Page 4
Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Page 9
Lens characteristic............... 141 Detecting an out-of-step condition........143 Maximum slip frequency............144 Taking care of the circuit breaker ........145 Design.................. 147 Technical data................148 Phase preference logic PPL2PHIZ..........148 Identification................148 Functionality................148 Function block................149 Line distance protection REL650 2.2 IEC Technical manual...
Page 10
Function block................179 Signals..................179 Settings..................180 Monitored data................180 Operation principle..............180 Technical data................181 Directional residual overcurrent protection, four steps EF4PTOC .182 Identification................182 Functionality................182 Function block................183 Signals..................183 Settings..................184 Monitored data................191 Line distance protection REL650 2.2 IEC Technical manual...
Page 11
SDEPSDE ..................217 Identification................217 Functionality................218 Function block................219 Signals..................220 Settings..................221 Monitored data................223 Operation principle..............223 Function inputs..............223 Technical data................229 Thermal overload protection, one time constant, Celsius/ Fahrenheit LCPTTR/LFPTTR............230 Identification................230 Line distance protection REL650 2.2 IEC Technical manual...
Page 12
Settings..................252 Monitored data................253 Operation principle..............254 Measured quantities............. 254 Base quantities..............254 Overcurrent protection............254 Logic diagram...............256 Undervoltage protection............256 Technical data................257 Section 8 Voltage protection............259 Two step undervoltage protection UV2PTUV ........259 Line distance protection REL650 2.2 IEC Technical manual...
Page 13
Monitored data................289 Operation principle..............290 Measurement principle............290 Time delay................290 Blocking................295 Design.................. 295 Technical data................296 Section 9 Frequency protection............299 Underfrequency protection SAPTUF ..........299 Identification................299 Functionality................299 Function block................299 Line distance protection REL650 2.2 IEC Technical manual...
Page 14
Design.................. 312 Technical data................313 Section 10 Secondary system supervision........315 Current circuit supervision CCSSPVC..........315 Identification................315 Functionality................315 Function block................315 Signals..................316 Settings..................316 Operation principle..............316 Technical data................318 Fuse failure supervision FUFSPVC..........318 Line distance protection REL650 2.2 IEC Technical manual...
Page 15
Description of the status transition........359 Functional sequence description..........360 Time sequence diagrams............. 374 Technical data................377 Interlocking ..................378 Logical node for interlocking SCILO ......... 378 Identification................. 378 Functionality................. 378 Function block..............378 Line distance protection REL650 2.2 IEC Technical manual...
Page 16
Function block..............410 Signals..................410 Settings................412 Operation principle............... 412 Position supervision............. 412 Command response evaluation..........412 Logic rotating switch for function selection and LHMI presentation SLGAPC..............414 Identification................414 Functionality................414 Function block................415 Line distance protection REL650 2.2 IEC Technical manual...
Page 17
Functionality................426 Function block................427 Signals..................427 Settings..................428 Operation principle..............429 Single command, 16 signals SINGLECMD........429 Identification................429 Functionality................429 Function block................430 Signals..................430 Settings..................431 Operation principle..............431 Section 12 Scheme communication..........433 Line distance protection REL650 2.2 IEC Technical manual...
Page 18
Function block................446 Signals..................447 Settings..................447 Operation principle..............448 Zone extension..............448 Loss-of-Load acceleration............ 448 Scheme communication logic for residual overcurrent protection ECPSCH ...............449 Identification................449 Functionality................449 Function block................450 Signals..................450 Settings..................451 Operation principle..............451 Line distance protection REL650 2.2 IEC Technical manual...
Page 19
Signals..................473 Settings..................474 Operation principle..............474 Trip matrix logic TMAGAPC............480 Identification................480 Functionality................480 Function block................481 Signals..................481 Settings..................483 Operation principle..............483 Technical data................484 Logic for group alarm ALMCALH............484 Identification................484 Line distance protection REL650 2.2 IEC Technical manual...
Page 20
Inverter function block INV............494 Function block..............494 Signals..................494 Technical data..............495 Loop delay function block LLD..........495 Function block..............495 Signals..................495 Technical data..............495 OR function block..............496 Function block..............496 Signals..................496 Line distance protection REL650 2.2 IEC Technical manual...
Page 21
Boolean 16 to Integer conversion B16I.......... 505 Identification................505 Functionality................505 Function block................505 Signals..................506 Monitored data................506 Settings..................506 Operation principle..............507 Technical data................508 Boolean to integer conversion with logical node representation, 16 bit BTIGAPC............. 508 Line distance protection REL650 2.2 IEC Technical manual...
Page 29
Function status fault protection for IEC 60870-5-103 I103FLTPROT................744 Functionality................. 744 Identification................. 744 Function block..............745 Signals..................745 Settings................746 IED status for IEC 60870-5-103 I103IED........747 Functionality................. 747 Identification................. 747 Function block..............747 Line distance protection REL650 2.2 IEC Technical manual...
Page 30
Settings................756 Function commands generic for IEC 60870-5-103 I103GENCMD................756 Functionality................. 756 Identification................. 756 Function block..............757 Signals..................757 Settings................757 IED commands with position and select for IEC 60870-5-103 I103POSCMD............757 Functionality................. 757 Line distance protection REL650 2.2 IEC Technical manual...
Page 31
Authority check ATHCHCK.............777 Identification................777 Functionality................777 Operation principle ..............778 Authorization with Central Account Management enabled IED................780 Authority management AUTHMAN..........783 Identification................783 AUTHMAN.................783 Settings..................783 FTP access with password FTPACCS........... 783 Identification................783 Line distance protection REL650 2.2 IEC Technical manual...
Page 32
Synchronization alternatives..........805 Process bus IEC/UCA 61850-9-2LE synchronization..808 Precision Time Protocol (PTP) ..........808 Technical data................809 Parameter setting groups............... 810 Functionality................810 Function block................810 Signals..................810 Settings..................811 Operation principle..............811 Line distance protection REL650 2.2 IEC Technical manual...
Page 33
Summation block 3 phase 3PHSUM..........826 Functionality................826 Function block................826 Signals..................826 Settings..................827 Operation principle ..............828 Global base values GBASVAL............828 Identification................828 Functionality................828 Settings..................828 Primary system values PRIMVAL...........829 Identification................829 Functionality................829 Line distance protection REL650 2.2 IEC Technical manual...
For operate and reset time testing, the default setting values of the function are used if not explicitly stated otherwise. During testing, signals with rated frequency have been injected if not explicitly stated otherwise. Line distance protection REL650 2.2 IEC Technical manual...
The intended use of manuals throughout the product lifecycle The engineering manual contains instructions on how to engineer the IEDs using the various tools available within the PCM600 software. The manual provides Line distance protection REL650 2.2 IEC Technical manual...
Page 39
The guideline can be used as a technical reference during the engineering phase, installation and commissioning phase, and during normal service. Line distance protection REL650 2.2 IEC Technical manual...
Function block names are used in ACT and PST to identify functions. Respective function block names of Edition 1 logical nodes and Edition 2 logical nodes are shown in the table below. Line distance protection REL650 2.2 IEC Technical manual...
ZMFPDIS Distance protection, quad and mho characteristic PPL2PHIZ Phase preference logic ZMRPSB Power swing detection PSLPSCH Power swing logic OOSPPAM Out-of-step protection ZCVPSOF Automatic switch onto fault logic, voltage and current based Line distance protection REL650 2.2 IEC Technical manual...
OV2PTOV Two step overvoltage protection ROV2PTOV Two step residual overvoltage protection Frequency protection SAPTUF Underfrequency protection SAPTOF Overfrequency protection SAPFRC Rate-of-change of frequency protection 1) 67 requires voltage 2) 67N requires voltage Line distance protection REL650 2.2 IEC Technical manual...
Fuse failure supervision Logic SMPPTRC Tripping logic SMAGAPC General start matrix block STARTCOMB Start combinator TMAGAPC Trip matrix logic ALMCALH Logic for group alarm WRNCALH Logic for group warning Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 50
Line distance function name REL650 (A11) REL650 (A12) Monitoring CVMMXN Power system measurement CMMXU Current measurement VMMXU Voltage measurement phase-phase CMSQI Current sequence measurement VMSQI Voltage sequence measurement Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 51
Supervision status for IEC 60870-5-103 I103USRDEF Status for user defined signals for IEC 60870-5-103 L4UFCNT Event counter with limit supervision TEILGAPC Running hour meter Metering PCFCNT Pulse-counter logic ETPMMTR Function for energy calculation and demand handling Line distance protection REL650 2.2 IEC Technical manual...
GOOSE function block to receive a switching device MULTICMDRCV/ Multiple command and transmit 60/10 60/10 MULTICMDSND OPTICAL103 IEC 60870-5-103 Optical serial communication RS485103 IEC 60870-5-103 serial communication for RS485 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 53
Current reversal and weak-end infeed logic for distance protection ZCLCPSCH Local acceleration logic ECPSCH Scheme communication logic for residual overcurrent protection ECRWPSCH Current reversal and weak-end infeed logic for residual overcurrent protection Line distance protection REL650 2.2 IEC Technical manual...
Local HMI functions IEC 61850 or function ANSI Description name LHMICTRL Local HMI signals LANGUAGE Local human machine language SCREEN Local HMI Local human machine screen behavior Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 55
Parameter setting function for HMI in PCM600 FNKEYMD1– FNKEYMD5 LEDGEN General LED indication part for LHMI OPENCLOSE_LED LHMI LEDs for open and close keys GRP1_LED1– Basic part for CP HW LED indication module GRP1_LED15 GRP2_LED1– GRP2_LED15 GRP3_LED1– GRP3_LED15 Line distance protection REL650 2.2 IEC Technical manual...
ACT when a TRM is included in the configuration with the hardware configuration tool. In the SMT or the ACT, they can be mapped to the desired virtual input (SMAI) of the IED and used internally in the configuration. Line distance protection REL650 2.2 IEC Technical manual...
CH9(I) STRING Analogue current input 9 CH10(I) STRING Analogue current input 10 CH11(U) STRING Analogue voltage input 11 CH12(U) STRING Analogue voltage input 12 Settings SEMOD129840-4 v2 Dependent on ordered IED type. Line distance protection REL650 2.2 IEC Technical manual...
Page 60
MU10-L1U - L4U MU11-L1I - L4I MU11-L1U - L4U MU12-L1I - L4I MU12-L1U - L4U GUID-72A8BEE0-2430-4C94-A1E0-9B6A0D149FE2 v1 All the visible parameter selections that are visible are not supported by the 650-series IED. Line distance protection REL650 2.2 IEC Technical manual...
Page 61
Rated VT secondary voltage VTprim11 0.05 - 2000.00 0.05 400.00 Rated VT primary voltage VTsec12 0.001 - 999.999 0.001 110.000 Rated VT secondary voltage VTprim12 0.05 - 2000.00 0.05 400.00 Rated VT primary voltage Line distance protection REL650 2.2 IEC Technical manual...
Page 62
0.001 - 999.999 0.001 110.000 Rated VT secondary voltage VTprim10 0.05 - 2000.00 0.05 400.00 Rated VT primary voltage VTsec11 0.001 - 999.999 0.001 110.000 Rated VT secondary voltage Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 63
FromObject ToObject ToObject= towards protected object, ToObject FromObject= the opposite CTsec9 1 - 10 Rated CT secondary current CTprim9 1 - 99999 3000 Rated CT primary current Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Values (Range) Unit Description STATUS BOOLEAN 0=Ok Analogue input module 1=Error status PID-6598-MONITOREDDATA v6 Table 16: TRM_10I_2U Monitored data Name Type Values (Range) Unit Description STATUS BOOLEAN 0=Ok Analogue input module 1=Error status Line distance protection REL650 2.2 IEC Technical manual...
VTs are, therefore, basic data for the IED. The user has to set the rated secondary and primary currents and voltages of the CTs and VTs to provide the IED with their rated ratios. Line distance protection REL650 2.2 IEC Technical manual...
Screw compression type 250 V AC, 20 A 4 mm (AWG12) 2 x 2.5 mm (2 x AWG14) Terminal blocks suitable for 250 V AC, 20 A 4 mm (AWG12) ring lug terminals Line distance protection REL650 2.2 IEC Technical manual...
Settings GUID-07348953-4A72-444B-A31A-030ABEA8E0C4 v1 OscBlock must always be set to a value greater than OscRelease. If this is not done, oscillation detection will not function correctly, and the resulting behaviour will be undefined. Line distance protection REL650 2.2 IEC Technical manual...
^HM1L01R ^HM1L01Y ^HM1L01G IEC09000322 V1 EN-US Figure 5: GRP1_LED1 function block The GRP1_LED1 function block is an example. The 15 LEDs in each of the three groups have a similar function block. Line distance protection REL650 2.2 IEC Technical manual...
LEDGEN Non group settings (basic) Name Values (Range) Unit Step Default Description Operation Operation Off/On tRestart 0.0 - 100.0 Defines the disturbance length tMax 0.1 - 100.0 Maximum time for the definition of a disturbance Line distance protection REL650 2.2 IEC Technical manual...
Only the function block for the first button is shown above. There is a similar block for every function key button. 5.4.3 Signals PID-1657-INPUTSIGNALS v18 Table 28: FNKEYMD1 Input signals Name Type Default Description LEDCTL1 BOOLEAN LED control input for function key Line distance protection REL650 2.2 IEC Technical manual...
Step Default Description Type Function key type Menu shortcut Control MenuShortcut Menu shortcut for function key GUID-BCE87D54-C836-40EE-8DA7-779B767059AB v1 MenuShortcut values are product dependent and created dynamically depending on the product main menu. Line distance protection REL650 2.2 IEC Technical manual...
AMU0600442 v14 IEC13000239-3-en.vsd IEC13000239 V3 EN-US Figure 7: Local human-machine interface The LHMI of the IED contains the following elements: • Keypad • Display (LCD) • LED indicators • Communication port for PCM600 Line distance protection REL650 2.2 IEC Technical manual...
The push-buttons are also used to acknowledge alarms, reset indications, provide help and switch between local and remote control mode. The keypad also contains programmable push-buttons that can be configured either as menu shortcut or control buttons. Line distance protection REL650 2.2 IEC Technical manual...
Page 76
LHMI keypad with object control, navigation and command push- buttons and RJ-45 communication port 1...5 Function button Close Open Escape Left Down Right Enter Remote/Local Uplink LED Not in use Multipage Menu Line distance protection REL650 2.2 IEC Technical manual...
320 x 240 pixels. The character size can vary. The amount of characters and rows fitting the view depends on the character size and the view that is shown. The display view is divided into four basic areas. Line distance protection REL650 2.2 IEC Technical manual...
Page 78
If text, pictures or other items do not fit in the display, a vertical scroll bar appears on the right. The text in content area is truncated from the beginning if it does not fit in the display horizontally. Truncation is indicated with three dots. Line distance protection REL650 2.2 IEC Technical manual...
Page 79
Each function button has a LED indication that can be used as a feedback signal for the function button control action. The LED is connected to the required signal with PCM600. Line distance protection REL650 2.2 IEC Technical manual...
Pressing the ESC button clears the panel from the display. Both panels have a dynamic width that depends on the label string length. 5.5.1.3 LEDs AMU0600427 v13 The LHMI includes three status LEDs above the display: Ready, Start and Trip. Line distance protection REL650 2.2 IEC Technical manual...
Page 81
OPENCLOSE_LED function block. For instance, OPENCLOSE_LED can be connected to a circuit breaker to indicate the breaker open/close status on the LEDs. IEC16000076-1-en.vsd IEC16000076 V1 EN-US Figure 13: OPENCLOSE_LED connected to SXCBR Line distance protection REL650 2.2 IEC Technical manual...
BxRBDR binary input function block using the PCM600, and configuring the setting to Off, Start or Trip for that particular signal. 5.5.2.3 Indication LEDs Operating modes GUID-B67F1ED3-900B-4D34-8EEB-A3005999CE50 v4 Collecting mode Line distance protection REL650 2.2 IEC Technical manual...
Page 83
• Automatic reset • The automatic reset can only be performed for LED indications defined for re-starting mode with the latched sequence type 6 (LatchedReset-S). Line distance protection REL650 2.2 IEC Technical manual...
Page 84
This sequence follows the corresponding input signals all the time with a steady light. It does not react on acknowledgment or reset. Every LED is independent of the other LEDs in its operation. Line distance protection REL650 2.2 IEC Technical manual...
Page 85
If the signal is still present after acknowledgment it gets a steady light. Activating signal Acknow. en01000231.vsd IEC01000231 V1 EN-US Figure 17: Operating Sequence 3 LatchedAck-F-S GUID-CC607709-5344-4C88-AA97-6395FD335E55 v5 Line distance protection REL650 2.2 IEC Technical manual...
Page 86
19. Activating signal GREEN Activating signal YELLOW Activating signal RED Acknow. IEC09000314-1-en.vsd IEC09000314 V1 EN-US Figure 19: Operating sequence 3, three colors involved, alternative 1 GUID-071B9EB5-A1D2-49C5-9458-4D21B7E068BE v3 Line distance protection REL650 2.2 IEC Technical manual...
Page 87
That means if an indication with higher priority has reset while an indication with lower priority still is active at the time of reset, the LED will change color according to figure22. Line distance protection REL650 2.2 IEC Technical manual...
Page 88
LEDs set for sequence 6 are completely independent in its operation of LEDs set for other sequences. Timing diagram for sequence 6 SEMOD56072-86 v4 Figure shows the timing diagram for two indications within one disturbance. Line distance protection REL650 2.2 IEC Technical manual...
Page 89
Disturbance Disturbance tRestart tRestart Activating signal 1 Activating signal 2 LED 1 LED 2 Automatic reset Manual reset IEC01000240_2_en.vsd IEC01000240 V2 EN-US Figure 24: Operating sequence 6 (LatchedReset-S), two different disturbances Line distance protection REL650 2.2 IEC Technical manual...
Page 90
Disturbance tRestart Activating signal 1 Activating signal 2 LED 1 LED 2 Automatic reset Manual reset IEC01000242_2_en.vsd IEC01000242 V2 EN-US Figure 26: Operating sequence 6 (LatchedReset-S), manual reset Line distance protection REL650 2.2 IEC Technical manual...
In this mode the output toggles each time the function key has been pressed for more than 500ms. Note that the input attribute is reset each time the function block executes. The function block execution is marked with a dotted line below. Line distance protection REL650 2.2 IEC Technical manual...
Page 92
It has been implemented this way for safety reasons; the idea is that the function key LEDs should always reflect the actual status of any primary equipment monitored by these LEDs. Line distance protection REL650 2.2 IEC Technical manual...
The operation of the phase-selection element is primarily based on current change criteria (i.e. delta quantities), with significantly increased dependability. There is also a phase selection criterion operating in parallel which bases its operation only on voltage and current phasors. Line distance protection REL650 2.2 IEC Technical manual...
Trip in any phase or phases from zone 1 - forward direction TRL1Z1 BOOLEAN Trip in phase L1 from zone 1 - forward direction TRL2Z1 BOOLEAN Trip in phase L2 from zone 1 - forward direction Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 96
Start in phase L1 from zone RV - reverse direction STL2ZRV BOOLEAN Start in phase L2 from zone RV - reverse direction STL3ZRV BOOLEAN Start in phase L3 from zone RV - reverse direction Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Dead band & 5s Cyclic Dead band & 30s Cyclic Dead band & 1min Cyclic ZAngDbRepInt 1 - 100000 Type Cycl: Report interval (s), Db: In % of range, Int Db: In %s Line distance protection REL650 2.2 IEC Technical manual...
Resistance in phase L3 REAL Reactance in phase L3 L12R REAL Resistance in phase L1- L12X REAL Reactance in phase L1- L23R REAL Resistance in phase L2- Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
GUID-2432C04F-62E4-4817-9900-C830306FB4B0 v3 Settings, input and output names are sometimes mentioned in the following text without its zone suffix (i.e. BLKZx instead of BLKZ3) when the description is equally valid for all zones. Line distance protection REL650 2.2 IEC Technical manual...
So, a setting (CVTtype) is introduced in order to inform the algorithm about the type of CVT applied and Line distance protection REL650 2.2 IEC Technical manual...
Measurement in two phase-to-earth loops at the same time is associated with so-called simultaneous faults: two earth faults at the same time, one each on the two circuits of a double line, or when the Line distance protection REL650 2.2 IEC Technical manual...
L1 and L2 (L2 lagging L1). PolL1L2 is the current difference between phase L1 and L2 (L2 lagging L1). L1L2 The corresponding reverse directional sectors range from 165 to -60 degrees. Line distance protection REL650 2.2 IEC Technical manual...
Zone 1 has individual positive sequence impedance settings for phase-to-phase and phase-to-earth (X1PPZ1, R1PPZ1 and X1PEZ1, R1PEZ1). For the other zones, the positive sequence impedance reach is common for phase-to-phase and phase-to- earth (X1Zx, R1Zx). Line distance protection REL650 2.2 IEC Technical manual...
Page 105
(arc) may be divided into parts like for three-phase or phase-to-phase faults. The R1Zx + jX1Zx represent the positive sequence impedance from the measuring point to the fault location. Line distance protection REL650 2.2 IEC Technical manual...
Page 106
Zones 3 to 5 can be selected to be either forward or reverse with positive sequence polarized mho characteristic; alternatively self polarized offset mho characteristics. The operating characteristic is in accordance to figure where zone 5 is selected offset mho. Line distance protection REL650 2.2 IEC Technical manual...
Page 107
Forward or Reverse, directional lines are introduced. Information about the directional lines is given from the directional element. Basic Mho and offset Mho characteristics with different mode settings are indicated in figure 36. Line distance protection REL650 2.2 IEC Technical manual...
Page 108
The mho algorithm is based on the phase comparison of an operating phasor and a polarizing phasor. When the operating phasor leads the reference polarizing phasor by 90 degrees or more, the function operates and gives a trip output. Phase-to-phase fault SEMOD154224-240 v2 GUID-D162893C-918A-4DDA-AAC2-0D0A814D85C1 v1 Line distance protection REL650 2.2 IEC Technical manual...
Page 109
(x=2-5 and RV) X1Zx is the positive sequence reactance reach for zone x (x=2-5 and RV) is the polarizing voltage Operation occurs if 90°≤β≤270° Line distance protection REL650 2.2 IEC Technical manual...
