ABB Relion 650 Series Product Manual

ABB Relion 650 Series Product Manual

Line distance protection
Hide thumbs Also See for Relion 650 Series:

Advertisement

Quick Links

®
Relion
650 series
Line distance protection
REL650
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 650 Series

  • Page 1 ® Relion 650 series Line distance protection REL650 Product Guide...
  • Page 2: Table Of Contents

    20. Ordering............73 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumes no responsibility for any errors that may appear in this document. © Copyright 2009 ABB AB.
  • Page 3: Description

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Configured Revision: - with the synchrocheck function with high- 1. Description speed or delayed reclosing. High set instantaneous phase and earth Line distance protection IED overcurrent, four step directional or non- REL650 directional delayed phase and earth overcurrent, sensitive earth fault, thermal...
  • Page 4 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 132 kV Bus REL650 A01 – Quad Distance Zones, Single Breaker 10AI (4I+1I+5U) 132kV/ 110V 132kV/ 110V Meter. V MMXU Meter. V MMXU 0->1 1->0 SYNC SMB RREC SMP PTRC SES RSYN...
  • Page 5 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 132 kV Bus REL650 A05 – Mho Distance Zones, Single Breaker 10AI (4I+1I+5U) 132kV/ 110V 132kV/ 110V Meter. V MMXU Meter. V MMXU 0->1 1->0 SYNC SMB RREC SMP PTRC SES RSYN...
  • Page 6: Available Functions

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 3. Available functions Main protection functions ANSI Function description Line Distance 61850 Impedance protection ZQDPDIS Five zone distance protection, quadrilateral characteristic FDPSPDIS 21 Phase selection with load enchroachment, quadrilateral characteristic ZMOPDIS Five zone distance protection, mho characteristic...
  • Page 7 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Back-up protection functions IEC 61850 ANSI Function description Line Distance Current protection PHPIOC Instantaneous phase overcurrent protection OC4PTOC 51/67 Four step directional phase overcurrent protection EFPIOC Instantaneous residual overcurrent protection EF4PTOC 51N/...
  • Page 8 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Control and monitoring functions IEC 61850 ANSI Function description Line Distance Control SESRSYN Synchrocheck, energizing check, and synchronizing SMBRREC Autorecloser QCBAY Bay control LOCREM Handling of LR-switch positions LOCREMCTRL LHMI control of PSTO SLGGIO...
  • Page 9 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 IEC 61850 ANSI Function description Line Distance LOOPDELAY Configurable logic blocks, loop delay TimeSet Configurable logic blocks, timer Configurable logic blocks, AND SRMEMORY Configurable logic blocks, set-reset memory RSMEMORY Configurable logic blocks, reset-set memory FXDSIGN...
  • Page 10 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 IEC 61850 ANSI Function description Line Distance MVEXP Measured value expander block LMBRFLO Fault locator SPVNZBAT Station battery supervision SSIMG Insulation gas monitoring function SSIML Insulation liquid monitoring function SSCBR Circuit breaker condition monitoring Metering...
  • Page 11 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Designed to communicate IEC 61850 ANSI Function description Line Distance Station communication IEC 61850 communication protocol DNP3.0 for TCP/IP communication protocol GOOSEINT Horizontal communication via GOOSE for LKRCV interlocking GOOSEBIN...
  • Page 12: Impedance Protection

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Basic IED functions IEC 61850 Function description Basic functions included in all products INTERRSIG Self supervision with internal event list Time synchronization SETGRPS Setting group handling ACTVGRP Parameter setting groups TESTMODE...
  • Page 13 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 (forward or reverse) or non-directional mode. which gives high flexibility for all types of This makes them suitable, together with lines. different communication schemes, for the The IED can be used up to high voltage protection of power lines and cables in levels.
  • Page 14: Current Protection

