The Features and Application tabs contain product related information in a compact format.
  • Page 24 Contact us ABB India Ltd, Distribution Automation Maneja Works Vadodara-390013, India Phone: +91 265 6724402 Fax: +91 265 6724407 ABB Oy, Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone: +358 10 22 11 Fax: +358 10 22 41094 www.abb.com/mediumvoltage...

This manual is also suitable for:

Ref601

Table of Contents