Page 110
The angle β for L1 to L2 fault can be defined according to equation below. (Equation 6) IECEQUATION15008 V2 EN-US Line distance protection REL650 2.2 IEC Technical manual...
Page 111
Compensation for earth return path for faults involving earth is done by setting the positive and zero sequence impedance of the line. It is known that the ground compensation factor K Line distance protection REL650 2.2 IEC Technical manual...
Page 112
L1 is the complex positive sequence impedance of the line in Ω/phase for phase-to-earth fault in zone direction is the polarizing voltage for phase L1 Line distance protection REL650 2.2 IEC Technical manual...
Page 113
40. The angle will be 90° for fault location on the boundary of the circle. (Equation 9) IECEQUATION15022 V2 EN-US Line distance protection REL650 2.2 IEC Technical manual...
The IED has a built in feature which shapes the characteristic according to the characteristic shown in figure 41. The load encroachment algorithm will increase Line distance protection REL650 2.2 IEC Technical manual...
(RV) signals. The internal input 'IN present' is activated if the residual current (3I0) exceeds 10% of the maximum phase current magnitude and at the same time is above 5% of [1] RLdRv=RLdRvFactor*RLdFw Line distance protection REL650 2.2 IEC Technical manual...
Overfunction, when the measured quantity exceeds the High limit (XHiLim) or High-high limit (XHiHiLim) pre-set values • Underfunction, when the measured quantity decreases under the Low limit (XLowLim) or Low-low limit (XLowLowLim) pre-set values. X_RANGE is illustrated in figure 49. Line distance protection REL650 2.2 IEC Technical manual...
Page 123
Amplitude Deadband and 1min cyclic Cyclic reporting SEMOD54417-158 v3 The cyclic reporting of measured value is performed according to chosen setting (XRepTyp). The measuring channel reports the value independent of amplitude or integral dead-band reporting. Line distance protection REL650 2.2 IEC Technical manual...
Page 124
The picture is simplified: the process is not continuous but the values are evaluated with a time interval of one execution cycle from each other. Line distance protection REL650 2.2 IEC Technical manual...
Page 125
(as well as for the values Y3, Y4 and Y5). The integral dead-band supervision is particularly suitable for monitoring signals with small variations that can last for relatively long periods. Line distance protection REL650 2.2 IEC Technical manual...
Page 126
2% of IBase, the resistance and reactance of the impedance are forced to 99 999 ohm, corresponding to a magnitude at 141419 (99 999*√2) ohm and an angle at 45 degree. Line distance protection REL650 2.2 IEC Technical manual...
±0.2% of set value or ±35 ms whichever and Ph-Ph operation is greater Operate time 24 ms typically, IEC 60255-121 Reset time at 0.1 to 2 x Zreach Min. = 20 ms Max. = 35 ms Line distance protection REL650 2.2 IEC Technical manual...
Table 38: ZMRPSB Input signals Name Type Default Description GROUP Group signal for current input SIGNAL GROUP Group signal for voltage input SIGNAL BLOCK BOOLEAN Block of function Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
The impedance and the characteristic passing times are measured in all three phases separately. One-out-of-three or two-out-of-three operating modes can be selected according to the specific system operating conditions. Line distance protection REL650 2.2 IEC Technical manual...
To avoid load encroachment, the resistive reach is limited in forward direction by setting the parameter RLdOutFw which is the outer resistive load boundary value while the inner resistive boundary is calculated according to equation 12. Line distance protection REL650 2.2 IEC Technical manual...
The inner resistive characteristic in the second quadrant outside the load encroachment part corresponds to the setting parameter R1FInRv for the inner boundary. The outer boundary is internally calculated as the sum of DRv+R1FInRv. Line distance protection REL650 2.2 IEC Technical manual...
The tP2 timer become activated for the detection of the consecutive swings, if the measured impedance exit the operate area and returns within the time delay, set on the tW waiting timer. The upper part Line distance protection REL650 2.2 IEC Technical manual...
Page 134
Detection of power swing in phase L1 DET-L1 DET-L2 DET1of3 - int. >1 DET-L3 & DET2of3 - int. >1 & & IEC01000057-2-en.vsd IEC01000057-TIFF V2 EN-US Figure 56: Detection of power swing for 1-of-3 and 2-of-3 operating mode Line distance protection REL650 2.2 IEC Technical manual...
OperationLdCh = Off, but notice that the DFw and DRv will still be calculated from RLdOutFw and RLdOutRv. The characteristic will in this case be only quadrilateral. There are four different ways to form the internal INHIBIT signal: Line distance protection REL650 2.2 IEC Technical manual...
SIGNAL BLOCK BOOLEAN Block of function START_DLYD BOOLEAN Start from function to be accelerated with delay by SOTF BOOLEAN External enabling of SOTF ZACC BOOLEAN Distance zone to be accelerated by SOTF Line distance protection REL650 2.2 IEC Technical manual...
PID-3875-MONITOREDDATA v7 Table 48: ZCVPSOF Monitored data Name Type Values (Range) Unit Description REAL Current in phase L1 REAL Current in phase L2 REAL Current in phase L3 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Mode = UILevel; TRIP is released if UILevel detector is activated • Mode = UILvl&Imp; TRIP is released based either on the impedance- measured criteria or UILevel detection The ZCVPSOF function can be blocked by activating the input BLOCK. Line distance protection REL650 2.2 IEC Technical manual...
Delay time for activation of dead line detection (0.000-60.000) s ±0.2% or ±20 ms whichever is greater Drop-off delay time of switch onto fault function (0.000-60.000) s ±0.2% or ±30 ms whichever is greater Line distance protection REL650 2.2 IEC Technical manual...
The protection function performs a simple summation of the currents of the two channels I3P1 and I3P2. Line distance protection REL650 2.2 IEC Technical manual...
Generator rotates faster than the system during pole slip MOTMODE BOOLEAN Generator rotates slower than the system during pole slip REAL Real part of measured positive-sequence impedance % of UBase/(sqrt(3)*IBase) Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Real part of source impedance behind relay, in % of UBase/(sqrt(3)*IBase) ReverseX 0.00 - 1000.00 0.01 10.00 Imag. part of source impedance behind relay, in % of UBase/(sqrt(3)*IBase) InvertCTCurr Invert current direction Line distance protection REL650 2.2 IEC Technical manual...
When displayed in the complex impedance plane, these changes are characterized by a cyclic change in the complex load impedance Z(R, X) as measured at the terminals of the generator, or at the location of the Line distance protection REL650 2.2 IEC Technical manual...
Page 145
Measurement of the rotor (power) angle δ is important as well. Line distance protection REL650 2.2 IEC Technical manual...
Page 146
In order to be able to fully understand the principles of OOSPPAM, a stable case, that is, a case where the disturbance does not make a generator to go out-of-step, must be shown. Line distance protection REL650 2.2 IEC Technical manual...
10% wider than the the circle that has the line SE-RE as diameter (that is the out-of-step characteristic which corresponds to the rotor (power) angle of 90 degrees). Figure illustrates construction of the lens characteristic for a power system. Line distance protection REL650 2.2 IEC Technical manual...
Page 148
Figure the relay is connected to the terminals of the generator and, therefore, the previous quantities shall be referred to Line distance protection REL650 2.2 IEC Technical manual...
Z lies practically on, or very near, the Z-line. Transition of the measured Z from point 0 to point 1 takes app. 20 ms, due to Fourier filters. Point 2: Z immediately after the fault has been cleared. Transition of Line distance protection REL650 2.2 IEC Technical manual...
In other words, if we consider a linear increase of frequency from 50 Hz to 57.777 Hz, at least three pole-slips will occur (in fact: (57.777 - 50) / 2 = 3.889). The exact instantaneous slip-frequency expressed in Hz (corresponding to Line distance protection REL650 2.2 IEC Technical manual...
(0), then the alternative setting TripAngle decides when the trip command is given. If specified tBreaker > 0, for example tBreaker = 0.040 second, then automatically, the TripAngle is ignored and the second, more exact method applied. Line distance protection REL650 2.2 IEC Technical manual...
Page 152
← tBreaker = 60 ms → rotor angle ← angle towards 0° 1000 1200 Time in milliseconds → IEC10000115-1-en.vsd IEC10000115 V1 EN-US Figure 67: Trip initiation when the break-time of the circuit breaker is known Line distance protection REL650 2.2 IEC Technical manual...
Open Open a zone? a zone? circuit circuit ROTORANG ROTORANG UCOSPHI UCOSPHI ZONE 1 ZONE 1 TRIPZ2 TRIPZ2 breaker breaker safely safely IEC10000116-3-en.vsd IEC10000116 V3 EN-US Figure 68: OOSPPAM Simplified function block Line distance protection REL650 2.2 IEC Technical manual...
If PPL2PHIZ is unable to detect both faulty phases, then it is not possible to provide preference. The distance protection will still be released however, without preference. The final result might be that both faulty feeders are Line distance protection REL650 2.2 IEC Technical manual...
Release condition for the L3 to earth loop PID-6809-OUTPUTSIGNALS v2 Table 59: PPL2PHIZ Output signals Name Type Description START BOOLEAN Indicates start for earth fault(s), regardless of direction ZREL INTEGER Integer coded output release signal Line distance protection REL650 2.2 IEC Technical manual...
Figure 70. The phase selection inside the distance protection has to detect the fault before an operation from the distance zones can be achieved, even when the distance protection is released by PPL2PHIZ. Line distance protection REL650 2.2 IEC Technical manual...
The time delay for residual current start is also bypassed as soon as two low voltages are detected during the cross-country fault (startUPP). See Figure 71. Line distance protection REL650 2.2 IEC Technical manual...
IEC16000019 V1 EN-US Figure 72: Phase selection The voltage phase selection can be complemented with external phase selection through inputs RELL1-3N. Voltage phase selection is disabled in No Filter and NoPref operating modes. Line distance protection REL650 2.2 IEC Technical manual...
The ‘NoPref’ mode uses only the residual current criteria (startIN). There is no preference provided in this mode. All three phase-to-earth loops of the distance protection releases when a residual current start has occurred. Line distance protection REL650 2.2 IEC Technical manual...
Page 160
40 ms from the activation of the residual current start. Hence, if there is a residual current start, it is guaranteed that the distance protection is released in at least one phase. This is valid for all phase preference schemes. Line distance protection REL650 2.2 IEC Technical manual...
Page 161
Preferred phase for each cross-country fault type and operating mode Operating mode start in L1 & L2 start in L2 & L3 start in L3 & L1 1231c 1321c 123a 132a 213a 231a 312a 321a Line distance protection REL650 2.2 IEC Technical manual...
PPL2PHIZ is designed not to have any influence on the phase-to- phase loops of the distance protection. startU zrelL1 zrelL2 zrelL3 ZREL Bool to TRUE L1L2 Integer TRUE L2L3 BLOCK TRUE L3L1 IEC16000025-1-en.vsdx IEC16000025 V1 EN-US Figure 78: Output Line distance protection REL650 2.2 IEC Technical manual...
(0.000 - 60.000) s ±0.2% or ±25 ms residual voltage at 1.2 to 0.8 x whichever is greater Operating mode No Filter, NoPref Cyclic: 1231c, 1321c Acyclic: 123a, 132a, 213a, 231a, 312a, 321a Line distance protection REL650 2.2 IEC Technical manual...
7.1.4 Signals IP11433-1 v2 PID-6914-INPUTSIGNALS v3 Table 64: PHPIOC Input signals Name Type Default Description GROUP Three phase current SIGNAL BLOCK BOOLEAN Block of function ENMULT BOOLEAN Enable current start value multiplier Line distance protection REL650 2.2 IEC Technical manual...
Value groups 7.1.6 Monitored data PID-6914-MONITOREDDATA v3 Table 69: PHPIOC Monitored data Name Type Values (Range) Unit Description REAL Current in phase L1 REAL Current in phase L2 REAL Current in phase L3 Line distance protection REL650 2.2 IEC Technical manual...
Figure 80. IP>>Max IP>>_used IP>> IP>>Min IEC17000016-1-en.vsdx IEC17000016 V1 EN-US Figure 80: Logic for limitation of used operation current value PHPIOC can be blocked using the binary input BLOCK. Line distance protection REL650 2.2 IEC Technical manual...
Directional phase overcurrent protection, four steps (OC4PTOC) has an inverse or definite time delay for each step. All IEC and ANSI inverse time characteristics are available together with an optional user defined time characteristic. Line distance protection REL650 2.2 IEC Technical manual...
Trip signal from step2 phase L2 TR2L3 BOOLEAN Trip signal from step2 phase L3 TR3L1 BOOLEAN Trip signal from step3 phase L1 TR3L2 BOOLEAN Trip signal from step3 phase L2 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Values (Range) Unit Step Default Description Operation Operation Off / On AngleRCA 40 - 65 Relay characteristic angle (RCA) AngleROA 40 - 89 Relay operation angle (ROA) Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 172
1 I1Mult 1.0 - 10.0 Multiplier for current operate level for step 1 DirMode2 Non-directional Directional mode of step 2 (off, nodir, Non-directional forward, reverse) Forward Reverse Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 173
Operating phase current level for step 3 in % of IBase 0.000 - 60.000 0.001 0.800 Def time delay or add time delay for inverse char of step 3 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 174
5 - 2500 Minimum used operating phase current level for step 1 in % of IBase, if I1> is less than I1>Min then I1> is set to I1>Min Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 175
0.005 - 100.000 0.001 13.500 Parameter TR for customer programmable curve for step 2 tCRCrv2 0.1 - 10.0 Parameter CR for customer programmable curve for step 2 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 176
0.00 - 20.00 0.01 0.00 Parameter B for customer programmable curve for step 4 tCCrv4 0.1 - 10.0 Parameter C for customer programmable curve for step 4 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
For each step x , where x is step 1, 2, 3 and 4, an operation mode is set by DirModex: Off/Non-directional/Forward/Reverse. The protection design can be divided into four parts: Line distance protection REL650 2.2 IEC Technical manual...
Page 178
If the RMS option is selected, then the true RMS value is used. The true RMS value includes the contribution from the current DC component as well as from the higher current harmonic in addition to the fundamental frequency component. Line distance protection REL650 2.2 IEC Technical manual...
Page 180
The directional setting is given as a characteristic angle AngleRCA for the function and an angle window ROADir. Reverse Forward en05000745.vsd IEC05000745 V1 EN-US Figure 83: Directional characteristic of the phase overcurrent protection Line distance protection REL650 2.2 IEC Technical manual...
Page 181
The possibilities for inverse time characteristics are described in section "Inverse characteristics". Characteristx=DefTime a>b Ix> BLKSTx BLOCK Inverse Characteristx=Inverse STAGEx_DIR_Int DirModex=Off DirModex=Non-directional DirModex=Forward FORWARD_Int DirModex=Reverse REVERSE_Int IEC12000008.vsd IEC12000008.vsd IEC12000008 V2 EN-US Figure 84: Simplified logic diagram for OC4PTOC Line distance protection REL650 2.2 IEC Technical manual...
Page 182
Ix>Min, the limits are swapped. The principle of the limitation is shown in Figure 86. Ix>Max Ix>_used Ix> Ix>Min IEC17000018-1-en.vsdx IEC17000018 V1 EN-US Figure 86: Logic for limitation of used operation current value Line distance protection REL650 2.2 IEC Technical manual...
Page 183
2ndHarmStab setting, any of the four overcurrent stages can be selectively blocked by the parameter HarmBlockx setting. When the 2nd harmonic restraint feature is active, the OC4PTOC function output signal ST2NDHRM will be set to the logical value one. Line distance protection REL650 2.2 IEC Technical manual...
Reset time, start non-directional at 10 x I Min. = 20 ms Max. = 35 ms Critical impulse time 10 ms typically at 0 to 2 x I Impulse margin time 15 ms typically Line distance protection REL650 2.2 IEC Technical manual...
PID-6915-INPUTSIGNALS v4 Table 79: EFPIOC Input signals Name Type Default Description GROUP Three phase currents SIGNAL BLOCK BOOLEAN Block of function BLKAR BOOLEAN Block input for auto reclose ENMULT BOOLEAN Enable current multiplier Line distance protection REL650 2.2 IEC Technical manual...
The sampled analog residual currents are pre-processed in a discrete Fourier filter (DFT) block. From the fundamental frequency components of the residual current, as well as from the sample values the equivalent RMS value is derived. This Line distance protection REL650 2.2 IEC Technical manual...
Operate time at 0 to 2 x I Min. = 15 ms Max. = 25 ms Reset time at 2 x I to 0 Min. = 15 ms Max. = 25 ms Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
A second harmonic blocking can be set individually for each step. Directional operation can be combined together with the corresponding communication logic in permissive or blocking teleprotection scheme. The current reversal and weak-end infeed functionality are available as well. Line distance protection REL650 2.2 IEC Technical manual...
When activated, the current multiplier is in use for step1 ENMULT2 BOOLEAN When activated, the current multiplier is in use for step2 ENMULT3 BOOLEAN When activated, the current multiplier is in use for step3 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
-180 - 180 Relay Characteristic Angle (RCA) polMethod Voltage Voltage Type of polarization Current Dual UPolMin 1 - 100 Minimum voltage level for polarization in % of UBase Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 191
Pos / CB Command) tUnderTime 0.000 - 60.000 0.001 0.300 Time delay for under time DirMode1 Non-directional Directional mode of step 1 (Off, Non-dir, Non-directional Forward, Reverse) Forward Reverse Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 192
IEC L.T. inv. IEC Def. Time Reserved Programmable RI type RD type IN2> 1 - 2500 Residual current operate level for step 2 in % of IBase Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 193
3 HarmBlock3 Enable block of step 3 from harmonic restrain DirMode4 Non-directional Directional mode of step 4 (Off, Non-dir, Non-directional Forward, Reverse) Forward Reverse Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 194
Param P for customized inverse trip time curve for step 1 tACrv1 0.005 - 200.000 0.001 13.500 Param A for customized inverse trip time curve for step 1 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 195
0.000 - 60.000 0.001 0.020 Reset time delay for step 3 tPCrv3 0.005 - 3.000 0.001 1.000 Param P for customized inverse trip time curve for step 3 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 196
Choice of measurand for directional Neg seq current SeqTypeIPol Zero seq Zero seq Choice of measurand for polarizing Neg seq current SeqTypeUPol Zero seq Zero seq Choice of measurand for polarizing Neg seq voltage Line distance protection REL650 2.2 IEC Technical manual...
(when a dedicated CT input of the IED is connected in PCM600 to the fourth analog input of the pre-processing block connected to EF4PTOC function input I3P). This dedicated IED CT input can be, for example, connected to: Line distance protection REL650 2.2 IEC Technical manual...
The function can be set to use voltage polarizing, current polarizing or dual polarizing. Voltage polarizing When voltage polarizing is selected, the protection will use the residual voltage as the polarizing quantity U3P. Line distance protection REL650 2.2 IEC Technical manual...
Page 199
EF4PTOC function input I3PPOL). This dedicated IED CT input is then typically connected to one single current transformer located between power system star point and earth (current transformer located in the star point of a star connected transformer winding). Line distance protection REL650 2.2 IEC Technical manual...
Page 200
Then the phasor of the total polarizing voltage UTotPol will be used, together with the phasor of the operating current, to determine the direction of the earth fault (forward/reverse). Line distance protection REL650 2.2 IEC Technical manual...
7.4.7.7 Four residual overcurrent steps M13941-166 v8 Each overcurrent step uses operating quantity Iop (residual current) as the measuring quantity. Each of the four residual overcurrent steps has the following built-in facilities: Line distance protection REL650 2.2 IEC Technical manual...
Page 202
The principle of the limitation is shown in Figure 91. INx>Max INx>_used INx> INx>Min IEC17000017-1-en.vsdx IEC17000017 V1 EN-US Figure 91: Logic for limitation of used operation current value Simplified logic diagram for one residual overcurrent step is shown in Figure 92. Line distance protection REL650 2.2 IEC Technical manual...
When polMethod = Voltage, UPol will be used as polarizing quantity. When polMethod = Current, IPol will be used as polarizing quantity. When polMethod = Dual, UPol + IPol · ZNPol will be used as polarizing quantity. Line distance protection REL650 2.2 IEC Technical manual...
Page 204
STRV=1 when operating quantity magnitude Iop x cos(φ - AngleRCA) is bigger than 60% of setting parameter IN>Dir and directional supervision element detects fault in reverse direction. Line distance protection REL650 2.2 IEC Technical manual...
(defined by parameter 2ndHarmStab), output signal 2NDHARMD is set to logical value one and the harmonic restraining feature to the function block will be applicable. Blocking from the 2nd harmonic element activates if all of three criteria are satisfied: Line distance protection REL650 2.2 IEC Technical manual...
Page 206
UseStartValue (see condition 3 above). Simplified logic diagram for 2 harmonic blocking feature is shown in Figure 95. Line distance protection REL650 2.2 IEC Technical manual...
StepForSOTF. The setting parameter ActivationSOTF can be set for activation of CB position open change, CB position closed change or CB close command. In case of a residual current start from step 2 or 3 (dependent on Line distance protection REL650 2.2 IEC Technical manual...
Page 208
ActUnderTime Close command STIN4 IEC06000643-5-en.vsdx IEC06000643 V5 EN-US Figure 96: Simplified logic diagram for SOTF and under-time features M13941-3 v6 Simplified logic diagram for the complete EF4PTOC function is shown in Figure Line distance protection REL650 2.2 IEC Technical manual...
(0.000-60.000) s ±0.2% or ±35 ms whichever is greater Minimum operate time for inverse curves, (0.000 - 60.000) s ±0.2% or ±35 ms step 1-4 whichever is greater Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Four step directional negative phase sequence overcurrent protection (NS4PTOC) has an inverse or definite time delay independent for each step separately. All IEC and ANSI time delayed characteristics are available together with an optional user defined characteristic. Line distance protection REL650 2.2 IEC Technical manual...