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 algorithm for load encroachment, which gives breaker onto a fault. A dead line detection the possibility to enlarge the resistive setting check is provided to activate the function of the measuring zones without interfering when the line is dead.
  • Page 15 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Four step residual overcurrent Time delayed 2-step undercurrent protection EF4PTOC protection UC2PTUC The four step residual overcurrent protection Time delayed 2-step undercurrent protection (EF4PTOC) has an setable inverse or definite (UC2PTUC) function is used to supervise the time delay independent for step 1 and 4 line for low current, for example, to detect a...
  • Page 16: Voltage Protection

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 CCRBRF function can be programmed to give Directional over/underpower a three-phase re-trip of the own breaker to protection GOPPDOP/GUPPDUP avoid unnecessary tripping of surrounding breakers at an incorrect initiation due to The directional over-/under-power protection mistakes during testing.
  • Page 17: Frequency Protection

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 function can be used to open circuit breakers value for a time longer than the set time and to prepare for system restoration at power the circuit breaker remains closed. outages or as long-time delayed back-up to primary protection.
  • Page 18: Secondary System Supervision

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 without the presence of the negative- 8. Secondary system sequence current 3I supervision The zero sequence detection algorithm is recommended for IEDs used in directly or low impedance earthed networks.
  • Page 19 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 The systems can thus be reconnected after an choose if the switch signals are coming from auto-reclose or manual closing which the local HMI or from an external hardware improves the network stability.
  • Page 20: Scheme Communication

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 example, SCSWI). In this way, simple Local acceleration logic ZCLCPLAL commands can be sent directly to the IED outputs, without confirmation. Confirmation To achieve fast clearing of faults on the (status) of the result of the commands is whole line, when no communication channel supposed to be achieved by other means,...
  • Page 21: Logic

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 protection function can be supported with output signals to different output contacts on logic, that uses communication channels. the IED. The 650 series IEDs have for this reason TMAGGIO output signals and the physical available additions to scheme communication outputs are available in PCM600 and this...
  • Page 22: Monitoring

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 setting controls if the block after a power • measured voltages, currents, frequency, interruption should return to the state active, reactive and apparent power and before the interruption, or be reset. Reset power factor input has priority.
  • Page 23 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 time to the end of post-fault time, will be example corrective actions) and in the long included in the recording. term (for example Functional Analysis). Every disturbance report recording is saved The event recorder logs all selected binary in the IED in the standard Comtrade format.
  • Page 24: Metering

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 The function is characterized by great In the definite time (DT) mode, SPVNZBAT flexibility and is not dependent on the operates after a predefined operate time and operation of protection functions.
  • Page 25: Human Machine Interface

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 energy meter, for calculation of energy The LHMI is used for setting, monitoring and consumption values. The pulses are captured controlling. by the BIO (binary input/output) module The Local human machine interface, LHMI and then read by the PCGGIO function.
  • Page 26: Station Communication

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 authorization, as it is implemented in the IED Parameter setting groups ACTVGRP and in PCM600 is based on the following facts: Use the four sets of settings to optimize IED There are two types of access points to the operation for different system conditions.
  • Page 27: Hardware Description

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 events to five different clients on the IEC 17. Hardware description 61850 station bus. All communication connectors, except for the Layout and dimensions front port connector, are placed on integrated communication modules.
  • Page 28 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 IEC09000675.ai IEC09000673.ai IEC09000675 V1 EN IEC09000673 V1 EN Figure 9. Semi-flush mounted IED Figure 7. Flush mounted IED 154 mm + 12 mm with ring-lug connector 222 mm 265 mm 27 mm...
  • Page 29 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Rack mounting the IED Wall mounting the IED IEC09000678.ai IEC09000678 V1 EN Figure 12. Wall mounting the IED 270 mm 190.5 mm IEC09000676.ai 252.5 mm 296 mm IEC09000676 V1 EN ∅6.8 mm Figure 10.
  • Page 30: Connection Diagrams

