Line Differential Protection and Control
RED615
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB RED615

  • Page 1 Line Differential Protection and Control RED615 Product Guide...
  • Page 2: Table Of Contents

    13. Protection communication and supervision . . 8 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any errors that may appear in this document.
  • Page 3: Description

    (impedance earthed) and solidly earthed RED615, member of ABB’s 615 product networks. Once the IED has been given the series, is a phase-segregated two-end line application-specific settings, it can directly be differential protection and control IED (intel- put into service.
  • Page 4: Protection Functions

    Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 continued Measurement • Transient disturbance recorder • Three-phase current measurement Current sequence components • Differential current measurement • Bias current measurement • • = Included through the protected zone increasing errors 3. Protection functions...
  • Page 5: Application

    (LOM) protection in networks with distrib- network can be selectively isolated, thus se- uted generation. The performance of the curing power distribution to the healthy part of the network. Fig. 2 Closed loop network configuration with RED615 line differential protection and control IEDs...
  • Page 6 To avoid major re-parameterization of the protection devices of the network when the network topology is Fig. 3 RED615 protecting an interconnecting feeder between two primary distribution substations...
  • Page 7: Control

    Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 By default, the binary channels are set to 5. Control record external or internal IED signals, e.g. the start or trip signals of the IED stages, or external blocking or control signals. Binary...
  • Page 8: Trip-Circuit Supervision

    Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 The fault recording can be triggered by the and the measured residual current originat- start signal or the trip signal of a protection ing from the second core in the current block, or by both.
  • Page 9: Access Control

    Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 cation, persists. The two high-set stages of the Optional I/O extension module: overcurrent protection are further by default • Six binary control inputs released. • Three changeover signaling-output con- tacts 13. Access control...
  • Page 10 Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 bance files and storing of the latest fault methods with a time-stamping resolution of records. If a Modbus TCP connection is used, +/- 1 ms: five clients can be connected to the IED simultaneously.
  • Page 11: Technical Data

    Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 17. Technical data Dimensions Width frame 177 mm, case 164 mm Height frame 177 (4U) case 160 mm Depth case 155 mm Weight 3.5 kg spare unit 1.8 kg Power Supply...
  • Page 12 Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 Energizing inputs Rated frequency 50/60 Hz ± 5 Hz Current inputs Rated current, I 1/5 A Thermal withstand capability: • Continuously 20 A • For 1 s For 1 s 500 A •...
  • Page 13 Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 IRF relay change over - type signal output relay 250 V AC/DC Rated voltage Continuous contact carry Make and carry for 3.0 s 10 A Make and carry 0.5 s...
  • Page 14 Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 Degree of protection of flush-mounted IED IP 54 Front side Rear side, connection terminals IP 20 Environmental conditions and tests Environmental conditions Operating temperature range -25...+55ºC (continuous) Short-time service temperature range -40...+70ºC (<16h)
  • Page 15 Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 (continued) Radio frequency interference tests: • Conducted, common mode According to IEC 61000-4-6 IEC 60255-22-6, level 3 10 V (emf), f = 150 kHz...80 MHz • Radiated, amplitude-modulated According to IEC 61000-4-3 and IEC 60255-22-3, level 3 10 V/m (rms), f=80...1000 MHz...
  • Page 16 Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 Insulation and mechanical tests Insulation tests Dielectric tests: According to IEC 60255-5 • Test voltage 2 kV, 50 Hz, 1 min 500 V, 50 Hz, 1min, communication Impulse voltage test: According to IEC 60255-5 •...
  • Page 17 Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 Protection communication link, fibre-optic Wavelength Fibre type Connector Permitted path Distance attenuation 1300 nm MM 62.5/125 μm LC < 8 dB ≤ 2 km 1300 nm SM 9/125 μm <...
  • Page 18 Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 Protection functions Line differential protection (LNPLDF) Operation Depending on the frequency of the current measured: fn ±2 Hz accuracy Low stage ±2.5% of the set value High stage ±2.5% of the set value...
  • Page 19 Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 Three-phase non-directional overcurrent protection (PHxPTOC) Operation Depending on the frequency of the current measured: f ±2Hz accuracy PHLPTOC ±1.5% of the set value or ±0.002 x I PHHPTOC ±1.5% of set value or ±0.002 x I (at currents in the range of 0.1…10 x I...
  • Page 20 Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 Negative phase-sequence current protection (NSPTOC) Operation accuracy Depending on the frequency of the current measured: f = ±2Hz ±1.5% of the set value or ±0.002 x I Start time...
  • Page 21 Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 Circuit breaker failure protection (CCBRBRF) main settings Parameter Function Value (Range) Step Current value CCBRBRF 0.05...1.00 x I 0.05 (Operating phase current) Current value Res CCBRBRF 0.05...1.00 x I 0.05...
  • Page 22 Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 Operating characteristics Parameter Values (Range) Operating curve type 1=ANSI Ext. inv. 2=ANSI Very. inv. 3=ANSI Norm. inv. 4=ANSI Mod inv. 5=ANSI Def. Time 6=L.T.E. inv. 7=L.T.V. inv. 8=L.T. inv.
  • Page 23: Display Options

    Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 The large display offers increased front- 18. Display options panel usability with less menu scrolling and improved information overview. The large display is suited for IED installations where The IED is available with two optional dis- the front panel user interface is frequently plays, a large one and a small one.
  • Page 24: Mounting Methods

    Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 Panel cut-out for flush mounting: 19. Mounting methods • Height: 161.5±1 mm • Width: 165.5±1 mm By means of appropriate mounting acces- sories the standard IED case for the 615 series IEDs can be flush mounted, semi-flush 20. IED case and IED...
  • Page 25: Selection And Ordering Data

    Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 codes generated from the hardware and soft- 21. Selection and ware modules of the IED. ordering data Use the ordering key information in Fig. 10 to generate the order number when ordering The IED type and serial number label identi- complete protection and control IEDs.
  • Page 26 Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 H B D A A C A D A B B 1 A N N 1 X A DESCRIPTION Substation communication (serial) 1) 2) RS485 (connector incl. IRIG-B) ST glass fi bre (Rx/Tx)
  • Page 27 Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 H B D A A C A D A B B 1 A N N 1 X A DESCRIPTION Language English Front panel Small LCD Large LCD Option 1...
  • Page 28: Accessories And Ordering Data

    (IE the IED specific connectivity package. The 7.0 or later). For security reasons, the web- connectivity package for RED615 includes a browser based user interface is disabled by tool for line differential protection parameter default.
  • Page 29 Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 Tool function overview Function WebHMI PCM600 • IED signal configuration (signal matrix tool) • IEC 61850 communication configuration, GOOSE (communication configuration tool) Modbus communication configuration • ® (communication management tool) •...
  • Page 30: Terminal Diagram

    Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 24. Terminal diagram Fig. 10 Terminal diagram of standard configuration A...
  • Page 31: Functions, Codes And Symbols

    Line Differential Protection and Control 1MRS756500 A RED615 Product version: 1.1 25. Functions, codes and symbols RED615 functions, codes and symbols Functions IEC 61850 ANSI 60617 Protection functions LNPLDF Line differential protection, stabilized low stage and 3∆I>, instantaneous high stage 3∆I>> PHLPTOC Three-phase non-directional overcurrent, low-set 3I>...