BLOCK BOOLEAN General block BLKTR BOOLEAN Block of trip BLKST1 BOOLEAN Block of step 1 (Start and trip) BLKST2 BOOLEAN Block of step 2 (Start and trip) Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
UPolMin 1 - 100 Minimum voltage level for polarization in % of UBase I2>Dir 1 - 100 Residual current level in % of IBase for Direction release Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 213
L.T. inv. IEC Norm. inv. IEC Very inv. IEC inv. IEC Ext. inv. IEC S.T. inv. IEC L.T. inv. IEC Def. Time Reserved Programmable RI type RD type Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 214
1.0 - 10.0 Multiplier for scaling the current setting value for step 3 DirMode4 Non-directional Directional mode of step 4 (off, nodir, Non-directional forward, reverse) Forward Reverse Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 215
0.001 13.500 Param TR for customized inverse reset time curve for step tCRCrv1 0.1 - 10.0 Param CR for customized inverse reset time curve for step 1 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 216
0.00 Param B for customized inverse trip time curve for step 4 tCCrv4 0.1 - 10.0 Param C for customized inverse trip time curve for step 4 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
(I2) for its operating quantity. The negative sequence current is calculated from three-phase current input within the IED. The pre-processing block calculates I2 from the first three inputs into the pre- processing block by using the following formula: Line distance protection REL650 2.2 IEC Technical manual...
To use this all three phase-to-earth voltages must be connected to three IED VT inputs. This phasor is used together with the phasor of the operating current, in order to determine the direction to the fault (Forward/Reverse).To enable voltage polarizing Line distance protection REL650 2.2 IEC Technical manual...
For the complete list of available inverse curves, refer to Chapter "Inverse characteristics" • Type of reset characteristic (Instantaneous / IEC Reset /ANSI reset).By this parameter setting it is possible to select the reset characteristic of the stage. For Line distance protection REL650 2.2 IEC Technical manual...
Directional supervision element with integrated directional comparison function GUID-F54E21F7-7C99-41D6-BEC6-2D6EC6D2B2A3 v3 At least one of the four negative sequence overcurrent steps must be set as directional in order to enable execution of the directional Line distance protection REL650 2.2 IEC Technical manual...
Page 221
40% of I>Dir and the directional condition is fulfilled in set direction. • Relay characteristic angle AngleRCA which defines the position of forward and reverse areas in the operating characteristic. Directional comparison step, built-in within directional supervision element, set NS4PTOC output binary signals: Line distance protection REL650 2.2 IEC Technical manual...
Sensitive directional residual overcurrent and power protection SDEPSDE SEMOD171436-1 v4 7.6.1 Identification SEMOD172025-2 v4 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Sensitive directional residual over SDEPSDE current and power protection Line distance protection REL650 2.2 IEC Technical manual...
In such networks, the active fault current would be small and by using sensitive directional residual power protection, the operating quantity is elevated. Therefore, better Line distance protection REL650 2.2 IEC Technical manual...
Start of directional function for a fault in reverse direction STDIR INTEGER Direction of fault. A general signal common to all three mode of residual over current protection UNREL BOOLEAN Residual voltage release of operation of all directional modes Line distance protection REL650 2.2 IEC Technical manual...
L.T. inv. IEC Norm. inv. IEC Very inv. IEC inv. IEC Ext. inv. IEC S.T. inv. IEC L.T. inv. IEC Def. Time Reserved Programmable RI type RD type Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 228
Global base selection for function groups Table 105: SDEPSDE Non group settings (advanced) Name Values (Range) Unit Step Default Description RotResU 0 deg 180 deg Setting for rotating polarizing quantity if 180 deg necessary Line distance protection REL650 2.2 IEC Technical manual...
RCADir is set equal to -90° in an isolated network as all currents are mainly capacitive. The function operates when 3I ·cos φ gets larger than the set value. Line distance protection REL650 2.2 IEC Technical manual...
Page 230
If the output signals START and STDIRIN remain active for the set delay tDef the binary output signals TRIP and TRDIRIN get activated. The trip from this sub-function has definite time delay. Line distance protection REL650 2.2 IEC Technical manual...
Page 231
·cos (φ + 180°) ≥ the set value. It is also possible to tilt the characteristic to compensate for current transformer angle error with a setting RCAComp as shown in the Figure 107: Line distance protection REL650 2.2 IEC Technical manual...
Page 232
(setting kSN) the binary output signals TRIP and TRDIRIN get activated. The function shall indicate forward/reverse direction to the fault. Reverse direction ·cos (φ + 180°) ³ the set value. is defined as 3I · 3U Line distance protection REL650 2.2 IEC Technical manual...
Page 233
TRIP and TRDIRIN get activated. The function indicates forward/reverse direction to the fault. Reverse direction is defined as φ is within the angle sector: RCADir + 180° ± ROADir This variant has definite time delay. Line distance protection REL650 2.2 IEC Technical manual...
Page 234
When the function picks up, binary output signal STUN is activated. If the output signal STUN is active for the set delay tUNNonDir, the binary output signals TRIP and TRUN get activated. A simplified logical diagram of the total function is shown in Figure 109. Line distance protection REL650 2.2 IEC Technical manual...
±1.0% of I at I > I Operate level for non-directional overcurrent (1.00-400.00)% of IBase ±1.0% of I at I £ I ±1.0% of I at I > I Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
PID-3908-INPUTSIGNALS v7 Table 108: LCPTTR Input signals Name Type Default Description GROUP Group signal for current input SIGNAL BLOCK BOOLEAN Block of function BLKTR BOOLEAN Block of trip Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 238
BOOLEAN Alarm signal LOCKOUT BOOLEAN Lockout signal PID-3909-OUTPUTSIGNALS v8 Table 111: LFPTTR Output signals Name Type Description TRIP BOOLEAN Trip START BOOLEAN Start Signal ALARM BOOLEAN Alarm signal LOCKOUT BOOLEAN Lockout signal Line distance protection REL650 2.2 IEC Technical manual...
Time constant of the line in minutes. AlarmTemp 0 - 400 Deg F Temperature level for start (alarm) TripTemp 0 - 600 Deg F Temperature level for trip Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Estimated time to reset of lockout (in min) TEMP REAL Temperature Calculated temperature Fahrenheit of the device TEMPAMB REAL Temperature Ambient temperature Fahrenheit used in the calculations TERMLOAD REAL Temperature relative to operate temperature Line distance protection REL650 2.2 IEC Technical manual...
The actual temperature of the protected component (line or cable) is calculated by adding the ambient temperature to the calculated temperature, as shown above. The ambient temperature can be taken from a separate sensor or can be given a constant Line distance protection REL650 2.2 IEC Technical manual...
Page 242
The protection has a reset input: RESET. By activating this input the calculated temperature is reset to its default initial value. This is useful during testing when secondary injected current has given a calculated “false” temperature level. Line distance protection REL650 2.2 IEC Technical manual...
Page 243
Lockout logic Actual Temp < Recl Temp BLOCK TTRIP Calculation of time to trip BLKTR TENRECL Calculation of time to reset of lockout IEC09000637-2-en.vsd IEC09000637 V2 EN-US Figure 111: Functional overview of LCPTTR/LFPTTR Line distance protection REL650 2.2 IEC Technical manual...
Breaker failure protection (CCRBRF) ensures a fast backup tripping of the surrounding breakers in case the own breaker fails to open. CCRBRF can be current-based, contact-based or an adaptive combination of these two conditions. Line distance protection REL650 2.2 IEC Technical manual...
The re-trip function can be done with or without CB position check according to table 125. Line distance protection REL650 2.2 IEC Technical manual...
Page 248
• It is possible to have instantaneous back-up trip function if a signal is high if the circuit breaker is incapable to clear faults, for example at low gas pressure. Line distance protection REL650 2.2 IEC Technical manual...
Page 249
Retrip Time Out L1 TRRETL2 phases tPulse TRRETL1 RetripMode No CBPos Check 30ms CB Pos Check CB Closed L1 CBFLT IEC09000978-4-en.vsd IEC09000978 V4 EN-US Figure 115: Simplified logic scheme of the retrip logic function Line distance protection REL650 2.2 IEC Technical manual...
±1.0% of I at I > I Reset ratio > 95% Operate time for current detection 10 ms typically Reset time for current detection 15 ms maximum Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
The Pole discordance protection function (CCPDSC) operates based on information from auxiliary contacts of the circuit breaker for the three phases with additional criteria from unsymmetrical phase currents when required. Line distance protection REL650 2.2 IEC Technical manual...
BOOLEAN Pole three closed indication from CB PID-3525-OUTPUTSIGNALS v8 Table 128: CCPDSC Output signals Name Type Description TRIP BOOLEAN Trip signal to CB START BOOLEAN Trip condition TRUE, waiting for time delay Line distance protection REL650 2.2 IEC Technical manual...
The detection of pole discordance can be made in two different ways. If the contact based function is used an external logic can be made by connecting the auxiliary contacts of the circuit breaker so that a pole discordance is indicated, see figure 118. Line distance protection REL650 2.2 IEC Technical manual...
Page 254
CurrUnsymLevel times the largest phase current the settable trip timer (tTrip) is started. The tTrip timer gives a trip signal after the set delay. The TRIP signal is a pulse 150 ms long. The current based pole discordance function can be Line distance protection REL650 2.2 IEC Technical manual...
Page 255
It can be connected to the output signal 1PT1 on SMBRRECfunction block. If the autoreclosing function is an external device, then BLKDBYAR has to be connected to a binary input in the IED and this binary input Line distance protection REL650 2.2 IEC Technical manual...
(that is from auxiliary contacts of the close and open push buttons) or may be software connected to the outputs of other integrated functions (that is close command from a control function or a general trip from integrated protections). Line distance protection REL650 2.2 IEC Technical manual...
Selection of one of the Global Base Value groups 7.10.6 Monitored data PID-3858-MONITOREDDATA v6 Table 138: VRPVOC Monitored data Name Type Values (Range) Unit Description IMAX REAL Maximum phase current magnitude UUMIN REAL Minimum ph-to-ph voltage magnitude Line distance protection REL650 2.2 IEC Technical manual...
122. The voltage restrained characteristic is defined by the two points: (0.25*UBase ; VDepFact *StartCurr/100*IBase) and (UHighLimit/ 100*UBase; StartCurr/100*IBase). In the first point the factor 0.25 that multiply UBase cannot be changed. Line distance protection REL650 2.2 IEC Technical manual...
Page 261
Start level of the current StartCurr VDepFact * StartCurr UHighLimit UBase IEC10000124-2-en.vsd IEC10000124 V2 EN-US Figure 123: Example for start level of the current variation as function of measured voltage magnitude in Step mode of operation Line distance protection REL650 2.2 IEC Technical manual...
The start signal starts a definite time delay. If the value of the start signal is logical TRUE for longer than the set time delay, the undervoltage step sets its trip signal to logical TRUE. Line distance protection REL650 2.2 IEC Technical manual...
10 ms typically at 0 to 2 x I Impulse margin time 15 ms typically Undervoltage: Critical impulse time 10ms typically at 2 x U to 0 Impulse margin time 15 ms typically Line distance protection REL650 2.2 IEC Technical manual...
UV2PTUV has two voltage steps, each with inverse or definite time delay. It has a high reset ratio to allow settings close to the system service voltage. Line distance protection REL650 2.2 IEC Technical manual...
Common trip signal from step2 TR2L1 BOOLEAN Trip signal from step2 phase L1 TR2L2 BOOLEAN Trip signal from step2 phase L2 TR2L3 BOOLEAN Trip signal from step2 phase L3 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Time delay of internal (low level) blocking for step 1 HystAbs1 0.0 - 50.0 Absolute hysteresis in % of UBase, step OperationStep2 Enable execution of step 2 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 268
Reset time delay used in IEC Definite Time curve step 2 ResetTypeCrv2 Instantaneous Instantaneous Selection of used IDMT reset curve type Frozen timer for step 2 Linearly decreased Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
To avoid an unwanted trip due to the disconnection of the related high-voltage equipment, a voltage-controlled blocking of the function is Line distance protection REL650 2.2 IEC Technical manual...
A • inverse curve B • customer programmable inverse curve The type A curve is described as: æ ö < - ç ÷ < è ø (Equation 38) EQUATION1431 V2 EN-US Line distance protection REL650 2.2 IEC Technical manual...
Page 271
> (Equation 41) EQUATION1435 V1 EN-US The lowest voltage is always used for the inverse time delay integration. The details of the different inverse time characteristics are shown in section "Inverse characteristics". Line distance protection REL650 2.2 IEC Technical manual...
Page 272
See figure and figure 129. Line distance protection REL650 2.2 IEC Technical manual...
Page 273
Frozen Timer Time Linearly Instantaneous decreased IEC05000010-4-en.vsd IEC05000010 V4 EN-US Figure 128: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay at different reset types Line distance protection REL650 2.2 IEC Technical manual...
Page 274
130. Detailed information about individual stage reset/operation behavior is shown in figure and figure respectively. Note that by setting tResetn = 0.0s, instantaneous reset of the definite time delayed stage is ensured. Line distance protection REL650 2.2 IEC Technical manual...
Page 275
Voltage protection tReset1 a<b U1< IEC09000785-3-en.vsd IEC09000785 V3 EN-US Figure 130: Logic diagram for step 1, DT operation U1< tReset1 IEC10000039-3-en.vsd IEC10000039 V3 EN-US Figure 131: Example for Definite Time Delay stage1 reset Line distance protection REL650 2.2 IEC Technical manual...
The event will START both the under voltage function and the blocking function, as seen in figure 133. The delay of the blocking function must be set less than the time delay of under voltage function. Line distance protection REL650 2.2 IEC Technical manual...
A special logic is included to achieve the 1 out of 3, 2 out of 3 and 3 out of 3 criteria to fulfill the START condition. The design of Two step undervoltage protection UV2PTUV is schematically shown in Figure 134. Line distance protection REL650 2.2 IEC Technical manual...
(1.0–100.0)% of ±0.5% of U UBase Absolute hysteresis (0.0–50.0)% of ±0.5% of U UBase Internal blocking level, step 1 and step 2 (1–50)% of ±0.5% of U Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
When triggered, the function will cause an alarm, switch in reactors, or switch out capacitor banks. OV2PTOV has two voltage steps, each of them with inverse or definite time delayed. Line distance protection REL650 2.2 IEC Technical manual...
Trip signal from step1 phase L2 TR1L3 BOOLEAN Trip signal from step1 phase L3 BOOLEAN Common trip signal from step2 TR2L1 BOOLEAN Trip signal from step2 phase L1 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Enable execution of step 2 Characterist2 Definite time Definite time Selection of time delay curve type for Inverse curve A step 2 Inverse curve B Inverse curve C Prog. inv. curve Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 282
0.50 - 100.00 0.01 1.00 Parameter B for customer programmable curve for step 2 CCrv2 0.0 - 1.0 Parameter C for customer programmable curve for step 2 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
UBase, which is set in kV, phase-to-phase. OV2PTOV can be set to measure phase-to-earth fundamental value, phase-to-phase fundamental value, phase-to-earth RMS value or phase-to-phase RMS value. The choice of measuring is done by the parameter ConnType. Line distance protection REL650 2.2 IEC Technical manual...
B • inverse curve C • customer programmable inverse curve The type A curve is described as: æ ö > ç ÷ > è ø (Equation 44) IECEQUATION2422 V1 EN-US Line distance protection REL650 2.2 IEC Technical manual...
Page 285
The highest phase (or phase-to-phase) voltage is always used for the inverse time delay integration, see figure 136. The details of the different inverse time characteristics are shown in section "Inverse characteristics". Line distance protection REL650 2.2 IEC Technical manual...
Page 286
However, there are three ways to reset the timer: either the timer is reset instantaneously, or the timer value is frozen during the reset time, or the timer value is linearly decreased during the reset time. Line distance protection REL650 2.2 IEC Technical manual...
Page 287
Linearly decreased Frozen Timer Time Instantaneous IEC09000055-2-en.vsd IEC09000055 V2 EN-US Figure 137: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay at different reset types Line distance protection REL650 2.2 IEC Technical manual...
Page 288
139. Detailed information about individual stage reset/operation behavior is shown in figure and figure respectively. Note that by setting tResetn = 0.0s (where n means either 1 or 2 respectively), instantaneous reset of the definite time delayed stage is ensured. Line distance protection REL650 2.2 IEC Technical manual...
Page 289
Figure 139: Logic diagram for step 1, definite time delay, DT operation U1> START TRIP tReset1 IEC10000037-2-en.vsd IEC10000037 V2 EN-US Figure 140: Example for step 1, Definite Time Delay stage 1 reset Line distance protection REL650 2.2 IEC Technical manual...
A special logic is included to achieve the 1 out of 3, 2 out of 3 or 3 out of 3 criteria to fulfill the START condition. The design of Two step overvoltage protection (OV2PTOV) is schematically described in figure 142. Line distance protection REL650 2.2 IEC Technical manual...
UBase ±0.5% of U at U ≤ U ±0.5% of U at U > U Inverse time characteristics for steps 1 See table and 2, see table Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
ROV2PTOV has two voltage steps, each with inverse or definite time delay. A reset delay ensures operation for intermittent earth faults. Line distance protection REL650 2.2 IEC Technical manual...
TRIP BOOLEAN Trip BOOLEAN Common trip signal from step1 BOOLEAN Common trip signal from step2 START BOOLEAN General start signal BOOLEAN Common start signal from step1 BOOLEAN Common start signal from step2 Line distance protection REL650 2.2 IEC Technical manual...
Selection of used IDMT reset curve type Frozen timer for step 1 Linearly decreased tIReset1 0.000 - 60.000 0.001 0.025 Time delay in IDMT reset (s), step 1 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
1 - 12 Selection of one of the Global Base Value groups 8.3.6 Monitored data PID-3531-MONITOREDDATA v4 Table 159: ROV2PTOV Monitored data Name Type Values (Range) Unit Description ULevel REAL Magnitude of measured voltage Line distance protection REL650 2.2 IEC Technical manual...
The type A curve is described as: æ ö > ç ÷ > è ø (Equation 49) IECEQUATION2422 V1 EN-US where: Un> Set value for step 1 and step 2 Measured voltage Line distance protection REL650 2.2 IEC Technical manual...
Page 297
(tReset1 and tReset2 for the definite time and tIReset1 and tIReset2 for the inverse time) the corresponding START output is reset, after the defined reset time has elapsed. Line distance protection REL650 2.2 IEC Technical manual...
Page 298
TRIP Time Integrator Linearly decreased Frozen Timer Time Instantaneous IEC09000055-2-en.vsd IEC09000055 V2 EN-US Figure 144: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay Line distance protection REL650 2.2 IEC Technical manual...
Page 299
146. Detailed information about individual stage reset/operation behavior is shown in figure and figure respectively. Note that by setting tResetn = 0.0s, instantaneous reset of the definite time delayed stage is ensured. Line distance protection REL650 2.2 IEC Technical manual...
Page 300
IEC10000100-2-en.vsd IEC10000100 V2 EN-US Figure 146: Logic diagram for step 1, Definite time delay, DT operation U1< tReset1 IEC10000039-3-en.vsd IEC10000039 V3 EN-US Figure 147: Example for Definite Time Delay stage 1 reset Line distance protection REL650 2.2 IEC Technical manual...
Recursive Fourier filters filter the input voltage signal for the rated frequency. The residual voltage is compared to the set value, and is also used for the inverse time characteristic integration. The design of the function is schematically described in figure 149. Line distance protection REL650 2.2 IEC Technical manual...
Definite time delay high step (step 2) at 0 (0.000–60.000) s ± 0.2% or ± 45 ms to 1.2 x U whichever is greater Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 303
Reset time, start at 1.2 x U to 0 Min. = 5 ms Max. = 25 ms Critical impulse time 10 ms typically at 0 to 2 x U Impulse margin time 15 ms typically Line distance protection REL650 2.2 IEC Technical manual...
For calculation of the curve form for voltage based timer tMax 0.010 - 60.000 0.001 1.000 Maximum time operation limit for voltage based timer tMin 0.010 - 60.000 0.001 1.000 Minimum time operation limit for voltage based timer Line distance protection REL650 2.2 IEC Technical manual...
START output is reset, after that the defined reset time has elapsed. Here it should be noted that after leaving the Line distance protection REL650 2.2 IEC Technical manual...
The inverse time characteristics are shown in figure 151, for: UMin = 90% UNom = 100% tMax = 1.0 s tMin = 0.0 s Exponent = 0, 1, 2, 3 and 4 Line distance protection REL650 2.2 IEC Technical manual...
When the frequency has returned back to the setting of RestoreFreq, the RESTORE output is issued after the time delay tRestore. The design of underfrequency protection SAPTUF is schematically described in figure 152. Line distance protection REL650 2.2 IEC Technical manual...
Max. = 30 ms Operate time, definite time function at f + 0.02 Hz (0.000-60.000)s ±0.2% or ±100 ms to f - 0.02 Hz whichever is greater Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
A definite time delay is provided for operate. SAPTOF is provided with an undervoltage blocking. The operation is based on positive sequence voltage measurement and requires two phase-phase or three phase-neutral voltages to be connected. For information about Line distance protection REL650 2.2 IEC Technical manual...
Frequency set value IntBlockLevel 0.0 - 100.0 50.0 Internal blocking level in % of UBase tDelay 0.000 - 60.000 0.001 0.000 Operate time delay tReset 0.000 - 60.000 0.001 0.000 Time delay for reset Line distance protection REL650 2.2 IEC Technical manual...
The total time delay consists of the set value for time delay plus minimum operate time of the start function (80 - 90 ms). Line distance protection REL650 2.2 IEC Technical manual...
SAPFRC is provided with an undervoltage blocking. The operation is based on positive sequence voltage measurement and requires two phase-phase or three phase-neutral voltages to be connected. For information about how to connect Line distance protection REL650 2.2 IEC Technical manual...
Frequency gradient start value, the sign defines direction IntBlockLevel 0.0 - 100.0 50.0 Internal blocking level in % of UBase tDelay 0.000 - 60.000 0.001 0.200 Operate time delay Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
StartFreqGrad, sets SAPFRC to START and TRIP for frequency increases. To avoid oscillations of the output START signal, a hysteresis has been included. 9.3.6.2 Time delay M14970-10 v7 Rate-of-change frequency protection SAPFRC has a settable definite time delay, tDelay. Line distance protection REL650 2.2 IEC Technical manual...
The sign of the setting StartFreqGrad is essential, and controls if the function is used for raising or lowering frequency conditions. The design of SAPFRC is schematically described in figure 156. Line distance protection REL650 2.2 IEC Technical manual...
±0.2% or ±100 ms whichever is greater Definite time delay for (0.200-60.000) s ±0.2% or ±120 ms whichever is frequency gradient trip greater Definite reset time delay (0.000-60.000) s ±0.2% or ±250 ms whichever is greater Line distance protection REL650 2.2 IEC Technical manual...