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 18. Connection diagrams Module Rear Position X0, X1, X4, X9,X304 X307, X309, X410 X101, X102 X321, X324 X326, X329 X331, X334 X336, X339 1MRK006501-DA 2 PG V1 EN Figure 13.
  • Page 31 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 1MRK006501-HA 7 PG V1 EN Figure 18. Binary input/output (BIO) option (Terminal X321, X324) 1MRK006501-HA 5 PG V1 EN Figure 16. Power supply module (PSM) AC, 110-250V DC 1MRK006501-HA 8 PG V1 EN Figure 19.
  • Page 32: Technical Data

    Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 19. Technical data General Definitions Reference The specified value of an influencing factor to which are referred the value characteristics of the equipment Nominal The range of values of an influencing quantity (factor) within which, under range specified conditions, the equipment meets the specified requirements Operative...
  • Page 33 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Analog inputs Table 2. Energizing inputs Description Value Rated frequency 50/60 Hz Operating range Rated frequency ± 5 Hz Current inputs Rated current, I 0.1/0.5 A 1/5 A Thermal withstand capability:...
  • Page 34 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Auxiliary DC voltage Table 3. Power supply Description Type 1 Type 2 nominal 100, 110, 120, 220, 240 V 48, 60, 110, 125 V DC AC, 50 and 60 Hz 110, 125, 220, 250 V DC variation 85...110% of U...
  • Page 35 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 5. Signal output and IRF output IRF relay change over - type signal output relay Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 10 A Make and carry 0.5 s...
  • Page 36 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 9. Fibre-optic communication link Wave length Fibre type Connector Permitted path Distance attenuation 1300 nm MM 62.5/125 <8 dB 2 km μm glass fibre core 1) Maximum allowed attenuation caused by connectors and cable together Table 10.
  • Page 37 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 14. Environmental conditions Description Value Operating temperature range -25...+55ºC (continuous) Short-time service temperature range -40...+85ºC (<16h) Note: Degradation in MTBF and HMI performance outside the temperature range of -25...+55ºC Relative humidity <93%, non-condensing...
  • Page 38 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Type tests according to standards Table 16. Electromagnetic compatibility tests Description Type test value Reference 100 kHz and 1 MHz burst IEC 61000-4-18 disturbance test IEC 60255-22-1, level 3 •...
  • Page 39 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 16. Electromagnetic compatibility tests, continued Description Type test value Reference Power frequency immunity IEC 60255-22-7, class A test 300 V rms IEC 61000-4-16 • Common mode 150 V rms •...
  • Page 40 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 17. Insulation tests Description Type test value Reference Dielectric tests: IEC 60255-5 • Test voltage 2 kV, 50 Hz, 1 min 1 kV, 50 Hz, 1min, communication Impulse voltage test: IEC 60255-5...
  • Page 41 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 EMC compliance Table 20. EMC compliance Description Reference EMC directive 2004/108/EC Standard EN 50263 (2000) EN 60255-26 (2007)
  • Page 42 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Impedance protection Table 21. Distance measuring zone, Quad ZQDPDIS Function Range or value Accuracy Number of zones 5 with selectable direction Minimum operate (5-30)% of IBase ±...
  • Page 43 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 22. Phase selection with load encroachment, quadrilateral characteristic FDPSPDIS Function Range or value Accuracy Minimum operate current (5-30)% of IBase ± 1.0% of I Reactive reach, positive (0.50–3000.00) ±...
  • Page 44 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 23. Full-scheme distance protection, Mho characteristic ZMOPDIS Function Range or value Accuracy Number of zones with 5 with selectable selectable directions direction Minimum operate current (10–30)% of I ±...
  • Page 45 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 25. Phase preference logic PPLPHIZ Function Range or value Accuracy Operate value, phase-to- (10.0 - 100.0)% of UBase ± 0,5% of U phase and phase-to- neutral undervoltage Reset ratio, undervoltage <...
  • Page 46 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 27. Automatic switch onto fault logic, voltage and current based ZCVPSOF Parameter Range or Accuracy value Operate voltage, detection of dead line (1–100)% of ± 0.5% of U UBase Operate current, detection of dead line (1–100)% of...
  • Page 47 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 29. Four step phase overcurrent protection OC4PTOC Function Setting range Accuracy ± 1.0% of I at I £ I Operate current (5-2500)% of lBase ± 1.0% of I at I > I Reset ratio >...
  • Page 48 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 30. Instantaneous residual overcurrent protection EFPIOC Function Range or value Accuracy ± 1.0% of I at I £ I Operate current (1-2500)% of lBase ± 1.0% of I at I > I Reset ratio >...
  • Page 49 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 31. Four step residual overcurrent protection EF4PTOC Function Range or value Accuracy ± 1.0% of I at I £ I Operate current (1-2500)% of lBase ±...
  • Page 50 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 32. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy ± 1.0% of I at I £ I (0.25-200.00)% of lBase Operate level for 3I ·cosj ±...
  • Page 51 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 32. Sensitive directional residual overcurrent and power protection SDEPSDE, continued Function Range or value Accuracy Operate time, non 35 ms typically at 0.5 to 2 ·I directional residual over current Reset time, non directinal...
  • Page 52 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 34. Thermal overload protection, one time constant LPTTR Function Range or value Accuracy ± 1.0% of I Reference current (0-400)% of IBase ± 1.0°C Start temperature (0-400)°C reference Time constant t = (0–...
  • Page 53 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 36. Stub protection STBPTOC Function Range or value Accuracy ± 1.0% of I at I £ I Operating current (1-2500)% of IBase ± 1.0% of I at I > I Reset ratio >...
  • Page 54 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 39. Directional over/underpower protection GOPPDOP/GUPPDUP Function Range or value Accuracy Power level (0.0–500.0)% of Sbase ± 1.0% of S at S < S ± 1.0% of S at S > S At low setting: (0.5-2.0)% of Sbase <...
  • Page 55 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Voltage protection Table 41. Two step undervoltage protection UV2PTUV Function Range or value Accuracy Operate voltage, low and (1–100)% of UBase ± 0.5% of U high step Reset ratio <105% Inverse time characteristics...
  • Page 56 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 43. Two step residual overvoltage protection ROV2PTOV Function Range or value Accuracy Operate voltage, step 1 (1-200)% of Ubase ± 0.5% of U at U < U ±...
  • Page 57 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Frequency protection Table 45. Under frequency protection SAPTUF Function Range or value Accuracy Operate value, start function (35.00-75.00) Hz ± 2.0 mHz Operate value, restore frequency (45 - 65) Hz ±...
  • Page 58 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Secondary system supervision Table 48. Current circuit supervision CCSRDIF Function Range or value Accuracy ± 10.0% of I at I £ I Operate current (5-200)% of I ±...
  • Page 59 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Control Table 51. Synchronizing, synchrocheck check and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage ratio, U 0.20-5.00 line Frequency difference limit between...
  • Page 60 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 52. Autorecloser SMBRREC Function Range or value Accuracy Number of autoreclosing shots 1 - 5 Autoreclosing open time: shot 1 - t1 3Ph (0.000-60.000) s ±...
  • Page 61 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Scheme communication Table 53. Scheme communication logic for distance or overcurrent protection ZCPSCH Function Range or value Accuracy Scheme type Intertrip Permissive UR Permissive OR Blocking Co-ordination time for (0.000-60.000) s ±...
  • Page 62 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 55. Scheme communication logic for residual overcurrent protection ECPSCH Function Range or value Accuracy Scheme type Intertrip Permissive UR Permissive OR Blocking Communication scheme (0.000-60.000) s ±...
  • Page 63 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 58. Configurable logic blocks Logic block Quantity with Range or value Accuracy cycle time 5 ms LogicAND LogicOR LogicXOR LogicInverter LogicSRMemory LogicGate LogicPulseTimer (0.000–90000.000) s ±...
  • Page 64 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 60. Event counter CNTGGIO Function Range or value Accuracy Counter value 0-10000 Max. count up speed 10 pulses/s...
  • Page 65 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 61. Disturbance report DRPRDRE Function Range or value Accuracy Current recording ± 1,0% of I at I ≤ I ± 1,0% of I at I > Ir Voltage recording ±...
  • Page 66 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 62. Fault locator LMBRFLO Function Value or range Accuracy Reactive and resistive (0.001-1500.000) Ω/phase ± 2.0% static accuracy reach ± 2.0% degrees static angular accuracy Conditions: Voltage range: (0.1-1.1) x U Current range: (0.5-30) x I...
  • Page 67 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 66. Trip value recorder DRPRDRE Function Value Buffer capacity Maximum number of analog inputs Maximum number of disturbance reports Table 67. Disturbance recorder DRPRDRE Function Value Buffer capacity Maximum number of analog inputs...
  • Page 68 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 70. Insulation liquid monitoring function SSIML Function Range or value Accuracy Alarm, oil level 0.00-25.00 Oil level lockout 0.00-25.00 Temperature alarm -40.00-200.00 Temperature lockout -40.00-200.00 Timers (0.000-60.000) s ±...
  • Page 69 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Hardware Table 74. Degree of protection of flush-mounted IED Description Value Front side IP 40 Rear side, connection terminals IP 20 Table 75. Degree of protection of the LHMI Description Value Front and side...
  • Page 70 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Inverse time characteristics Table 77. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = 0.05-999 in steps of 0.01 unless otherwise stated æ...
  • Page 71 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 79. RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic k=(0.05-999) in steps of 0.01 IEC 60255-3, class 5 + 40 ms ×...
  • Page 72 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 81. Inverse time characteristics for Two step overvoltage protection OV2PTOV Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of Class 5 +40 ms 0.01 æ...
  • Page 73 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Table 82. Inverse time characteristics for Two step residual overvoltage protection ROV2PTOV Function Range or value Accuracy Type A curve: k = (0.05-1.10) in Class 5 +40 ms steps of 0.01 æ...
  • Page 74: Ordering