10.1.3 Function block M12436-3 v9 CCSSPVC I3P* FAIL IREF* ALARM BLOCK IEC13000304-1-en.vsd IEC13000304 V1 EN-US Figure 157: CCSSPVC function block Signal ISIREF must be connected in the configuration. Line distance protection REL650 2.2 IEC Technical manual...
Current circuit supervision CCSSPVC compares the absolute value of the vectorial sum of the three phase currents |ΣIphase| and the absolute value of the residual current |Iref| from another current transformer set, see figure 158. Line distance protection REL650 2.2 IEC Technical manual...
Page 323
100 ms ALARM 150 ms OPERATION BLOCK en05000463.tif IEC05000463 V2 EN-US Figure 158: Simplified logic diagram for Current circuit supervision CCSSPVC The operate characteristic is percentage restrained, which is shown in Figure 159. Line distance protection REL650 2.2 IEC Technical manual...
Common start signal of sudden change in voltage STDUL1 BOOLEAN Start signal of sudden change in voltage, phase STDUL2 BOOLEAN Start signal of sudden change in voltage, phase STDUL3 BOOLEAN Start signal of sudden change in voltage, phase Line distance protection REL650 2.2 IEC Technical manual...
% of UBase Table 185: FUFSPVC Non group settings (basic) Name Values (Range) Unit Step Default Description GlobalBaseSel 1 - 12 Selection of one of the Global Base Value groups Line distance protection REL650 2.2 IEC Technical manual...
3I2<. A drop out delay of 100 ms for the measured zero-sequence and negative sequence current will prevent a false fuse failure detection at un-equal breaker opening at the two line ends. Line distance protection REL650 2.2 IEC Technical manual...
Page 329
IED. When activated for more than 20 ms, the operation of the fuse failure is blocked; a fixed drop-out timer prolongs the block for 100 ms. The aim is to increase the security against unwanted operations during Line distance protection REL650 2.2 IEC Technical manual...
The following quantities are calculated in all three phases: • The change in voltage DU • The change in current DI The internal FuseFailDetDUDI signal is activated if the following conditions are fulfilled: Line distance protection REL650 2.2 IEC Technical manual...
Page 331
The delta function (except the sudden change of voltage and current detection) is deactivated by setting the parameter OpDUDI to Off. Line distance protection REL650 2.2 IEC Technical manual...
Page 332
DUDI detection Phase 3 DeltaIL3 DeltaUL3 Same logic as for phase 1 a<b a>b IPh> CBCLOSED a<b a>b a<b a>b FuseFailDetDUDI IEC12000166-3-en.vsd IEC12000166 V3 EN-US Figure 162: Simplified logic diagram for the DU/DI detection part Line distance protection REL650 2.2 IEC Technical manual...
UDLD< and IDLD<. If at least one phase is considered to be dead the output DLD1PH and the internal signal DeadLineDet1Ph is activated. If all three phases are considered to be dead the output DLD3PH is activated Line distance protection REL650 2.2 IEC Technical manual...
The delta function can be activated by setting the parameter OpDUDI to On. When selected it operates in parallel with the sequence based algorithms. Line distance protection REL650 2.2 IEC Technical manual...
Page 335
BLKU in order to block the voltage related functions when the line disconnector is open. The impedance protection function does not have to be affected since there will be no line currents that can cause malfunction of the distance protection. Line distance protection REL650 2.2 IEC Technical manual...
Page 336
BLKZ 150 ms MCBOP BLKU 60 s All UL > UsealIn< VoltZeroSeq VoltNegSeq AllCurrLow CBCLOSED DISCPOS IEC10000033-2-en.vsd IEC10000033 V2 EN-US Figure 165: Simplified logic diagram for fuse failure supervision function, Main logic Line distance protection REL650 2.2 IEC Technical manual...
Operate time, start, 1 ph, at 1 x U to 0 Min. = 10 ms Max. = 25 ms Reset time, start, 1 ph, at 0 to 1 x U Min. = 15 ms Max. = 30 ms Line distance protection REL650 2.2 IEC Technical manual...
The synchronizing feature evaluates voltage difference, phase angle difference, slip frequency and frequency rate of change before issuing a controlled closing of the circuit breaker. Breaker closing time is a setting. Line distance protection REL650 2.2 IEC Technical manual...
Group signal for phase to earth voltage input L1, SIGNAL line 2 BLOCK BOOLEAN General block BLKSYNCH BOOLEAN Block synchronizing BLKSC BOOLEAN Block synchro check BLKENERG BOOLEAN Block energizing check Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 341
BOOLEAN Manual energizing check OK TSTSYNOK BOOLEAN Synchronizing OK test output TSTAUTSY BOOLEAN Auto synchro check OK test output TSTMANSY BOOLEAN Manual synchro check OK test output Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 342
Calculated difference of frequency PHDIFFME REAL Calculated difference of phase angle UBUS REAL Bus voltage ULINE REAL Line voltage MODEAEN INTEGER Selected mode for automatic energizing MODEMEN INTEGER Selected mode for manual energizing Line distance protection REL650 2.2 IEC Technical manual...
Manual tSCA 0.000 - 60.000 0.001 0.100 Time delay output for synchrocheck Auto tSCM 0.000 - 60.000 0.001 0.100 Time delay output for synchrocheck Manual Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 344
Selection of one of the Global Base Value groups, Line SelPhaseBus2 Phase L1 Phase L1 Select phase for busbar2 Phase L2 Phase L3 Phase L1L2 Phase L2L3 Phase L3L1 Positive sequence Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
The synchrocheck feature measures the conditions across the circuit breaker and compares them to set limits. The output for closing operation is given when all measured quantities are simultaneously within their set limits. Line distance protection REL650 2.2 IEC Technical manual...
FreqDiffA, FreqDiffM, PhaseDiffA, PhaseDiffM and UDiffSC. If additional phase angle adjustment is done with the PhaseShift setting, the adjustment factor is deducted from the line voltage before the comparison of the phase angle values. Line distance protection REL650 2.2 IEC Technical manual...
Page 347
60 degrees to smaller than 5 degrees. Line distance protection REL650 2.2 IEC Technical manual...
Page 348
The measured frequencies between the settings for the maximum and minimum frequency will initiate the measuring and the evaluation of the angle change to allow operation to be sent at the right moment including the set tBreaker time. The Line distance protection REL650 2.2 IEC Technical manual...
Page 349
The inputs BLOCK and BLKSYNCH are available for total block of the complete SESRSYN function and block of the Synchronizing function respectively. TSTSYNCH will allow testing of the function where the fulfilled conditions are connected to a separate output. Line distance protection REL650 2.2 IEC Technical manual...
Page 350
MANENOK and AUTOENOK conditions. The Energizing direction can also be selected by an integer input AENMODE respective MENMODE, which for example, can be connected to a Binary to Integer function Line distance protection REL650 2.2 IEC Technical manual...
Page 352
Figure 170: Automatic energizing BLKENERG manEnergOpenBays BLOCK ManEnerg 1½ bus CB CBConfig B1QOPEN LN1QOPEN B1QCLD B2QOPEN LN2QOPEN 1½ bus alt. CB B2QCLD Tie CB IEC14000032-1-en.vsd IEC14000032 V1 EN-US Figure 171: Open bays Line distance protection REL650 2.2 IEC Technical manual...
Page 353
B2QCLD for Bus 2 to select between bus 1 and bus 2 voltages. If the disconnector connected to bus 1 is closed and the disconnector connected to bus 2 is opened the Line distance protection REL650 2.2 IEC Technical manual...
Page 354
Voltage selection for a 1 1/2 circuit breaker arrangement M14839-3 v8 Note that with 1½ breaker schemes three Synchrocheck functions must be used for the complete diameter. Below, the scheme for one Bus breaker and the Tie breaker is described. Line distance protection REL650 2.2 IEC Technical manual...
Page 355
This output as well as the function can be blocked with the input signal BLOCK. The function block diagram for the voltage selection of a bus circuit breaker is shown in figure and for the tie circuit breaker in figure 174. Line distance protection REL650 2.2 IEC Technical manual...
Page 356
UB2FF USELFAIL ULN1OK ULN1FF ULN2OK ULN2FF BLOCK en05000780-2.vsd IEC05000780 V2 EN-US Figure 173: Simplified logic diagram for the voltage selection function for a bus circuit breaker in a 1 1/2 breaker arrangement Line distance protection REL650 2.2 IEC Technical manual...
Page 357
UB2OK UB2FF USELFAIL ULN1OK ULN1FF ULN2OK ULN2FF BLOCK en05000781-2.vsd IEC05000781 V2 EN-US Figure 174: Simplified logic diagram for the voltage selection function for the tie circuit breaker in 1 1/2 breaker arrangement. Line distance protection REL650 2.2 IEC Technical manual...
±0.5% of U at U > U Reset ratio, voltage high limit > 95% Voltage low limit for (10.0-80.0)% of UBase ±0.5% of U energizing check Reset ratio, voltage low limit < 105% Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Several auto reclosing functions can be provided for multi-breaker arrangements. A priority circuit allows one circuit breaker to reclose first and the second will only close if the fault proved to be transient. Line distance protection REL650 2.2 IEC Technical manual...
Start high-speed reclosing without synchrocheck TRSOTF BOOLEAN Continue to shots 2-5 at a trip from switch-on-to- fault SKIPHS BOOLEAN Skip high speed shot and continue with delayed shots Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 361
Number of single-phase reclosing shots COUNT2P INTEGER Number of two-phase reclosing shots COUNT3P1 INTEGER Number of three-phase shot 1 reclosings COUNT3P2 INTEGER Number of three-phase shot 2 reclosings Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Minimum time that circuit breaker must be closed before new sequence is allowed tUnsucCl 0.00 - 6000.00 0.01 30.00 Maximun wait time for circuit breaker closing before indicating unsuccessful Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 363
Wait time after close command before proceeding to next shot UnsucClByCBChk NoCBCheck NoCBCheck Unsuccessful closing signal obtained by CB check checking circuit breaker position BlockByUnsucCl Block AR at unsuccessful reclosing Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
• or the circuit breaker is not ready The function will not react on any start from protection trips while in “inactive” status and no automatic reclosing is possible. Line distance protection REL650 2.2 IEC Technical manual...
When the auto recloser is for instance in “inactive” status only two transition are possible: • transition to “ready” status when the circuit breaker is ready and closed • transition to “blocked” status by external blocking Line distance protection REL650 2.2 IEC Technical manual...
(when enabled by setting StartByCBOpen=On) At the end of the dead time, provided that other conditions are fulfilled, a circuit breaker close command signal is given. The other conditions to be fulfilled are: Line distance protection REL650 2.2 IEC Technical manual...
Page 367
The circuit breaker must have been closed for at least the set value for setting tCBClosedMin before a start is accepted. The logic for Off or On operation is shown in Figure 176. Line distance protection REL650 2.2 IEC Technical manual...
Page 368
Please note that tripping mode of the IED is defined in Trip Logic function block SMPPTRC. For example for two-phase faults either 2ph or 3ph tripping and consequent auto reclosing can be selected Line distance protection REL650 2.2 IEC Technical manual...
Page 369
The high-speed dead time shall be set shorter than normal first shot three-phase dead time. Note that if high-speed three- phase shot is not successful the auto reclosing sequence will continue with shot two. Line distance protection REL650 2.2 IEC Technical manual...
Page 370
To start a new auto reclosing cycle, a number of conditions of input signals need to be fulfilled. The inputs are: Line distance protection REL650 2.2 IEC Technical manual...
Page 371
If the user wants to start the auto recloser from circuit breaker open position instead of the protection trip signals, this starting mode is selected by enabling a setting StartByCBOpen. Typically, a circuit breaker auxiliary contact of type normally Line distance protection REL650 2.2 IEC Technical manual...
Page 372
The auto recloser will be blocked the time set in tInhibit after the deactivation of the INHIBIT input. The following internal inhibit signals are also affected by the setting tInhibit: Line distance protection REL650 2.2 IEC Technical manual...
Page 374
If the circuit breaker closing command is given and the circuit breaker is closed within the set time interval tUnsucCl, the SUCCL output is activated after the set time interval tSuccessful. The logic for successful and unsuccessful reclosing indication is shown in Figure 180. Line distance protection REL650 2.2 IEC Technical manual...
Page 375
IEC16000157 V1 EN-US Figure 180: Successful/Unsuccessful Figure shows the logic for most parts of an auto reclosing sequence. Figure should be read together with the other logic diagrams to get the whole picture. Line distance protection REL650 2.2 IEC Technical manual...
Page 376
Section 11 1MRK 506 382-UEN A Control IEC16000158-1-en.vsdx IEC16000158 V1 EN-US Figure 181: Auto reclosing sequence Line distance protection REL650 2.2 IEC Technical manual...
Page 377
SUCCL = 0, UNSUCC = 0, INPROG = 0 Set Off, Not Ready SETON = 0 Others Means that auto recloser is in transitional state, that should not be visible in steady state situation Line distance protection REL650 2.2 IEC Technical manual...
Page 378
THOLHOLD input can also be used to set the auto recloser on hold, for longer or shorter time periods, for other purposes if for some reason the auto recloser needs to be halted. The logic for thermal protection hold is shown in Figure 182. Line distance protection REL650 2.2 IEC Technical manual...
Page 379
Typical setting is 2sec. In single circuit breaker applications, the setting Priority is set to None. The logic for master-slave is shown in Figure 183. Line distance protection REL650 2.2 IEC Technical manual...
11.2.6.5 Time sequence diagrams M12458-10 v5 Some examples of the timing of internal and external signals at typical transient and permanent faults are shown below in Figure to 187. Line distance protection REL650 2.2 IEC Technical manual...
Maximum allowed start pulse duration (0.000-60.000) s ±0.2% or ±15 ms “tLongStartInh” whichever is greater Circuit breaker closing pulse duration (0.000-60.000) s ±0.2% or ±15 ms “tPulse” whichever is greater Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
The interlocking conditions are generated in separate function blocks containing the interlocking logic. 11.3.1.3 Function block M15049-3 v6 SCILO POSOPEN EN_OPEN POSCLOSE EN_CLOSE OPEN_EN CLOSE_EN IEC05000359-2-en.vsd IEC05000359 V2 EN-US Figure 188: SCILO function block Line distance protection REL650 2.2 IEC Technical manual...
Overriding of interlocking functions • Overriding of synchrocheck • Operation counter • Suppression of mid position Two types of command models can be used: • Direct with normal security • SBO (Select-Before-Operate) with enhanced security Line distance protection REL650 2.2 IEC Technical manual...
Three types of function blocks are available to cover most of the control and supervision within the bay. These function blocks are interconnected to form a Line distance protection REL650 2.2 IEC Technical manual...
Control action is aborted due to invalid switch position (Pos in XCBR) Position-reached Switch is already in the intended position (Pos in XCBR) Parameter-change- Control action is blocked due to running parameter in-execution change Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 389
Operate service are different Locked-by-other- Another client has already reserved the object client Wrong-Ctl-model Command from client uses wrong control model Blocked-for-open- Blocked for Open command Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 390
Ed 2 Ed 1 None Not-supported Blocked-by-switching-hierarchy Select-failed Invalid-position Position-reached Parameter-change-in-execution Step-limit Blocked-by-Mode Blocked-by-process Blocked-by-interlocking Blocked-by-synchrocheck Command-already-in-execution Blocked-by-health 1-of-n-control Abortion-by-cancel Time-limit-over Abortion-by-trip Object-not-selected Object-already-selected No-access-authority Blocked-by-command Inconsistent-parameters Locked-by-other-client Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
The parameters between successive control services are not consistent, for example the ctlNum of Select and Operate service are different. Locked-by-other-client Another client has already reserved the object. 11.4.4 Bay control QCBAY IP15597-1 v2 Line distance protection REL650 2.2 IEC Technical manual...
Value for the operator place allocation UPD_BLKD BOOLEAN Update of position is blocked CMD_BLKD BOOLEAN Function is blocked for commands BOOLEAN Local operation allowed BOOLEAN Station operation allowed BOOLEAN Remote operation allowed Line distance protection REL650 2.2 IEC Technical manual...
If the setting AllPSTOValid is set to No Priority and the LR-switch position is in Local or Remote state, the PSTO output is set to 5 (all), that is, it is permitted to Line distance protection REL650 2.2 IEC Technical manual...
Page 394
The blocking states for position indications and commands are intended to provide the possibility for the user to make common blockings for the functions configured within a complete bay. The blocking facilities provided by the bay control function are the following: Line distance protection REL650 2.2 IEC Technical manual...
Bitmask output 1 to local remote LHMI input HMICTR2 INTEGER Bitmask output 2 to local remote LHMI input HMICTR3 INTEGER Bitmask output 3 to local remote LHMI input Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
When the local HMI is used, the inputs are not used. The switching between external and local HMI source is done through the parameter ControlMode. The outputs from the LOCREM function block control the output PSTO (Permitted Source To Operate) on Bay control (QCBAY). Line distance protection REL650 2.2 IEC Technical manual...
IED. Otherwise the default authority level, SuperUser, can handle the control without LogOn. The users and passwords are defined with the IED Users tool in PCM600. 11.4.6 Switch controller SCSWI IP15603-1 v2 Line distance protection REL650 2.2 IEC Technical manual...
BOOLEAN Synchronizing function in progress SYNC_OK BOOLEAN Closing is permitted at set to true by the synchrocheck EN_OPEN BOOLEAN Enables open operation EN_CLOSE BOOLEAN Enables close operation Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 400
If the control model used is Select before operate, Also the corresponding enable input must be set, and no interlocking is active. The L_SEL input must be set before Line distance protection REL650 2.2 IEC Technical manual...
Control handling M13484-6 v7 Two types of control models can be used. The two control models are "direct with normal security" and "SBO (Select-Before-Operate) with enhanced security". The Line distance protection REL650 2.2 IEC Technical manual...
Page 402
SEL_CL = FALSE RES_RQ = FALSE RES_GRT = FALSE IEC16000083=1=en=Original.vsdx IEC16000083 V1 EN-US Figure 195: Example of command sequence for a successful close command when the control model SBO with enhanced security is used Line distance protection REL650 2.2 IEC Technical manual...
Page 403
"merge" the position of the switches to the resulting multi-phase position. In the case when the position differ between the one-phase switches, following principles will be applied: Line distance protection REL650 2.2 IEC Technical manual...
Page 404
Table 214. Commands through the inputs L_SEL, L_OPEN and L_CLOSE are always from the local operator place. For commands through the inputs AU_OPEN Line distance protection REL650 2.2 IEC Technical manual...
Page 405
Example of interaction between SCSWI, SESRSYN (synchrocheck and synchronizing function) and SXCBR function Time diagrams M13484-51 v6 The Switch controller (SCSWI) function has timers for evaluating different time supervision conditions. These timers are explained here. Line distance protection REL650 2.2 IEC Technical manual...
Page 406
1- tResResponse of-n-control in 'cause' is timer IEC05000093-2-en.vsd IEC05000093 V2 EN-US Figure 199: tResResponse The timer tExecutionFB supervises the time between the execute command and the command termination, see Figure 200. Line distance protection REL650 2.2 IEC Technical manual...
Page 407
The start signal for the synchronizing is obtained if the synchrocheck conditions are not fulfilled. The parameter tSynchronizing is used to define the maximum allowed time between the start signal for synchronizing and the confirmation that synchronizing is in progress. Line distance protection REL650 2.2 IEC Technical manual...
XLNPROXY function is connected, SCSWI automatically awaits that the switch is selected before accepting the selection. Also, if the seSeld data attribute is set before the selection is requested, the selection request fails. Line distance protection REL650 2.2 IEC Technical manual...
Signal for close position of truck from I/O RS_CNT BOOLEAN Resets the operation counter EEH_WARN BOOLEAN Warning from external equipment EEH_ALM BOOLEAN Alarm from external equipment GROUP Execution information from CSWI SIGNAL Line distance protection REL650 2.2 IEC Technical manual...
61850 client residing in another IED or the operator place. This switch function executes commands, evaluates block conditions and evaluates different time supervision conditions. Only if all conditions indicate a switch operation to be Line distance protection REL650 2.2 IEC Technical manual...
Page 412
Blocking of function, BLOCK. If BLOCK signal is set, it means that the function is active, but no outputs are generated, no reporting, control commands are rejected and functional and configuration data is visible. Line distance protection REL650 2.2 IEC Technical manual...
Page 413
Figure explains these two timers during the execute phase. Line distance protection REL650 2.2 IEC Technical manual...
Page 414
Figure 206: Execute output pulse If the pulse is set to be adaptive, it is not possible for the pulse to exceed tOpenPulse or tClosePulse. The execute output pulses are reset when: Line distance protection REL650 2.2 IEC Technical manual...
Page 415
An example of when a primary device is open and an open command is executed is shown in Figure OPENPOS CLOSEPOS AdaptivePulse=FALSE EXE_OP tOpenPulse AdaptivePulse=TRUE EXE_OP tOpenPulse tStartMove timer en05000099.vsd IEC05000099 V1 EN-US Figure 207: Open command with open position indication Line distance protection REL650 2.2 IEC Technical manual...
Valid data on BEH input BOOLEAN Local control behaviour LOC_VLD BOOLEAN Valid data on LOC input BLKOPN BOOLEAN Block opening BLKOPN_VLD BOOLEAN Valid data on BLKOPN input BLKCLS BOOLEAN Block closing Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 417
INTEGER Operation counter value L_CAUSE INTEGER Latest value of the error indication during command EEHEALTH INTEGER External equipment health. 1=No warning or alarm, 2=Warning, 3=Alarm OPCAP INTEGER Switch / breaker operating capability Line distance protection REL650 2.2 IEC Technical manual...
SCSWI function controlling the switch. If an operation is initiated by the SCSWI, the XLNPROXY function checks if the switch is blocked for the operation direction and that the position moves to the Line distance protection REL650 2.2 IEC Technical manual...
Page 419
Switch returned to the initial position. Switch-in-bad-state Switch is in a bad position. Not-expected-final-position Switch did not reach the expected final position. The L_CAUSE output keeps its output value until a new command sequence has been started. Line distance protection REL650 2.2 IEC Technical manual...
Hardware selector switches are used extensively by utilities, in order to have different functions operating on pre-set values. Hardware switches are however Line distance protection REL650 2.2 IEC Technical manual...
The operator place (local or remote) is specified through the PSTO input. If any operation is allowed the signal INTONE from the Fixed signal function block can be connected. Line distance protection REL650 2.2 IEC Technical manual...
In both cases, the switch full name will be shown, but the user has to redefine it when building the Graphical Display Editor, under the "Caption". If used for the control, the following sequence of commands will ensure: Line distance protection REL650 2.2 IEC Technical manual...
From the single line diagram on local HMI. 11.6 Selector mini switch VSGAPC SEMOD158754-1 v3 11.6.1 Identification SEMOD167850-2 v4 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Selector mini switch VSGAPC Line distance protection REL650 2.2 IEC Technical manual...
Position 1 indication, logical signal POS2 BOOLEAN Position 2 indication, logical signal CMDPOS12 BOOLEAN Execute command from position 1 to position 2 CMDPOS21 BOOLEAN Execute command from position 2 to position 1 Line distance protection REL650 2.2 IEC Technical manual...
An INTONE connection from Fixed signal function block (FXDSIGN) will allow operation from local HMI. As it can be seen, both indications and commands are done in double-bit representation, where a combination of signals on both inputs/outputs generate the desired result. Line distance protection REL650 2.2 IEC Technical manual...
IEC 61850-8-1 or other communication protocols. It is especially intended to be used in the interlocking station-wide logics. 11.7.3 Function block SEMOD54710-4 v5 IEC13000081 V1 EN-US Figure 212: DPGAPC function block Line distance protection REL650 2.2 IEC Technical manual...
POSITION will be updated as the time when DPGAPC function detects the change. Refer to Table for the description of the input-output relationship in terms of the value and the quality attributes. Line distance protection REL650 2.2 IEC Technical manual...
The commands can be pulsed or steady with a settable pulse time. 11.8.3 Function block SEMOD176479-4 v5 SPC8GAPC BLOCK ^OUT1 PSTO ^OUT2 ^OUT3 ^OUT4 ^OUT5 ^OUT6 ^OUT7 ^OUT8 IEC07000143-3-en.vsd IEC07000143 V3 EN-US Figure 213: SPC8GAPC function block Line distance protection REL650 2.2 IEC Technical manual...
AutomationBits, command function for AUTOBITS DNP3 11.9.2 Functionality SEMOD158591-5 v8 Automation bits function for DNP3 (AUTOBITS) is used within PCM600 to get into the configuration of the commands coming through the DNP3 protocol. The Line distance protection REL650 2.2 IEC Technical manual...
Name Type Description CMDBIT1 BOOLEAN Command out bit 1 CMDBIT2 BOOLEAN Command out bit 2 CMDBIT3 BOOLEAN Command out bit 3 CMDBIT4 BOOLEAN Command out bit 4 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Command out bit 31 CMDBIT32 BOOLEAN Command out bit 32 11.9.5 Settings PID-3776-SETTINGS v6 Table 245: AUTOBITS Non group settings (basic) Name Values (Range) Unit Step Default Description Operation Operation Off / On Line distance protection REL650 2.2 IEC Technical manual...
The IEDs can receive commands either from a substation automation system or from the local HMI. The command function block has outputs that can be used, for example, to control high voltage apparatuses or for other user defined functionality. Line distance protection REL650 2.2 IEC Technical manual...
IED. Also a BLOCK input is available used to block the updating of the outputs. The output signals, OUT1 to OUT16, are available for configuration to built-in functions or via the configuration logic circuits to the binary outputs of the IED. Line distance protection REL650 2.2 IEC Technical manual...
The built-in communication module (LDCM) can be used for scheme communication signaling when included. 12.1.3 Function block M13866-3 v7 ZCPSCH I3P* TRIP U3P* BLOCK CHSTOP BLKTR BLKCS CSBLK CACC CSOR CSUR CBOPEN IEC09000004 IEC09000004 V4 EN-US Figure 216: ZCPSCH function block Line distance protection REL650 2.2 IEC Technical manual...
TRIP BOOLEAN Trip output BOOLEAN Carrier Send signal CHSTOP BOOLEAN Stops the blocking signal to remote end BOOLEAN Carrier signal received or missing carrier guard signal BOOLEAN Loss of carrier guard signal Line distance protection REL650 2.2 IEC Technical manual...
A permissive scheme is inherently faster and has better security against false tripping than a blocking scheme. On the other hand, a permissive scheme depends Line distance protection REL650 2.2 IEC Technical manual...
DeltaU and DeltaI respectively, or if the change of zero sequence voltage and zero sequence current exceeds the settings Delta3U0,Delta3I0 respectively. The schemeType is selected as DeltaBlocking. Line distance protection REL650 2.2 IEC Technical manual...
The logic for trip signal in permissive scheme is shown in figure 219. tCoord CACC TRIP en05000513.vsd IEC05000513 V1 EN-US Figure 219: Logic for trip signal in permissive scheme Line distance protection REL650 2.2 IEC Technical manual...
The received signal created by the unblocking function is reset 150 ms after the security timer has elapsed. When that occurs an output signal LCG is activated for signalling purpose. The unblocking function is reset 200 ms after that the guard signal is present again. Line distance protection REL650 2.2 IEC Technical manual...
In the direct intertrip scheme, the send signal CS is sent from an underreaching zone that is tripping the line. The received signal CR is directly transferred to a trip for tripping without local criteria. The signal is further processed in the tripping logic. Line distance protection REL650 2.2 IEC Technical manual...
On detection of a current reversal, the current reversal logic provides an output to block the sending of the teleprotection signal to the remote end, and to block the Line distance protection REL650 2.2 IEC Technical manual...
Block of WEI logic due to operation of other protections VTSZ BOOLEAN Block of trip from WEI logic through fuse-failure function CBOPEN BOOLEAN Block of trip from WEI logic by an open breaker BOOLEAN POR Carrier receive for WEI logic Line distance protection REL650 2.2 IEC Technical manual...
The current reversal logic can be enabled by setting the parameter CurrRev = On. The current reversal logic uses a reverse zone connected to the input IRV to recognize the fault on the parallel line in any of the phases.When the reverse zone Line distance protection REL650 2.2 IEC Technical manual...
IED is usually used for this purpose. • The weak-end infeed logic also echoes the received permissive signal when local breaker opens, CBOPEN prior to faults appeared at the end of line. Line distance protection REL650 2.2 IEC Technical manual...
The logic can be controlled either by the autorecloser (zone extension) or by the loss-of-load current (loss-of-load acceleration). 12.3.3 Function block M13816-3 v4 ZCLCPSCH I3P* TRZE BLOCK TRLL ARREADY NDST EXACC LLACC IEC13000307-1-en.vsd IEC13000307 V1 EN-US Figure 228: ZCLCPSCH function block Line distance protection REL650 2.2 IEC Technical manual...
Time delay on pick-up for MINCURR value tLoadOn 0.000 - 60.000 0.001 0.000 Time delay on pick-up for load current release tLoadOff 0.000 - 60.000 0.001 0.300 Time delay on drop off for load current release Line distance protection REL650 2.2 IEC Technical manual...
When the "acceleration" is controlled by a loss-of-load, the overreaching zone used for "acceleration" connected to input LLACC is not allowed to trip "instantaneously" during normal non-fault system conditions. When all three-phase Line distance protection REL650 2.2 IEC Technical manual...
In the directional scheme, information of the fault current direction must be transmitted to the other line end. With directional comparison, a short operate time Line distance protection REL650 2.2 IEC Technical manual...
Signal to be used for tripping by Communication Scheme CSOR BOOLEAN Overreaching residual overcurrent signal for Carrier Send CSUR BOOLEAN Underreaching residual overcurrent signal for Carrier Send BOOLEAN Carrier Receive for Communication Scheme Logic BOOLEAN Carrier guard signal received Line distance protection REL650 2.2 IEC Technical manual...
Security timer for loss of carrier guard detection 12.4.6 Operation principle M13922-4 v5 The four step directional residual overcurrent protection EF4PTOC is configured to give input information, that is directional fault detection signals, to the ECPSCH logic: Line distance protection REL650 2.2 IEC Technical manual...
If the fault is on the line, the forward direction measuring element operates. If no blocking signal comes from the other line end via the CR binary input (received signal) the TRIP output is activated after the tCoord set time delay. Line distance protection REL650 2.2 IEC Technical manual...
The permissive scheme can be of either underreaching or overreaching type. In the underreaching alternative, an underreaching directional residual overcurrent measurement element will be used as sending criterion of the permissive input signal CSUR. Line distance protection REL650 2.2 IEC Technical manual...
The received signal created by the unblocking function is reset 150 ms after the security timer has elapsed. When that occurs an output signal LCG is activated for signaling purpose. The unblocking function is reset 200 ms after that the guard signal is present again. Line distance protection REL650 2.2 IEC Technical manual...
IRVBLK is activated. The tDelayRev timer delays the reset of the output signal. The signal blocks operation of the overreach permissive scheme for residual current and thus prevents unwanted operation caused by fault current reversal. Line distance protection REL650 2.2 IEC Technical manual...
If the forward or the reverse directional measuring element is activated during the last 200 ms, the fault current is sufficient for the IED to detect the fault with the earth fault function that is in operation. Line distance protection REL650 2.2 IEC Technical manual...
Page 466
200 ms WEIBLK2 1500 ms CBOPEN ST3U0 15 ms TRWEI a>b 3U0> WEI = Echo&Trip IEC09000020-6-en.vsd IEC09000020 V6 EN-US Figure 237: Simplified logic diagram for weak-end infeed logic - Echo & Trip Line distance protection REL650 2.2 IEC Technical manual...
Delay time for current reversal (0.000-60.000) s ±0.2% or ±30 ms whichever is greater Coordination time for weak-end (0.000–60.000) s ±0.2% or ±30 ms whichever infeed logic is greater Line distance protection REL650 2.2 IEC Technical manual...
The trip function can collect start and directional signals from different application functions. The aggregated start and directional signals are mapped to the IEC 61850 logical node data model. Line distance protection REL650 2.2 IEC Technical manual...
Prepare all tripping to be three-phase SETLKOUT BOOLEAN Input for setting the circuit breaker lockout function RSTLKOUT BOOLEAN Input for resetting the circuit breaker lockout function STDIR INTEGER General start direction input Line distance protection REL650 2.2 IEC Technical manual...
IEDs' binary inputs are routed. It has a single three-phase trip output (TRIP) to connect to one or more of the IEDs' binary outputs, as well as to other functions within the IED requiring this signal. Line distance protection REL650 2.2 IEC Technical manual...
Page 473
The inputs 1PTRZ and 1PTREF enable single- phase and two-phase tripping for those functions which do not have their own phase selection capability (i.e. which have just a single trip output). An example of such a protection function is the Line distance protection REL650 2.2 IEC Technical manual...
Page 477
TR1P 5 ms To ensure that the fault is two phase TR2P -LOOP -LOOP AutoLock CLKLKOUT SETLKOUT RSTLKOUT TripLockout -LOOP IEC17000066=1=en=Original.vsdx IEC17000066 V1 EN-US Figure 243: Final tripping circuits Line distance protection REL650 2.2 IEC Technical manual...
(0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater Evolving fault delay (0.000-60.000) s ±0.2% or ±15 ms whichever is greater Line distance protection REL650 2.2 IEC Technical manual...
Name Type Default Description BLOCK BOOLEAN Block of function STDIR1 INTEGER Start direction input 1 STDIR2 INTEGER Start direction input 2 STDIR3 INTEGER Start direction input 3 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
14 individual Boolean signals, which are positioned as, see Figure 247. STDIRX =[ b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14 ] START (start) FW (forward) REV (reverse) Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 481
REVN) to pass through to the general STDIR output. If both forward and reverse are active phase-wise (e.g. REVLx=FWLx = True) or at neutral (e.g. FWN = REVN = True) at the same time, none will be shown, see Figure 248. Line distance protection REL650 2.2 IEC Technical manual...
IED. The trip matrix logic function has 3 output signals and these outputs can be connected to physical tripping outputs according to the specific application needs for settable pulse or steady output. Line distance protection REL650 2.2 IEC Technical manual...
Page 488
TMAGAPC Output signals Name Type Description OUTPUT1 BOOLEAN OR function betweeen inputs 1 to 16 OUTPUT2 BOOLEAN OR function between inputs 17 to 32 OUTPUT3 BOOLEAN OR function between inputs 1 to 32 Line distance protection REL650 2.2 IEC Technical manual...
OR-function, a new pulse will only be given on the output if all related inputs are reset and then one is activated again. For steady operation the OffDelay will start when all related inputs have reset. Detailed logical diagram is shown in figure Line distance protection REL650 2.2 IEC Technical manual...
100 ms TMAGAPC 13.4 Logic for group alarm ALMCALH GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1 13.4.1 Identification GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number Logic for group alarm ALMCALH Line distance protection REL650 2.2 IEC Technical manual...
IEC13000191-1-en.vsd IEC13000191 V1 EN-US Figure 253: Group alarm logic 13.4.7 Technical data GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v1 Table 289: Number of ALMCALH instances Function Quantity with cycle time 3 ms 8 ms 100 ms ALMCALH Line distance protection REL650 2.2 IEC Technical manual...
WARNING output signal will get logical value 1. The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady signal. INPUT1 200 ms WARNING ³1 INPUT16 IEC13000192-1-en.vsd IEC13000192 V1 EN-US Line distance protection REL650 2.2 IEC Technical manual...
The logic for group indication INDCALH block is provided with 16 input signals and 1 IND output signal. The function block incorporates internal logic OR gate in order to provide grouping of connected input signals to the output IND signal from the function block. Line distance protection REL650 2.2 IEC Technical manual...
• INVERTER function block that inverts the input signal to the output. • LLD function block. Loop delay used to delay the output signal one execution cycle. Line distance protection REL650 2.2 IEC Technical manual...
The AND function block has up to four inputs and two outputs. One of the outputs is inverted. 13.7.1.1 Function block M11452-3 v2 INPUT1 INPUT2 NOUT INPUT3 INPUT4 IEC14000071-1-en.vsd IEC14000071 V1 EN-US Figure 254: AND function block Line distance protection REL650 2.2 IEC Technical manual...
Type Description BOOLEAN Output signal delayed one execution cycle 13.7.4.3 Technical data GUID-B2E6F510-8766-4381-9618-CE02ED71FFB6 v1 Table 310: Number of LLD instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms Line distance protection REL650 2.2 IEC Technical manual...
Output from OR gate NOUT BOOLEAN Inverted output from OR gate 13.7.5.3 Technical data GUID-35A795D7-A6BD-4669-A023-43C497DBFB01 v3 Table 313: Number of OR instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms Line distance protection REL650 2.2 IEC Technical manual...
Technical data GUID-E05E5FB1-23E7-4816-84F2-1FBFFDFF2B43 v1 Table 317: Number of PULSETIMER instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms PULSETIMER (0.000–90000.000) s ±0.5% ±10 ms Line distance protection REL650 2.2 IEC Technical manual...
Type Default Description BOOLEAN Input signal to set RESET BOOLEAN Input signal to reset PID-3811-OUTPUTSIGNALS v5 Table 320: RSMEMORY Output signals Name Type Description BOOLEAN Output signal NOUT BOOLEAN Inverted output signal Line distance protection REL650 2.2 IEC Technical manual...
Table 323: Truth table for SRMEMORY function block RESET NOUT Last Inverted value last value 13.7.8.1 Function block M11484-3 v2 SRMEMORY RESET NOUT IEC04000408_2_en.vsd IEC04000408 V2 EN-US Figure 261: SRMEMORY function block Line distance protection REL650 2.2 IEC Technical manual...
The timer has a settable time delay. It also has an Operation setting On and Off that controls the operation of the timer. Line distance protection REL650 2.2 IEC Technical manual...
The output signal OUT is 1 if the input signals are different and 0 if they are the same. Table 332: Truth table for XOR function block INPUT1 INPUT2 NOUT 13.7.10.1 Function block M11476-3 v1 INPUT1 INPUT2 NOUT IEC04000409-2-en.vsd IEC04000409 V2 EN-US Figure 264: XOR function block Line distance protection REL650 2.2 IEC Technical manual...
IED, either for forcing the unused inputs in other function blocks to a certain level/value, or for creating certain logic. Boolean, integer, floating point, string types of signals are available. One FXDSIGN function block is included in all IEDs. Line distance protection REL650 2.2 IEC Technical manual...
INTZERO is an integer number, fixed to integer value 0 • INTONE is an integer number, fixed to integer value 1 • INTALONE is an integer value FFFF (hex) • REALZERO is a floating point real number, fixed to 0.0 value Line distance protection REL650 2.2 IEC Technical manual...
Boolean to integer conversion, 16 bit (B16I) is used to transform a set of 16 boolean (logical) signals into an integer. 13.9.3 Function block SEMOD175798-5 v4 B16I BLOCK IN10 IN11 IN12 IN13 IN14 IN15 IN16 IEC07000128-2-en.vsd IEC07000128 V2 EN-US Figure 266: B16I function block Line distance protection REL650 2.2 IEC Technical manual...
Table 339: B16I Monitored data Name Type Values (Range) Unit Description INTEGER Output value 13.9.6 Settings ABBD8E283673 v3 The function does not have any parameters available in the local HMI or PCM600. Line distance protection REL650 2.2 IEC Technical manual...
The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can be converted to an integer by the B16I function block. Line distance protection REL650 2.2 IEC Technical manual...
The function does not have any parameters available in the local HMI or PCM600. 13.10.6 Monitored data PID-6944-MONITOREDDATA v2 Table 343: BTIGAPC Monitored data Name Type Values (Range) Unit Description INTEGER Output value Line distance protection REL650 2.2 IEC Technical manual...
The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can be converted to an integer by the BTIGAPC function block. Line distance protection REL650 2.2 IEC Technical manual...
OUTx = 0 for (5≤x≤16). OUTx represents a value when activated. The value of each of the OUTx is in accordance with the table IB16_1. When not activated the OUTx has the value 0. Line distance protection REL650 2.2 IEC Technical manual...
Page 519
The sum of the numbers in column “Value when activated” when all OUTx (where x = 1 to 16) are active that is=1; is 65535. 65535 is the highest integer that can be converted by the IB16 function block. Line distance protection REL650 2.2 IEC Technical manual...
PSTO ITBGAPC function block. The input BLOCK will freeze the output at the last received value and blocks new integer values to be received and converted to binary coded outputs. Line distance protection REL650 2.2 IEC Technical manual...
Elapsed time integrator TEIGAPC 13.13.2 Functionality GUID-390D7433-0C1C-48B4-9A90-71AA148C3C35 v3 Elapsed Time Integrator (TEIGAPC) function is a function that accumulates the elapsed time when a given binary signal has been high, see also Figure 270. Line distance protection REL650 2.2 IEC Technical manual...
BOOLEAN Freeze the integration and block the other outputs BOOLEAN The input signal that is used to measure the elapsed time, when its value is high RESET BOOLEAN Reset the integration time Line distance protection REL650 2.2 IEC Technical manual...
“Time Integration“ covers the logics for the first two items listed above while the block “Transgression Supervision Plus Retain“ contains the logics for the last two. Line distance protection REL650 2.2 IEC Technical manual...
Page 526
The ACCTIME output represents the integrated time in seconds while tOverflow, tAlarm and tWarning are the time limit parameters in seconds. tAlarm and tWarning are user settable limits. They are also independent, that is, there is no check if tAlarm > tWarning. Line distance protection REL650 2.2 IEC Technical manual...
Signed Signed Selection for absolute or signed Absolute comparison RefSource Set Value Set Value Selection for reference value either input Input REF or setting SetValue -2000000000 - Set value for reference 2000000000 Line distance protection REL650 2.2 IEC Technical manual...
If the input is above the reference value then INHIGH is set HIGH • If the input is below the reference value then INLOW is set HIGH • If the input is equal to reference value then INEQUAL is set HIGH Line distance protection REL650 2.2 IEC Technical manual...
It is a basic arithmetic function that can be used for monitoring, supervision, interlocking and other logics. 13.15.3 Function block GUID-8752DF2A-D131-4461-80C6-C52F9980D228 v1 REALCOMP INPUT INEQUAL INHIGH INLOW IEC15000053-1-en.vsdx IEC15000053 V1 EN-US Line distance protection REL650 2.2 IEC Technical manual...
Between 2 inputs, INPUT and REF Between INPUT and the SetValue setting The selection of reference value for comparison can be done through setting RefSource. If RefSource is selected as Input REF then the reference value for Line distance protection REL650 2.2 IEC Technical manual...
Page 532
If the INPUT is above the equal high level margin including hysteresis, then INHIGH will set. Similarly if the INPUT is below the equal low level margin including hysteresis, then INLOW will set. Line distance protection REL650 2.2 IEC Technical manual...
10 µ. GUID-3FDD7677-1D86-42AD-A545-B66081C49B47 v3 Table 365: Number of REALCOMP instances Function Quantity with cycle time 3 ms 8 ms 100 ms REALCOMP Line distance protection REL650 2.2 IEC Technical manual...
IEC 61850. The possibility to continuously monitor measured values of active power, reactive power, currents, voltages, frequency, power factor etc. is vital for efficient production, transmission and distribution of electrical energy. It Line distance protection REL650 2.2 IEC Technical manual...
Page 536
(DFT values) of the measured current and voltage signals. The measured power quantities are available either, as instantaneously calculated quantities or, averaged values over a period of time (low pass filtered) depending on the selected settings. Line distance protection REL650 2.2 IEC Technical manual...
Calculated current range REAL System frequency magnitude of deadband value F_RANGE INTEGER System frequency range PID-6735-INPUTSIGNALS v3 Table 368: CMMXU Input signals Name Type Default Description GROUP Group signal for current input SIGNAL Line distance protection REL650 2.2 IEC Technical manual...
Page 540
UL31 Amplitude, magnitude of reported value UL31RANG INTEGER UL31 Amplitude range UL31ANGL REAL UL31 Angle, magnitude of reported value PID-6736-INPUTSIGNALS v3 Table 372: CMSQI Input signals Name Type Default Description GROUP Group signal for current input SIGNAL Line distance protection REL650 2.2 IEC Technical manual...