    Selection for position #1. Configuration alternatives Notes and Rules Single breaker, 3-phase tripping, quadrilateral Single breaker, 3-phase tripping, mho ACT configuration ABB standard configuration Selection for position #2. Software options Notes and Rules No option Selection for postition #3 First HMI language...
  • Page 75 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Casing Notes and Rules Rack casing, 6 U 1/2 x 19" Selection for position #5. Mounting details with IP40 of protection Notes and Rules from the front No mounting kit included Rack mounting kit for 6 U 1/2 x 19"...
  • Page 76 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Binary input/output module Notes and Rules Slot position (rear view) Available slots in 1/2 case Only if no AIM selected No board in slot Binary input/output module 9 BI, 3 NO Trip, 5 NO Signal, 1 CO Signal Selection for position #10.
  • Page 77 Line distance protection 1MRK 506 308-BEN - REL650 Product version: 1.0 Issued: September 2009 Rule: Specify additional quantity of IED Connect CD requested User documentation Quantity: 1MRK 003 500-AA Rule: Specify the number of printed manuals requested Operation manual Quantity: 1MRK 500 088-UEN Technical manual Quantity:...
  • Page 78 Communication protocol manual, DNP3 1MRK 511 224-UEN Communication protocol manual, IEC 61850 1MRK 511 205-UEN Engineering manual 1MRK 511 206-UEN Installation manual 1MRK 514 013-UEN Point list manual, DNP3 1MRK 511 225-UEN Latest versions of the described documentation can be found on www.abb.com/substationautomation...
  • Page 80 Contact us ABB AB Substation Automation Products SE-721 59 Västerås, Sweden Phone +48 (0) 21 34 20 00 +48 (0) 21 14 69 18 www.abb.com/substationautomation...