Page 541
U2 Amplitude, magnitude of reported value U2RANG INTEGER U2 Amplitude range U2ANGL REAL U2 Angle, magnitude of reported value PID-6737-INPUTSIGNALS v2 Table 376: VNMMXU Input signals Name Type Default Description GROUP Group signal for voltage input SIGNAL Line distance protection REL650 2.2 IEC Technical manual...
200.0 Maximum value in % of SBase SRepTyp Cyclic Cyclic Reporting type Deadband Int deadband Db & Cyclic 5s Db & Cyclic 30s Db & Cyclic 1min Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 543
Db & Cyclic 5s Db & Cyclic 30s Db & Cyclic 1min Operation Operation Off / On GlobalBaseSel 1 - 12 Selection of one of the Global Base Value groups Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 544
-2000.0 - 2000.0 -150.0 Low Low limit in % of SBase QLimHyst 0.000 - 100.000 0.001 5.000 Hysteresis value in % of range, common for all limits Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 545
Zero point clamping in % of UBase IGenZeroDb 1 - 100 Zero point clamping in % of IBase UAmpComp5 -10.000 - 10.000 0.001 0.000 Amplitude factor to calibrate voltage at 5% of Ur Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 546
1 - 100000 Type Cycl: Report interval (s), Db: In 0,001% of range, Int Db: In 0,001%s IL3Min 0.0 - 500.0 50.0 Minimum value in % of IBase Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 547
Low limit in % of IBase IL3LowLowLim 0.0 - 500.0 60.0 Low Low limit in % of IBase IL3LimHys 0.000 - 100.000 0.001 5.000 Hysteresis value in % of range, common for all limits Line distance protection REL650 2.2 IEC Technical manual...
Page 548
Maximum value in % of UBase UL31RepTyp Cyclic Cyclic Reporting type Deadband Int deadband Db & Cyclic 5s Db & Cyclic 30s Db & Cyclic 1min UL31AngDbRepInt 1 - 100000 Cyclic report interval (s) Line distance protection REL650 2.2 IEC Technical manual...
Page 549
0.000 - 100.000 0.001 5.000 Hysteresis value in % of range, common for all limits 3I0AngDbRepInt 1 - 100000 Cyclic report interval (s) Operation Operation Mode On / Off Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 550
0.0 - 500.0 120.0 High limit in % of IBase I2LowLim 0.0 - 500.0 80.0 Low limit in % of IBase I2LowLowLim 0.0 - 500.0 60.0 Low Low limit in % of IBase Line distance protection REL650 2.2 IEC Technical manual...
Page 551
Db & Cyclic 5s Db & Cyclic 30s Db & Cyclic 1min U2LimHys 0.000 - 100.000 0.001 5.000 Hysteresis value in % of range, common for all limits Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 552
Db & Cyclic 5s Db & Cyclic 30s Db & Cyclic 1min UL1LimHys 0.000 - 100.000 0.001 5.000 Hysteresis value in % of range, common for all limits Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 553
Low limit in % of UBase UL2LowLowLim 0.0 - 200.0 60.0 Low Low limit in % of UBase UL3HiHiLim 0.0 - 200.0 150.0 High High limit in % of UBase Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
REAL IL2 Amplitude, magnitude of reported value IL2ANGL REAL IL2 Angle, magnitude of reported value REAL IL3 Amplitude, magnitude of reported value IL3ANGL REAL IL3 Angle, magnitude of reported value Line distance protection REL650 2.2 IEC Technical manual...
Page 555
Type Values (Range) Unit Description REAL 3U0 Amplitude, magnitude of reported value 3U0ANGL REAL 3U0 Angle, magnitude of reported value REAL U1 Amplitude, magnitude of reported value Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Locally by means of the local HMI • Remotely using the monitoring tool within PCM600 or over the station bus • Internally by connecting the analogue output signals to the Disturbance Report function Line distance protection REL650 2.2 IEC Technical manual...
Page 557
Each analogue output has one corresponding supervision level output (X_RANGE). The output signal is an integer in the interval 0-4 (0: Normal, 1: High limit exceeded, 3: High-high limit exceeded, 2: below Low limit and 4: below Low-low limit). Line distance protection REL650 2.2 IEC Technical manual...
Page 558
(XRepTyp). The measuring channel reports the value independent of amplitude or integral dead-band reporting. In addition to the normal cyclic reporting the IED also report spontaneously when measured value passes any of the defined threshold limits. Line distance protection REL650 2.2 IEC Technical manual...
Page 559
The picture is simplified: the process is not continuous but the values are evaluated with a time interval of one execution cycle from each other. Line distance protection REL650 2.2 IEC Technical manual...
Page 560
(as well as for the values Y3, Y4 and Y5). The integral dead-band supervision is particularly suitable for monitoring signals with small variations that can last for relatively long periods. Line distance protection REL650 2.2 IEC Technical manual...
Page 561
±ΔY predefined limits that are set by user (XDbRepInt), then the measuring channel reports the new value to a higher level immediately irrespective of cyclic trigger. See Figure for example. Line distance protection REL650 2.2 IEC Technical manual...
VT inputs connected to the IED. The end user can freely select by a parameter setting, which one of the nine available measuring modes shall be used within the function. Available options are summarized in the following table: Line distance protection REL650 2.2 IEC Technical manual...
Page 563
(Equation 67) EQUATION1396 V1 EN-US Used when × = × × only U phase-to- (Equation 68) earth voltage EQUATION1397 V1 EN-US is available (Equation 69) EQUATION1398 V1 EN-US Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 564
Binary output signal ILEAD is set TRUE when current phasor is leading the voltage phasor. Each analogue output has a corresponding supervision level output (X_RANGE). The output signal is an integer in the interval 0-4, see section "Measurement supervision". Line distance protection REL650 2.2 IEC Technical manual...
Page 565
P, Q, S, U, I and power factor. This will make slower measurement response to the step changes in the measured quantity. Filtering is performed in accordance with the following recursive formula: Line distance protection REL650 2.2 IEC Technical manual...
Page 566
If CT earthing parameter is set as described in section "Analog inputs", active and reactive power will be always measured towards the protected object. This is shown in the following figure 288. Line distance protection REL650 2.2 IEC Technical manual...
IEC 61850. This is achieved by amplitude and angle compensation at 5, 30 and 100% of rated current. The compensation below 5% and above 100% is constant and linear in between, see figure 287. Line distance protection REL650 2.2 IEC Technical manual...
S ≤0.5 x S (0.1-4.0) x I ±0.5% of S at S > 0.5 x S (100 to 220) V ±0.2% of P (0.5-2.0) x I cos φ< 0.7 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 569
±0.3% of I at I > 0.5 × I Phase angle (0.1–4.0) × I ±1.0 degrees at 0.1 × I < I ≤ 0.5 × I ±0.5 degrees at 0.5 × I < I ≤ 4.0 × I Line distance protection REL650 2.2 IEC Technical manual...
Insulation supervision for gas medium (SSIMG) is used for monitoring the circuit breaker condition. Binary information based on the gas pressure in the circuit breaker is used as input signals to the function. In addition, the function generates alarms based on received information. Line distance protection REL650 2.2 IEC Technical manual...
Pressure below alarm level or temperature above alarm level PRESALM BOOLEAN Pressure below alarm level TEMPALM BOOLEAN Temperature above alarm level PRESSURE REAL Pressure service value TEMP REAL Temperature of the insulation medium Line distance protection REL650 2.2 IEC Technical manual...
There may be sudden change in pressure of the gas for a very small time, for which the function need not to initiate any alarm. To avoid the intermittent alarm, two time delays tPressureAlarm or tPressureLO have been included. If the pressure Line distance protection REL650 2.2 IEC Technical manual...
Reset time delay for pressure (0.000-60.000) s ±0.2% or ±250ms whichever is alarm greater Time delay for pressure lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Time delay for level alarm tLevelLockOut 0.000 - 60.000 0.001 0.000 Time delay for level lockout indication tTempAlarm 0.000 - 60.000 0.001 0.000 Time delay for temperature alarm Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
TempLOLimit, temperature lockout TEMPLO will be initiated. There may be sudden change in temperature of the medium for a very small time, for which the function need not to initiate any alarm. To avoid the intermittent Line distance protection REL650 2.2 IEC Technical manual...
Pressure lockout indication from CB SPRCHRST BOOLEAN CB spring charging started indication signal SPRCHRD BOOLEAN CB spring charged indication signal RSTCBWR BOOLEAN Reset of CB remaining life and operation counter Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Rated operating current of the breaker OperNoRated 1 - 99999 10000 Number of operations possible at rated current RatedFltCurr 500.00 - 99999.99 0.01 5000.00 Rated fault current of the breaker Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 580
Initial value for accum I^CurrExponent integr over CB open travel time value InitInactDays 0 - 9999 Initial value for inactive days InactiveAlHrs 0 - 23 Hour Alarm time for inactive days counter in hours Line distance protection REL650 2.2 IEC Technical manual...
On and Off. The operation of the subfunctions is described by the module diagram as shown in figure 292. All the modules in the diagram are explained in subsequent sections. Line distance protection REL650 2.2 IEC Technical manual...
Page 583
POSOPEN auxiliary contact opens and the main contact is completely open. Therefore, a correction factor needs to be added to get the actual opening time. This factor is added with the OpenTimeCorr (t1+t2) setting. Line distance protection REL650 2.2 IEC Technical manual...
Page 584
POSOPEN input is high and the phase current is less than the setting AccStopCurr value. The circuit breaker is closed when the POSOPEN input is low and the POSCLOSE input is high. The breaker is in the error state if both auxiliary Line distance protection REL650 2.2 IEC Technical manual...
Page 585
When the remaining life of a circuit breaker phase drops below the CBLifeAlmLevel setting, the life alarm CBLIFEAL is activated. It is possible to deactivate the CBLIFEAL alarm signal by activating the binary input BLKALM. Line distance protection REL650 2.2 IEC Technical manual...
Page 586
ContTrCorr setting has passed. When the setting is negative, the calculation starts in advance by the correction time in relation to when the auxiliary contact opened. Line distance protection REL650 2.2 IEC Technical manual...
Page 587
The circuit breaker operation cycles subfunction counts the number of closing- opening sequences of the breaker. The operation counter value is updated after each closing-opening sequence. The operation is described in figure299. Line distance protection REL650 2.2 IEC Technical manual...
Page 588
The operation of the circuit breaker operation monitoring is shown in figure 300. POSCLOSE INADAYS Inactive timer POSOPEN Alarm limit MONALM BLOCK Check BLKALM IEC12000614 V2 EN-US Figure 300: Functional module diagram for circuit breaker operation monitoring Line distance protection REL650 2.2 IEC Technical manual...
Page 589
301. The last measured spring charging time SPCHT is provided as a service value. The spring charging time SPCHT can be reset on the LHMI or by activating the input RSTSPCHT. Line distance protection REL650 2.2 IEC Technical manual...
Page 590
Alarm level for number of (0 – 9999) operations Independent time delay for (0.00 – 60.00) s ±0.2% or ±30 ms whichever is spring charging time alarm greater Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 591
These events are created from any available signal in the IED that is connected to the Event function (EVENT). The EVENT function block is used for LON and SPA communication. Analog, integer and double indication values are also transferred through the EVENT function. Line distance protection REL650 2.2 IEC Technical manual...
Input 7 SIGNAL INPUT8 GROUP Input 8 SIGNAL INPUT9 GROUP Input 9 SIGNAL INPUT10 GROUP Input 10 SIGNAL INPUT11 GROUP Input 11 SIGNAL INPUT12 GROUP Input 12 SIGNAL Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Events are produced according to set event masks. The event masks are treated commonly for both the LON and SPA communication. An EventMask can be set individually for each input channel. These settings are available: Line distance protection REL650 2.2 IEC Technical manual...
Page 596
B1RBDR - B22RBDR 14.6.2 Functionality M12153-3 v13 Complete and reliable information about disturbances in the primary and/or in the secondary system together with continuous event-logging is accomplished by the disturbance report functionality. Line distance protection REL650 2.2 IEC Technical manual...
A3RADR: GRPINPUT21 to GRPINPUT30 (group signal for inputs 21 to 30) A4RADR block is used to record the calculated analog values of any type, not related to hardware devices (e.g. difference currents, power factors etc.). Line distance protection REL650 2.2 IEC Technical manual...
Page 600
B2RBDR: INPUT17 to INPUT32 (binary channels 17 to 32) • B3RBDR: INPUT33 to INPUT48 (binary channels 33 to 48) • B4RBDR: INPUT49 to INPUT64 (binary channels 49 to 64) • B5RBDR: INPUT65 to INPUT80 (binary channels 65 to 80) Line distance protection REL650 2.2 IEC Technical manual...
10 - 100 Maximum number of stored disturbances ZeroAngleRef 1 - 30 Trip value recorder, phasor reference channel OpModeTest Operation mode during test mode SetInfoInDRep Disable Enable Enable Disturbance report settings Enable functionality Line distance protection REL650 2.2 IEC Technical manual...
Page 602
Over trigger level for analog channel 2 in % of signal NomValue03 0.0 - 999999.9 Nominal value for analog channel 3 UnderTrigOp03 Use under level trigger for analog channel 3 (on) or not (off) Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 603
Use under level trigger for analog channel 8 (on) or not (off) UnderTrigLe08 0 - 200 Under trigger level for analog channel 8 in % of signal Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 604
A2RADR: 11 to 20 (NomValue11, nominal value for analog channel 11) • A3RADR: 21 to 30 (NomValue21, nominal value for analog channel 21) • A4RADR: 31 to 40 (NomValue31, nominal value for analog channel 31) Line distance protection REL650 2.2 IEC Technical manual...
Page 605
Start Trip Start and Trip TrigDR08 Trigger operation On/Off SetLED08 Set LED on HMI for binary channel 8 Start Trip Start and Trip TrigDR09 Trigger operation On/Off Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 606
Function type for binary channel 1 (IEC -60870-5-103) InfNo1 0 - 255 Information number for binary channel 1 (IEC -60870-5-103) FunType2 0 - 255 Function type for binary channel 2 (IEC -60870-5-103) Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 607
Function type for binary channel 13 (IEC -60870-5-103) InfNo13 0 - 255 Information number for binary channel 13 (IEC -60870-5-103) FunType14 0 - 255 Function type for binary channel 14 (IEC -60870-5-103) Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 608
Indication mask for binary channel 8 Show TrigLevel09 Trig on 0 Trig on 1 Trigger on positive (1) or negative (0) Trig on 1 slope for binary input 9 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 609
B12RBDR: 177 to 192 (SetLED177, set LED on HMI for binary channel 177) • B13RBDR: 193 to 208 (SetLED193, set LED on HMI for binary channel 193) • B14RBDR: 209 to 224 (SetLED209, set LED on HMI for binary channel 209) Line distance protection REL650 2.2 IEC Technical manual...
Page 610
B20RBDR: 305 to 320 (IndicationMa305, indication mask for binary channel 305) • B21RBDR: 321 to 336 (IndicationMa321, indication mask for binary channel 321) • B22RBDR: 337 to 352 (IndicationMa337, indication mask for binary channel 337) Line distance protection REL650 2.2 IEC Technical manual...
Over level trig for analog channel 8 activated UnTrigStatCh9 BOOLEAN Under level trig for analog channel 9 activated OvTrigStatCh9 BOOLEAN Over level trig for analog channel 9 activated Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 612
Over level trig for analog channel 18 activated UnTrigStatCh19 BOOLEAN Under level trig for analog channel 19 activated OvTrigStatCh19 BOOLEAN Over level trig for analog channel 19 activated Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 613
Over level trig for analog channel 28 activated UnTrigStatCh29 BOOLEAN Under level trig for analog channel 29 activated OvTrigStatCh29 BOOLEAN Over level trig for analog channel 29 activated Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 614
Over level trig for analog channel 38 activated UnTrigStatCh39 BOOLEAN Under level trig for analog channel 39 activated OvTrigStatCh39 BOOLEAN Over level trig for analog channel 39 activated Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
(BxRBDR). Trip value recorder (TVR) uses analog information from the analog input function blocks (AxRADR) which is used by FL after estimation by TVR. Disturbance recorder DRPRDRE acquires information from both AxRADR and BxRBDR. Line distance protection REL650 2.2 IEC Technical manual...
Page 616
All information in the disturbance report is stored in non-volatile flash memories. This implies that no information is lost in case of loss of auxiliary power. Each report will get an identification number in the interval from 0-999. Line distance protection REL650 2.2 IEC Technical manual...
Page 617
96 binary 6,3 s 6,3 s 50 Hz 6,3 s 60 Hz Total recording time 400 s en05000488.vsd IEC05000488 V1 EN-US Figure 310: Example of number of recordings versus the total recording time Line distance protection REL650 2.2 IEC Technical manual...
Page 618
During post processing of the disturbance record, the header file is updated with a section called Settings . Settings has complete setting values of the configured components that are read during the trigger time. The setting values, runtime status Line distance protection REL650 2.2 IEC Technical manual...
Page 619
The total recording time, tRecording, of a recorded disturbance is: tRecording = PreFaultrecT + tFault + PostFaultrecT or PreFaultrecT + TimeLimit , depending on which criterion stops the current disturbance recording Line distance protection REL650 2.2 IEC Technical manual...
Page 620
(3PHSUM). The last 10 channels may be connected to internally calculated analog signals available as function block output signals (mA input signals, phase differential currents, bias currents and so on). Line distance protection REL650 2.2 IEC Technical manual...
Page 621
The trigger is independent of the setting of Operation, and triggers even if operation is set to Off. Both undervoltage and overvoltage can be used as trigger conditions. The same applies for the current signals. Line distance protection REL650 2.2 IEC Technical manual...
Page 622
M12155-169 v4 Any binary signal state (logic one or a logic zero) can be selected to generate a trigger (Triglevel = Trig on 0/Trig on 1). When a binary signal is selected to Line distance protection REL650 2.2 IEC Technical manual...
Maximum number of indications in a disturbance report Maximum number of events in the Event recording per recording Maximum number of events in the 1000, first in - first out Event list Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU and VNMMXU), current and voltage sequence measurement functions (CMSQI and VMSQI) and IEC 61850 generic communication I/O functions (MVGAPC) are provided with measurement supervision functionality. All measured values can be Line distance protection REL650 2.2 IEC Technical manual...
The input signal must be connected to a range output of a measuring function block (CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGAPC). The function block converts the input integer value to five binary output signals according to table 436. Line distance protection REL650 2.2 IEC Technical manual...
Page 628
Especially on heavily loaded long lines, where the source voltage angles can be up to 35-40 degrees apart, the accuracy can be still maintained with the advanced compensation included in fault locator. Line distance protection REL650 2.2 IEC Technical manual...
L1 UL2Gain 0.000 - 10.000 0.001 1.000 Scale factor for fine tuning of voltage magnitude L2 UL3Gain 0.000 - 10.000 0.001 1.000 Scale factor for fine tuning of voltage magnitude L3 Line distance protection REL650 2.2 IEC Technical manual...
The calculation algorithm considers the effect of load currents, double-end infeed and additional fault resistance. DRPRDRE LMBRFLO IEC05000045_2_en.vsd IEC05000045 V2 EN-US Figure 317: Simplified network configuration with network data, required for settings of the fault location-measuring function Line distance protection REL650 2.2 IEC Technical manual...
Page 632
F from IED A on a line with the length L and impedance Z . The fault resistance is defined as R . A single-line model is used for better clarification of the algorithm. Line distance protection REL650 2.2 IEC Technical manual...
Page 633
For a single line, the value is equal to: × – ----------------------------------------- (Equation 81) EQUATION97 V1 EN-US Thus, the general fault location equation for a single line is: Line distance protection REL650 2.2 IEC Technical manual...
Page 634
(Equation 84) EQUATION100 V1 EN-US Where: is a zero sequence current of the parallel line, is a mutual zero sequence impedance and is the distribution factor of the parallel line, which is: Line distance protection REL650 2.2 IEC Technical manual...
Page 635
For a single line, Z = 0 and Z = 0. Thus, equation applies to both single and parallel lines. Equation can be divided into real and imaginary parts: Line distance protection REL650 2.2 IEC Technical manual...
Page 636
I103StatFltDis, FLTDISTX gives distance to fault (reactance, according the standard) and CALCMADE gives a pulse (100 ms) when a result is obtainable on FLTDISTX output. Line distance protection REL650 2.2 IEC Technical manual...
Moreover, the content of L4UFCNT is stored in flash memory and will not be lost at an auxiliary power interruption. Line distance protection REL650 2.2 IEC Technical manual...
Overflow indication when OnMaxValue is set to rollover pulsed The Error output is activated as an indicator of setting the counter limits and/or initial value setting(s) greater than the maximum value. The counter stops counting Line distance protection REL650 2.2 IEC Technical manual...
Page 639
Figure 321: L4UFCNT function block 14.10.5 Signals PID-6966-INPUTSIGNALS v2 Table 444: L4UFCNT Input signals Name Type Default Description BLOCK BOOLEAN Block of function INPUT BOOLEAN Input for counter RESET BOOLEAN Reset of function Line distance protection REL650 2.2 IEC Technical manual...
InitialValue 0 - 65535 Initial count value after reset of the function 14.10.7 Monitored data PID-6966-MONITOREDDATA v2 Table 447: L4UFCNT Monitored data Name Type Values (Range) Unit Description VALUE INTEGER Counted value Line distance protection REL650 2.2 IEC Technical manual...
Applicable to very long time accumulation (≤ 99999.9 hours) • Supervision of limit transgression conditions and rollover/overflow • Possibility to define a warning and alarm with the resolution of 0.1 hours • Retain any saved accumulation value at a restart Line distance protection REL650 2.2 IEC Technical manual...
WARNING BOOLEAN Indicator that accumulated time has reached warning limit OVERFLOW BOOLEAN Indicator that accumulated time has reached overflow limit ACC_HOUR REAL Accumulated time in hours ACC_DAY REAL Accumulated time in days Line distance protection REL650 2.2 IEC Technical manual...
ACC_HOUR Time Accumulation ACC_DAY ADDTIME tAddToTime Loop Delay IEC15000322.vsd IEC15000322 V1 EN-US Figure 324: TEILGAPC Simplified logic TEILGAPC main functionalities • IN: Accumulation of the elapsed time when input IN is high Line distance protection REL650 2.2 IEC Technical manual...
Page 644
The limit for the overflow supervision is fixed at 99999.9 hours. The outputs will reset and the accumulated time will reset and start from zero if an overflow occurs. 14.11.6.1 Operation accuracy GUID-B6FBEFD7-17C8-41C6-B5D5-32E1205E6752 v1 The accuracy of TEILGAPC depends on essentially two factors Line distance protection REL650 2.2 IEC Technical manual...
Page 645
(0 - 99999.9) hours ±0.1% of set value supervision, tAlarm Time limit for warning (0 - 99999.9) hours ±0.1% of set value supervision, tWarning Time limit for overflow Fixed to 99999.9 hours ±0.1% supervision Line distance protection REL650 2.2 IEC Technical manual...
The special Binary input module with enhanced pulse counting capabilities must be ordered to achieve this functionality. 15.1.3 Function block M13400-3 v5 PCFCNT BLOCK INVALID READ_VAL RESTART BI_PULSE* BLOCKED RS_CNT NEW_VAL SCAL_VAL IEC14000043-1-en.vsd IEC09000335 V3 EN-US Figure 325: PCFCNT function block Line distance protection REL650 2.2 IEC Technical manual...
Scaling value for SCAL_VAL output to unit per counted value Quantity Count Count Measured quantity for SCAL_VAL output ActivePower ApparentPower ReactivePower ActiveEnergy ApparentEnergy ReactiveEnergy tReporting 0 - 3600 Cycle time for reporting of counter value Line distance protection REL650 2.2 IEC Technical manual...
The pulse-counter logic function requires a binary input card, BIMp, that is specially adapted to the pulse-counter logic function. M13399-3 v9 Figure shows the pulse-counter logic function block with connections of the inputs and outputs. Line distance protection REL650 2.2 IEC Technical manual...
Page 650
The BLOCKED signal is a steady signal and is set when the counter is blocked. There are two reasons why the counter is blocked: • The BLOCK input is set, or • The Binary Input Module, where the counter input is situated, is inoperative. Line distance protection REL650 2.2 IEC Technical manual...
As output of this function: periodic energy calculations, integration of energy values, calculation of energy pulses, alarm signals for limit violation of energy values and maximum power demand, can be found. Line distance protection REL650 2.2 IEC Technical manual...
REAL Measured reactive power STARTACC BOOLEAN Start to accumulate energy values STOPACC BOOLEAN Stop to accumulate energy values. RSTACC BOOLEAN Reset of accumulated enery reading RSTDMD BOOLEAN Reset of maximum demand reading Line distance protection REL650 2.2 IEC Technical manual...
Time interval for energy calculation 5 Minutes 10 Minutes 15 Minutes 30 Minutes 60 Minutes 180 Minutes tEnergyOnPls 0.100 - 60.000 0.001 1.000 Energy accumulated pulse ON time in secs Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 654
Preset Initial value for reverse active 100000000.000 energy ERFPresetVal 0.000 - MVArh 0.001 0.000 Preset Initial value for forward reactive 100000000.000 energy ERRPresetVal 0.000 - MVArh 0.001 0.000 Preset Initial value for reverse reactive 100000000.000 energy Line distance protection REL650 2.2 IEC Technical manual...
The instantaneous output values of active and reactive power from the Measurements function CVMMXN are used and integrated over a selected time tEnergy to measure the integrated energy. Figure shows the overall functionality of the energy calculation and demand handling function ETPMMTR. Line distance protection REL650 2.2 IEC Technical manual...
Page 656
RSTACC. Figure shows the logic for integration of energy in active forward direction. Similarly, the integration of energy in active reverse, reactive forward and reactive reverse is done. Line distance protection REL650 2.2 IEC Technical manual...
Page 657
Similarly, the pulse generation for integrated energy in the active reverse, reactive forward and reactive reverse is done. Line distance protection REL650 2.2 IEC Technical manual...
Page 658
P (ACTIVE FORWARD) Average Power EAFALM Calculation a>b tEnergy EALim RSTMAXD MAXPAFD = unit delay IEC13000189-4-en.vsd IEC13000189 V4 EN-US Figure 332: Logic for maximum power demand calculation and energy alarm Line distance protection REL650 2.2 IEC Technical manual...
1MRK 506 382-UEN A Metering 15.2.8 Technical data 15.2.8.1 Technical data GUID-DA0A8AB5-755D-4F35-8C69-FFAA951FE374 v1 Table 463: Function Range or value Accuracy Energy metering MWh Export/Import, MVarh Input from MMXU. No extra Export/Import error at steady load Line distance protection REL650 2.2 IEC Technical manual...
0 - 18 255.255.255.0 Subnet mask of the access point Address Description 1 - 18 Station bus User editable access point description [1-18 char] Precision time protocol Slave only Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 662
Subnet mask of the access point Address Description 1 - 18 FrontPort User editable access point description [1-18 char] PCM600Access PCM600 access FTP and FTPS access IEC61850-8-1 MMS GOOSE IEC61850-8-1 GOOSE Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Ethernet ports, RCHLCCH is used for redundant communications over the rear Ethernet ports and FRONTSTATUS is used for communication over the front port. All access point function blocks include output signal for denial of service. Line distance protection REL650 2.2 IEC Technical manual...
Channel B redundancy status DOSALARM BOOLEAN Denial of service alarm (A + B) PID-6813-OUTPUTSIGNALS v3 Table 469: FRONTSTATUS Output signals Name Type Description LINKUP BOOLEAN Link status DOSALARM BOOLEAN Denial of service alarm Line distance protection REL650 2.2 IEC Technical manual...
The RCHLCCH function block supervise the redundant communication on the two channels. If no data package has been received on one (or both) channels within the last 10 s, the output LinkAUp and/or LinkBUp is set to 0 which indicates an error. Line distance protection REL650 2.2 IEC Technical manual...
Page 667
10 s, the output LinkAUp and/or LinkBUp is set to 0 which indicates an error. If IEEE1588 (PTP) is used an accuracy of 1 µs can be guaranteed for up to 15 devices in one HSR-ring. Line distance protection REL650 2.2 IEC Technical manual...
(or subscribers) in the system. Some merging units are able to get data from classical measuring transformers, others from non- conventional measuring transducers and yet others can pick up data from both types. Line distance protection REL650 2.2 IEC Technical manual...
MU not synced or MU 1=Error clock not synced to same clock as IED TESTMODE BOOLEAN 1=Yes Quality of one or more 0=No subscribed analogue channels is TEST Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 670
Oscillatory BOOLEAN 1=Yes Oscillatory indication 0=No output for I2 OutOfRange BOOLEAN 1=Yes OutOfRange indication 0=No output for I2 Overflow BOOLEAN 1=Yes Overflow indication 0=No output for I2 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 671
Inconsistent BOOLEAN 1=Yes Inconsistent indication 0=No output for I4 OldData BOOLEAN 1=Yes OldData indication 0=No output for I4 OperatorBlocked BOOLEAN 1=Yes OperatorBlocked 0=No indication output for I4 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 672
Derived BOOLEAN 1=Yes Derived indication output 0=No for U2 Failure BOOLEAN 1=Yes Failure indication output 0=No for U2 Inaccurate BOOLEAN 1=Yes Inaccurate indication 0=No output for U2 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 673
U3 Test BOOLEAN 1=Yes Test indication output for 0=No Validity INTEGER 0=Good Validity indication output 2=Reserved 1=Invalid 3=Questionable BadReference BOOLEAN 1=Yes BadReference indication 0=No output for U4 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
A route consists of a destination address and the address of the gateway to be used when sending data to the destination device, see Figure 339. Line distance protection REL650 2.2 IEC Technical manual...
User configurable name of the route [1-18 char] 16.5.3 Monitored data PID-6761-MONITOREDDATA v2 Table 477: ROUTE_1 Monitored data Name Type Values (Range) Unit Description RouteConfig INTEGER 0=Ok Route configuration 1=Error status -1=Off Line distance protection REL650 2.2 IEC Technical manual...
Diagnostics/IED status/Protocol diagnostics. The diagnostic values are: Diagnostic value Description Protocol is turned off Error An error has occured, refer to event list for more information Warning Configuration inconsistency. Unable to locate data point. Ready Protocol is ready Line distance protection REL650 2.2 IEC Technical manual...
(IEDs) from different vendors to exchange information and simplifies system engineering. IED-to-IED communication using GOOSE and client-server communication over MMS are supported. Disturbance recording file (COMTRADE) uploading can be done over MMS or FTP. Line distance protection REL650 2.2 IEC Technical manual...
Generic communication function for Single Point indication (SPGAPC) is used to send one single logical signal to other systems or equipment in the substation. 17.4.5.2 Function block SEMOD54714-4 v4 SPGAPC BLOCK IEC14000021-1-en.vsd IEC14000021 V1 EN-US Figure 341: SPGAPC function block Line distance protection REL650 2.2 IEC Technical manual...
SIGNAL OUT14 GROUP Output 14 status SIGNAL OUT15 GROUP Output 15 status SIGNAL OUT16 GROUP Output 16 status SIGNAL OUTOR GROUP Output status logic OR SIGNAL gate for input 1 to 16 Line distance protection REL650 2.2 IEC Technical manual...
Name Type Default Description BLOCK BOOLEAN Block of function REAL Analog input value PID-6753-OUTPUTSIGNALS v1 Table 486: MVGAPC Output signals Name Type Description VALUE REAL Magnitude of deadband value RANGE INTEGER Range Line distance protection REL650 2.2 IEC Technical manual...
17.4.6.5 Monitored data PID-6753-MONITOREDDATA v1 Table 488: MVGAPC Monitored data Name Type Values (Range) Unit Description VALUE REAL Magnitude of deadband value RANGE INTEGER 1=High Range 2=Low 3=High-High 4=Low-Low 0=Normal Line distance protection REL650 2.2 IEC Technical manual...
GOOSE connections. These connections are visible and possible to make only if Easy GOOSE engineering is enabled. For instructions on how to enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual. Line distance protection REL650 2.2 IEC Technical manual...
Incoming data with q=Normal Updated Incoming data with q=oldData Incoming data with q=Invalid Incoming data with q=test Incoming data with q=test+oldData Receiver in block Receiver in block and communication error Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
GOOSEINTRCV is used to receive an integer value using IEC 61850 protocol via GOOSE. 17.4.8.3 Function block GUID-56F0C9F7-98F3-4091-B071-53CA5074DC8F v1 GOOSEINTRCV BLOCK ^INTOUT ^SRCINTOUT DATAVALID COMMVALID TEST IEC10000250-2-en.vsd IEC10000250 V2 EN-US Figure 345: GOOSEINTRCV function block Line distance protection REL650 2.2 IEC Technical manual...
The COMMVALID output will become LOW when the sending IED is under total failure condition and the GOOSE transmission from the sending IED does not happen. The TEST output will go HIGH if the sending IED is in test mode. Line distance protection REL650 2.2 IEC Technical manual...
ANSI/IEEE C37.2 identification identification device number GOOSE function block to receive a GOOSEMVRCV measurand value 17.4.9.2 Functionality GUID-759CB016-2B4D-4D98-82E1-592044983D53 v3 GOOSEMVRCV is used to receive measured value using IEC 61850 protocol via GOOSE. Line distance protection REL650 2.2 IEC Technical manual...
GOOSEMVRCV Non group settings (basic) Name Values (Range) Unit Step Default Description Operation Operation Off/On 17.4.9.6 Operation principle GUID-7B24A6D3-2E5F-4961-A0A6-86436373809E v5 The DATAVALID output will be HIGH if the incoming message is with valid data. Line distance protection REL650 2.2 IEC Technical manual...
GOOSE function block to receive a single point value GOOSESPRCV 17.4.10.1 Identification GUID-F2B30A70-842E-435E-8FAB-B1E58B9C0164 v1 Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2 identification identification device number GOOSE function block to receive a GOOSESPRCV single point value Line distance protection REL650 2.2 IEC Technical manual...
BOOLEAN Communication valid for single point output TEST BOOLEAN Test output 17.4.10.5 Settings PID-6832-SETTINGS v3 Table 500: GOOSESPRCV Non group settings (basic) Name Values (Range) Unit Step Default Description Operation Operation Off/On Line distance protection REL650 2.2 IEC Technical manual...
If quality data validity is GOOD then the DATAVALID output will be HIGH. If quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the DATAVALID output will be LOW. Line distance protection REL650 2.2 IEC Technical manual...
BOOLEAN Apparatus 1 position is valid APP2_OP BOOLEAN Apparatus 2 position is open APP2_CL BOOLEAN Apparatus 2 position is closed APP2VAL BOOLEAN Apparatus 2 position is valid Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 696
BOOLEAN Apparatus 14 position is closed APP14VAL BOOLEAN Apparatus 14 position is valid APP15_OP BOOLEAN Apparatus 15 position is open APP15_CL BOOLEAN Apparatus 15 position is closed Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
SMT by means of a cross or in ACT by means of a GOOSE connection (if easy GOOSE engineering is enabled) to receive any data. Only those outputs whose source input is linked/ connected will be updated. Line distance protection REL650 2.2 IEC Technical manual...
GOOSE connections. These connections are visible and possible to make only if Easy GOOSE engineering is enabled. For instructions on how to enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual. Line distance protection REL650 2.2 IEC Technical manual...
Page 699
Valid data on binary output 6 OUT7 BOOLEAN Binary output 7 DVALID7 BOOLEAN Valid data on binary output 7 OUT8 BOOLEAN Binary output 8 DVALID8 BOOLEAN Valid data on binary output 8 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
The TEST output will go HIGH if the sending IED is in test mode. Data Value Data Valid Comm Valid Test Incoming data with q=Normal Updated Incoming data with q=oldData Incoming data with q=Invalid Incoming data with q=test Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
XCBR/XSWI logical node sent over process bus via GOOSE. The GOOSE XLN Receive component includes 12 different outputs (and their respective channel valid bits) with defined names to ease the 61850 mapping of the GOOSE signals in the configuration process. Line distance protection REL650 2.2 IEC Technical manual...
Source to operation counter SRCBLK BOOLEAN Source to dynamic blocking of function described by the LN SRCSTSELD BOOLEAN Source to the controllable data is in the status "selected” Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 703
Valid data on opOk output EEHEALTH INTEGER External equipment health EEHEALTH_VLD BOOLEAN Valid data on EEHealth output OPCAP INTEGER Operating capability OPCAP_VLD BOOLEAN Valid data on OpCap output COMMVALID BOOLEAN Communication valid TEST BOOLEAN Test output Line distance protection REL650 2.2 IEC Technical manual...
Merging Units (MU). The rear access points are used for the communication. 17.5.2 Function block GUID-2581F3AD-7487-4C80-BDF3-9C6EC9F2E43C v3 The function blocks are not represented in the configuration tool. The signals appear only in the SMT tool when merging units (MU) Line distance protection REL650 2.2 IEC Technical manual...
U1QUALITY INTEGER Binary coded quality information for U1 U2QUALITY INTEGER Binary coded quality information for U2 U3QUALITY INTEGER Binary coded quality information for U3 U4QUALITY INTEGER Binary coded quality information for U4 Line distance protection REL650 2.2 IEC Technical manual...
Failure BOOLEAN 1=Yes Failure indication output 0=No for I1 Inaccurate BOOLEAN 1=Yes Inaccurate indication 0=No output for I1 Inconsistent BOOLEAN 1=Yes Inconsistent indication 0=No output for I1 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 707
Validity INTEGER 0=Good Validity indication output 2=Reserved 1=Invalid 3=Questionable BadReference BOOLEAN 1=Yes BadReference indication 0=No output for I3 Derived BOOLEAN 1=Yes Derived indication output 0=No for I3 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 708
I4 Overflow BOOLEAN 1=Yes Overflow indication 0=No output for I4 Source BOOLEAN 0=Process Source indication output 1=Substituted for I4 Test BOOLEAN 1=Yes Test indication output for 0=No Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 709
OperatorBlocked BOOLEAN 1=Yes OperatorBlocked 0=No indication output for U2 Oscillatory BOOLEAN 1=Yes Oscillatory indication 0=No output for U2 OutOfRange BOOLEAN 1=Yes OutOfRange indication 0=No output for U2 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 710
Inaccurate BOOLEAN 1=Yes Inaccurate indication 0=No output for U4 Inconsistent BOOLEAN 1=Yes Inconsistent indication 0=No output for U4 OldData BOOLEAN 1=Yes OldData indication 0=No output for U4 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
The IED communicates with the MUs over the process bus via the rear access points. For the user, the MU appears in the IED as a normal analogue input module and is engineered in the very same way. Line distance protection REL650 2.2 IEC Technical manual...
Page 712
Ok[0] indicates that the merging unit samples are received from the merging unit and are accepted. • ERROR[1] indicates that the merging unit samples are generated by internal substitution. • SYNCH: • OK[0] indicates Line distance protection REL650 2.2 IEC Technical manual...
Page 713
SyncLostMode = NoBlock, the merging unit samples are not received • TESTMODE: • NO[0] indicates that No merging unit analog channels are in testmode • YES[1] indicates that one/more subscribed channels are in testmode • SIMMODE: Line distance protection REL650 2.2 IEC Technical manual...
Page 714
61850-9-2LE source malfunctions. Figure shows an example where MU1 malfunctions, and all function blocks connected to that 3-phase group get blocked as a result, this is also known as conditional blocking functionality. Line distance protection REL650 2.2 IEC Technical manual...
The source status of the quality as described in IEC 61850-7-3 is expanded to Process and Substituted (SUBST) outputs. The other quality statuses (Test, Operator Blocked (OPBLKD) and Derived) are shown as they are. Line distance protection REL650 2.2 IEC Technical manual...
These networks are characterized by high speed for data transfer, short messages (few bytes), peer-to-peer communication, multiple communication media, low maintenance, multivendor equipment, and low support costs. LonTalk supports the needs of applications that cover a range of requirements. The protocol Line distance protection REL650 2.2 IEC Technical manual...
The LonTalk protocol supports two types of application layer objects: network variables and explicit messages. Network variables are used to deliver short Line distance protection REL650 2.2 IEC Technical manual...
Page 718
Add LON Device Types LNT M15083-19 v3 A new device is added to LON Network Tool from the Device menu or by installing the device from the ABB LON Device Types package for LNT 505 using SLDT package version 1p2 r04. LON net address M15083-22 v3 To establish a LON connection, the IED has to be given a unique net address.
Page 720
Both the SPA-bus command messages (R or W) and the reply messages (D, A or N) are sent using the same message code. It is mandatory that one device sends out Line distance protection REL650 2.2 IEC Technical manual...
Page 721
1 I 5499 SPA parameters for block command BL_CMD SCSWI18 1 I 5523 SPA parameters for block command BL_CMD SCSWI19 1 I 5545 SPA parameters for block command Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 722
1 I 5299 SPA parameters for cancel command CANCEL SCSWI10 1 I 5323 SPA parameters for cancel command CANCEL SCSWI11 1 I 5347 SPA parameters for cancel command Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 723
SELECTOpen=00, SCSWI01 1 I 5105 SPA parameters for select (Open/ SELECTClose=01, Close) command SELOpen+ILO=10, Note: Send select command SELClose+ILO=11, before operate command SELOpen+SCO=20, SELClose+SCO=21, SELOpen+ILO+SCO=30, SELClose+ILO+SCO=31 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 724
1 I 5657 SPA parameters for select (Open/ SELECTClose=01, so on. Close) command SELECTOpen=00, SCSWI25 1 I 5681 SPA parameters for select (Open/ SELECTClose=01, so on. Close) command Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 725
SCSWI14 1 I 5418 SPA parameters for operate ExcClose=01, so on. (Open/Close) command ExcOpen=00, SCSWI15 1 I 5442 SPA parameters for operate ExcClose=01, so on. (Open/Close) command Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 726
Sub Value SXCBR05 2 I 7923 SPA parameter for position to be substituted Sub Value SXCBR06 2 I 7942 SPA parameter for position to be substituted Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 727
Sub Value SXSWI11 3 I 378 SPA parameter for position to be substituted Sub Value SXSWI12 3 I 397 SPA parameter for position to be substituted Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 728
SPA parameter for substitute enable command Sub Enable SXCBR06 2 I 7941 SPA parameter for substitute enable command Sub Enable SXCBR07 2 I 7962 SPA parameter for substitute enable command Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 729
SPA parameter for substitute enable command Sub Enable SXSWI12 3 I 398 SPA parameter for substitute enable command Sub Enable SXSWI13 3 I 417 SPA parameter for substitute enable command Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 730
SPA parameter for update block command Update Block SXCBR08 2 I 7981 SPA parameter for update block command Update Block SXCBR09 3 I 6 SPA parameter for update block command Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 731
SPA parameter for update block command Update Block SXSWI14 3 I 434 SPA parameter for update block command Update Block SXSWI15 3 I 453 SPA parameter for update block command Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 732
Configure the Network variables according to the specific application using the LON network tool (LNT). The following is an example of how to configure network variables concerning, for example, interlocking between two IEDs. Line distance protection REL650 2.2 IEC Technical manual...
Page 733
Download area in the bottom of the program window and drop them there; or, they can perform it by selecting the traditional menu, Configuration/ Download. Line distance protection REL650 2.2 IEC Technical manual...
Page 734
(ADM), and it is used for LON, SPA, IEC 60870-5-103 and DNP communication. In the following figure, X311 ports A/B are for SPA, IEC103 or DNP3 and X311 ports C/D are for LON protocol. Line distance protection REL650 2.2 IEC Technical manual...
TX transmitter output. Pay special attention to the instructions concerning handling and connection of fibre cables. 17.6.4 Technical data IP14442-1 v1 M11927-1 v2 Table 518: LON communication protocol Function Value Protocol Communication speed 1.25 Mbit/s Line distance protection REL650 2.2 IEC Technical manual...
Page 740
This is set in Parameter Setting Tool (PST) under: Main Menu/Settings / IED Settings / Control / Commands / Single Command or via Parameter Setting Tool (PST). Line distance protection REL650 2.2 IEC Technical manual...
Page 741
Signals coming from different protection and control functions and sent as events to the station level over the SPA-bus (or LON-bus), are connected to the EVENT function block as specified in Figure 359. Line distance protection REL650 2.2 IEC Technical manual...
(ADM). It is used for LON, SPA, IEC 60870-5-103 and DNP communication. In the following figure, X311 ports A/B are for SPA, IEC103 or DNP3 and X311 ports C/D are for LON protocol. Line distance protection REL650 2.2 IEC Technical manual...
Application manual and Commissioning manual respectively. 17.7.5 Technical data IP14404-1 v1 M11901-1 v2 Table 524: SPA communication protocol Function Value Protocol Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Slave number 1 to 899 Line distance protection REL650 2.2 IEC Technical manual...
Page 744
3.2 = IL2 AND UL1L2 AND NOT 3.3 3.1 = IL2 AND NOT (3.2 OR 3.3 OR 9) 17.8.2.2 Identification GUID-3E1AB624-1B68-4018-B1BA-BC2C811F8F74 v1 Function description Function block IEC 60617 ANSI/IEEE C37.2 name identification device number Measurands for IEC 60870-5-103 I103MEAS Line distance protection REL650 2.2 IEC Technical manual...
MaxIL1 1 - 99999 3000 Maximum current phase L1 MaxIL2 1 - 99999 3000 Maximum current phase L2 MaxIL3 1 - 99999 3000 Maximum current phase L3 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Maximum value for measurement on 10000000000.00 input 7 MaxMeasur8 0.05 - 0.05 1000.00 Maximum value for measurement on 10000000000.00 input 8 MaxMeasur9 0.05 - 0.05 1000.00 Maximum value for measurement on 10000000000.00 input 9 Line distance protection REL650 2.2 IEC Technical manual...
Page 748
130_BLKD BOOLEAN Information number 130, auto-recloser blocked 17.8.4.5 Settings PID-3973-SETTINGS v5 Table 530: I103AR Non group settings (basic) Name Values (Range) Unit Step Default Description FunctionType 1 - 255 Function type (1-255) Line distance protection REL650 2.2 IEC Technical manual...
Page 749
52_EFREV BOOLEAN Information number 52, earth-fault reverse 17.8.5.5 Settings PID-3974-SETTINGS v5 Table 532: I103EF Non group settings (basic) Name Values (Range) Unit Step Default Description FunctionType 1 - 255 Function type (1-255) Line distance protection REL650 2.2 IEC Technical manual...
Page 750
Disturbance Recorder and the respective configured signal to the IEC 60870-5-103 I103FLTPROT. 17.8.6.2 Identification GUID-55593EC4-7AED-47A0-8311-DB22D013A193 v1 Function description Function block IEC 60617 ANSI/IEEE C37.2 name identification device number Function status fault protection for IEC I103FLTPROT 60870-5-103 Line distance protection REL650 2.2 IEC Technical manual...
Information number 70, trip phase L2 71_TRL3 BOOLEAN Information number 71, trip phase L3 72_TRBKUP BOOLEAN Information number 72, back up trip I>> 73_SCL REAL Information number 73, fault location in ohm Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
FLTLOC BOOLEAN Faultlocator faultlocation valid (LMBRFLO- CALCMADE) 17.8.6.5 Settings PID-6864-SETTINGS v1 Table 534: I103FLTPROT Non group settings (basic) Name Values (Range) Unit Step Default Description FunctionType 1 - 255 Function type (1-255) Line distance protection REL650 2.2 IEC Technical manual...
Page 753
Information number 23, setting group 1 is active 24_GRP2 BOOLEAN Information number 24, setting group 2 is active 25_GRP3 BOOLEAN Information number 25, setting group 3 is active 26_GRP4 BOOLEAN Information number 26, setting group 4 is active Line distance protection REL650 2.2 IEC Technical manual...
I103SUPERV Input signals Name Type Default Description BLOCK BOOLEAN Block of status reporting 32_MEASI BOOLEAN Information number 32, measurand supervision of 33_MEASU BOOLEAN Information number 33, measurand supervision of Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
See Settings for details. 17.8.9.2 Identification GUID-474FDF39-CEFC-4370-9393-13BE62159969 v2 Function description Function block IEC 60617 ANSI/IEEE C37.2 name identification device number Status for user defined signals for IEC I103USRDEF 60870-5-103 Line distance protection REL650 2.2 IEC Technical manual...
Relative time is assigned only to inputs where the corresponding TypNo parameter is set to Relative. The maximum relative time and unit conform to the IEC 60870-5-103 standard. Line distance protection REL650 2.2 IEC Technical manual...
GiNo3 Excluded Included Response and status change (GI) Included GiNo4 Excluded Included Response and status change (GI) Included GiNo5 Excluded Included Response and status change (GI) Included Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 758
IEC 60617 ANSI/IEEE C37.2 name identification device number Function commands for IEC I103CMD 60870-5-103 17.8.10.3 Function block GUID-C0680812-C488-4546-AA65-F590955DBF0C v1 I103CMD BLOCK 16-AR 17-DIFF 18-PROT IEC10000282-1-en.vsd IEC10000282 V1 EN-US Figure 369: I103CMD function block Line distance protection REL650 2.2 IEC Technical manual...
All outputs are pulsed and they are NOT stored. Pulse length is fixed to 400ms. 17.8.11.2 Identification GUID-0D0B2477-1B0C-48F3-B047-CCF9C7A71856 v1 Function description Function block IEC 60617 ANSI/IEEE C37.2 name identification device number IED commands for IEC 60870-5-103 I103IEDCMD Line distance protection REL650 2.2 IEC Technical manual...
I103USRCMD is a command block in control direction with user defined output signals. These function blocks include the FunctionType parameter for each block in the private range, and the Information number parameter for each output signal. Line distance protection REL650 2.2 IEC Technical manual...
17.8.13.2 Identification GUID-1933A30C-5214-4116-8CD3-91BD975FACED v1 Function description Function block IEC 60617 ANSI/IEEE C37.2 name identification device number Function commands generic for IEC I103GENCMD 60870-5-103 Line distance protection REL650 2.2 IEC Technical manual...
IEC 60870-5-103 link. Additionally, it listens for general interrogation (GI) requests and replies to those with a GI response message with the current state of each connected input. Line distance protection REL650 2.2 IEC Technical manual...
I103POSCMD function block 17.8.14.4 Signals PID-6997-INPUTSIGNALS v1 Table 553: I103POSCMD Input signals Name Type Default Description BLOCK BOOLEAN Block of status reporting POSITION INTEGER Position of controllable object SELECT BOOLEAN Select of controllable object Line distance protection REL650 2.2 IEC Technical manual...
60870-5-103 identifier that associates a function in a 103 Master (such as Scada) with its equivalent in the IED. 17.8.15.2 Identification GUID-2249B679-03E4-43CC-B690-916246FE6A31 v1 Function description Function block IEC 60617 ANSI/IEEE C37.2 name identification device number IED direct commands with position for I103POSCMDV IEC 60870-5-103 Line distance protection REL650 2.2 IEC Technical manual...
Introduction to IEC 60870–5–103 protocol M11874-6 v3 IEC 60870-5-103 protocol functionality consists of the following functions: • Event handling • Report of analog service values (measurements) • Fault location • Command handling Line distance protection REL650 2.2 IEC Technical manual...
Page 767
Activate setting group 4 Function commands in control direction, pre-defined I103CMD M11874-53 v6 Function command block in control direction with defined output signals. Number of instances: 1 Function type is selected with parameter FunctionType. Line distance protection REL650 2.2 IEC Technical manual...
Page 768
M11874-109 v7 Indication block for status in monitor direction with defined IED functions. Number of instances: 1 Function type is selected with parameter FunctionType. Information number is defined for each input signals. Line distance protection REL650 2.2 IEC Technical manual...
Page 769
Supervision indications in monitor direction, I103SUPERV M11874-171 v7 Indication block for supervision in monitor direction with defined functions. Number of instances: 1 Function type is selected with parameter FunctionType. Information number is defined for output signals. Line distance protection REL650 2.2 IEC Technical manual...
Page 770
CB on by Autorecloser Autorecloser blocked Function status fault protection for IEC 60870-5-103, I103FLTPROT GUID-E9DF9410-F570-4F85-9063-C76D1D4A0668 v6 Number of instances: 1 Function type is selected with parameter FunctionType. Information number is defined for each input signal. Line distance protection REL650 2.2 IEC Technical manual...
Page 771
Function blocks in monitor direction for input measurands. Typically connected to monitoring function, for example to power measurement CVMMXN. Measurands in public range, I103MEAS M11874-385 v8 Number of instances: 1 The IED reports all valid measuring types depending on connected signals. Line distance protection REL650 2.2 IEC Technical manual...
Page 772
Q, reactive power f, frequency Measurands in private range, I103MEASUSR M11874-431 v5 Number of instances: 3 Function type parameter for each block in private range. Information number must be selected for measurands. Line distance protection REL650 2.2 IEC Technical manual...
Page 773
5 on disturbance function block A1RADR • connected to channel 6 on disturbance function block A1RADR • connected to channel 7 on disturbance function block A1RADR • connected to channel 8 on disturbance function block A1RADR Line distance protection REL650 2.2 IEC Technical manual...
Page 774
Disturbance data initiated by other events [1] Another information element in ASDU23 is the FAN (fault number). According to the standard this is a number that is incremented when a protection function takes Line distance protection REL650 2.2 IEC Technical manual...
Page 775
Selection of standard ASDUs in monitoring direction ASDU Time-tagged message Time-tagged message with rel. time Measurands I Time-tagged message with rel. time Identification Time synchronization End of general interrogation Measurands II Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
TX transmitter output. When the fibre optic cables are laid out, pay special attention to the instructions concerning the handling and connection of the optical fibres. The module is identified with a number on the label on the module. Line distance protection REL650 2.2 IEC Technical manual...
This means that no connected function block may have a cycle time that is higher than the execution cycle time of the particular MULTICMDRCV instance. Line distance protection REL650 2.2 IEC Technical manual...
MULTICMDSND function blocks. There are 60 instances of the MULTICMDRCV where the first 12 are fast (8 ms), and the others are slow (100 ms). Additionally, the MULTICMDRCV has a supervision Line distance protection REL650 2.2 IEC Technical manual...
There can be 6 external log servers to send syslog events to. Each server can be configured with IP address; IP port number and protocol format. The format can be either syslog (RFC 5424) or Common Event Format (CEF) from ArcSight. Line distance protection REL650 2.2 IEC Technical manual...
IED and the PCM600 is implemented at both access points to the IED: • local, through the local HMI • remote, through the communication ports The IED users can be created, deleted and edited with PCM600 IED user management tool. Line distance protection REL650 2.2 IEC Technical manual...
Ensure that the user logged on to the IED has the access required when writing particular data to the IED from PCM600. The meaning of the legends used in the table: • R= Read • W= Write • - = No access rights Line distance protection REL650 2.2 IEC Technical manual...
Page 785
If the IED is Central Account Management enabled, users can only be created, deleted or edited in the Central Account Management server. In that case, only the user rights can be edited using the PCM600 tool. See Cyber Security Deployment Guidelines manual. Line distance protection REL650 2.2 IEC Technical manual...
The users, their roles and rights are created, deleted and edited only in the Central Account Management server (SDM600). However, the user rights can be edited in the IED by using the PCM600 user tool. Line distance protection REL650 2.2 IEC Technical manual...
Page 787
Changes in user management settings do not cause an IED reboot. The PCM600 tool caches the login credentials after successful login for 15 minutes. During that time no more login will be necessary. Line distance protection REL650 2.2 IEC Technical manual...
Page 788
The IED users can be created, deleted and edited only in the CAM server. Authority This function enables/disables the maintenance menu. It also controls the management maintenance menu logon time out. AUTHMAN Line distance protection REL650 2.2 IEC Technical manual...
FTP access with SSL FTPACCS 18.3.2 FTP access with TLS, FTPACCS GUID-9E64EA68-6FA9-4576-B5E9-92E3CC6AA7FD v3 The FTP Client defaults to the best possible security mode when trying to negotiate with TLS. Line distance protection REL650 2.2 IEC Technical manual...
Authority status ATHSTAT 18.4.2 Functionality SEMOD158529-5 v6 Authority status ATHSTAT function is an indication function block for user log-on activity. User denied attempt to log-on and user successful log-on are reported. Line distance protection REL650 2.2 IEC Technical manual...
Whenever one of the two events occurs, the corresponding output (USRBLKED or LOGGEDON) is activated. The output can for example, be connected on Event (EVENT) function block for LON/SPA.The signals are also available on IEC 61850 station bus. Line distance protection REL650 2.2 IEC Technical manual...
Application startup block 18.5.4 Settings ABBD8E15533 v3 The function does not have any parameters available in the local HMI or PCM600. 18.5.5 Operation principle IP11943-1 v2 M11401-3 v12 The self-supervision operates continuously and includes: Line distance protection REL650 2.2 IEC Technical manual...
Page 793
Figure 381: Self-supervision event list in local HMI A self-supervision summary can be obtained by means of an output relay with potential free alarm contact (INTERNAL FAIL) located on the power supply Line distance protection REL650 2.2 IEC Technical manual...
Error threads. The actions can be loading of settings status or parameters for components, changing of setting groups, loading or unloading of application threads. Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 795
Activated if the module has a hardware Module error. Error n = slot number status NUM-Error Numerical NUM30 Activated if the module has a hardware /CPU or software error. Module Error status Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
The purpose is to block inadvertent IED configuration changes beyond a certain point in time. The change lock function activation is normally connected to a binary input. Line distance protection REL650 2.2 IEC Technical manual...
Control operations • Set system time • Enter and exit from test mode • Change of active setting group The binary input signal LOCK controlling the function is defined in ACT or SMT: Line distance protection REL650 2.2 IEC Technical manual...
DOSALARM indicates that DOS functionality is active on the access point • SCHLCCH and FRONTSTATUS • LINKUP indicates the Ethernet link status • DOSALARM indicates that DOS functionality is active on the access point Line distance protection REL650 2.2 IEC Technical manual...
Page 799
Section 18 1MRK 506 382-UEN A Security The DOS functionality activates when the inbound traffic rate exceeds 3000 packets per second. Line distance protection REL650 2.2 IEC Technical manual...
Time (UTC). The Synchronization group relates to selecting the coarse and fine synchronization sources. All the settings and parameters related to time are available via Local HMI under Main menu/Configuration/Time/System time and via PCM600 under IED Configuration/Time. Line distance protection REL650 2.2 IEC Technical manual...
Page 802
The source of the SNTP time SNTPMaster 0 - 16 The IP-adress of the SNTP master GPSNumberOfSats -1 - 12 GPS satellites used in calculation of time PTPOwnId 0 - 16 PTP own clock identity Line distance protection REL650 2.2 IEC Technical manual...
Page 803
Port number in the IED to communicate with the SNTP server PID-6212-SETTINGS v5 Table 594: DSTENABLE Non group settings (basic) Name Values (Range) Unit Step Default Description DST Enable Enables or disables the use of Daylight Saving Time Line distance protection REL650 2.2 IEC Technical manual...
Page 804
WeekInMonth Last Last Week in month when daylight time starts First Second Third Fourth UTCTimeOfDay -24:00 1:00 UTC Time of day in hours when daylight -23:30 time starts -00:30 00:00 00:30 48:00 Line distance protection REL650 2.2 IEC Technical manual...
Page 805
WeekInMonth Last Last Week in month when daylight time ends First Second Third Fourth UTCTimeOfDay -24:00 1:00 UTC Time of day in hours when daylight -23:30 time ends -00:30 00:00 00:30 48:00 Line distance protection REL650 2.2 IEC Technical manual...
Page 806
Step Default Description SynchType Opto Type of synchronization Opto TimeDomain LocalTime LocalTime Time domain Encoding IRIG-B IRIG-B Type of encoding 1344 1344TZ TimeZoneAs1344 MinusTZ PlusTZ Time zone as in 1344 standard PlusTZ Line distance protection REL650 2.2 IEC Technical manual...
Design of the time system (clock synchronization) GUID-E2B9E81C-5733-4521-B27F-BF33E05CCFB0 v8 The time system is based on software and hardware clocks that run independently from each other (see Figure 383). Line distance protection REL650 2.2 IEC Technical manual...
Page 808
The Fast and Slow settings are also available on the local HMI. SyncLostMode is not required to set as Block/BlockonLostUTC when differential protection is based on ECHO mode. Line distance protection REL650 2.2 IEC Technical manual...
Page 809
This gives the function the possibility to choose the source with the best quality, and to adjust its internal clock based on this source. The maximum error of a clock can be defined as: Line distance protection REL650 2.2 IEC Technical manual...
. In the IED, the rate accuracy at cold start is 2 ppm but if the IED is synchronized for a while, the rate accuracy is approximately 0.2 ppm if the surrounding temperature is constant. Line distance protection REL650 2.2 IEC Technical manual...
• Fine message is sent every second and comprises only seconds and milliseconds. The SLM module is located on the first analog digital conversion module (ADM) Line distance protection REL650 2.2 IEC Technical manual...
Page 812
IEC05000251 V1 EN-US Figure 385: Binary minute pulses The default time-out-time for a minute pulse is two minutes, and if no valid minute pulse is received within two minutes a SYNCERR will be given. Line distance protection REL650 2.2 IEC Technical manual...
Page 813
If the x is 0, 1, 2 or 3, the information contains only the time within the year, and year information has to be set via PCM600 or local HMI. Line distance protection REL650 2.2 IEC Technical manual...
PTP group if there is no better source available in the group. The IED can be connected to several groups and thereby connect them to each other, by acting as a “Boundary Clock”. If PTP is “On” on several Access Points, Line distance protection REL650 2.2 IEC Technical manual...
1 ms Time tagging error with synchronization once/min (minute pulse ± 1.0 ms typically synchronization), events and sampled measurement values Time tagging error with SNTP synchronization, sampled ± 1.0 ms typically measurement values Line distance protection REL650 2.2 IEC Technical manual...
ACTGRP3 BOOLEAN Selects setting group 3 as active ACTGRP4 BOOLEAN Selects setting group 4 as active ACTGRP5 BOOLEAN Selects setting group 5 as active ACTGRP6 BOOLEAN Selects setting group 6 as active Line distance protection REL650 2.2 IEC Technical manual...
The external control signals are used for activating a suitable setting group when adaptive functionality is necessary. Input signals that should activate setting groups must be either permanent or a pulse exceeding 400 ms. Line distance protection REL650 2.2 IEC Technical manual...
Page 818
GRP6 SETCHGD REMSETEN IEC05000119-3-en.vsd IEC05000119 V3 EN-US Figure 387: Connection of the function to external circuits The above example also includes seven output signals, for confirmation of which group that is active. Line distance protection REL650 2.2 IEC Technical manual...
BOOLEAN In test via IED TEST or via LD0 Mode IED_TEST BOOLEAN IED test mode is active BLOCK BOOLEAN Active when LD0 is blocked or test blocked Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
M11828-3 v8 The deblocking is reseted when exiting test mode. The blocking of a function concerns all output signals from the actual function, so no outputs will be activated. Line distance protection REL650 2.2 IEC Technical manual...
Page 821
IED main function type for IEC60870-5-103 TechnicalKey 0 - 16 AA0B0Q0A0 Technical key (part 1) 0 - 16 Technical key (part 2) 0 - 16 Technical key (part 3) 0 - 16 Technical key (part 4) Line distance protection REL650 2.2 IEC Technical manual...
Page 822
OrderingNo • ProductionDate • IEDProdType This information is very helpful when interacting with ABB product support (for example during repair and maintenance). 19.5.2 Settings GUID-168CD792-8811-43B5-8760-74ED82DE17F7 v4 The function does not have any parameters available in the local HMI or PCM600.
These names will be represented in SMT as information which signals shall be connected between physical IO and SMBI function. The input/ output user defined name will also appear on the respective output/input signal. Line distance protection REL650 2.2 IEC Technical manual...
Page 825
Signal name for BO7 in Signal Matrix Tool BOOLEAN Signal name for BO8 in Signal Matrix Tool BOOLEAN Signal name for BO9 in Signal Matrix Tool BO10 BOOLEAN Signal name for BO10 in Signal Matrix Tool Line distance protection REL650 2.2 IEC Technical manual...
2 • n=25–36 in task group 3 The task time defines the execution repetition rate, and is 1, 3 or 8 respectively for the three task time groups. Line distance protection REL650 2.2 IEC Technical manual...
DFT reference function G1AI3P GROUP SIGNAL Group 1 analog input 3-phase group G1AI1 GROUP SIGNAL Group 1 analog input 1 G1AI2 GROUP SIGNAL Group 1 analog input 2 Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
19.8.4 Settings SEMOD55783-1 v2 SEMOD130357-4 v3 Settings DFTRefExtOut and DFTReference shall be set to default value InternalDFTRef if no VT inputs are available. Internal nominal frequency DFT reference is then the reference. Line distance protection REL650 2.2 IEC Technical manual...
Page 829
Current Table 617: SMAI1 Non group settings (advanced) Name Values (Range) Unit Step Default Description Negation Negation NegateN Negate3Ph Negate3Ph+N MinValFreqMeas 5 - 200 Limit for frequency calculation in % of UBase Line distance protection REL650 2.2 IEC Technical manual...
GRPxL1, GRPxL2, GRPxL3 and GRPxN, x=1-12. GxN (x = 1-12) is always calculated residual sum from the first three inputs. A3P is grouped, three- phase information containing all relevant information about four connected inputs. Line distance protection REL650 2.2 IEC Technical manual...
Page 831
MinValFreqMeas. If SMAI setting ConnectionType is Ph-N and the same voltage is connected to all three SMAI inputs, the positive sequence voltage will be zero and the frequency functions will not work properly. Line distance protection REL650 2.2 IEC Technical manual...
Page 832
Block input for group 2 REVROT BOOLEAN Reverse rotation G1AI3P GROUP Group 1 three phase analog input from first SMAI SIGNAL G2AI3P GROUP Group 2 three phase analog input from second SIGNAL SMAI Line distance protection REL650 2.2 IEC Technical manual...
DFT reference for external output DFTRefGrp1 External DFT ref Table 623: 3PHSUM Non group settings (advanced) Name Values (Range) Unit Step Default Description FreqMeasMinVal 5 - 200 Amplitude limit for frequency calculation in % of UBase Line distance protection REL650 2.2 IEC Technical manual...
Values (Range) Unit Step Default Description UBase 0.05 - 2000.00 0.05 400.00 Global base voltage IBase 1 - 99999 3000 Global base current SBase 1.00 - 200000.00 0.05 2000.00 Global base apparent power Line distance protection REL650 2.2 IEC Technical manual...
Page 835
PID-1626-SETTINGS v17 Table 625: PRIMVAL Non group settings (basic) Name Values (Range) Unit Step Default Description Frequency 50.0 - 60.0 10.0 50.0 Rated system frequency PhaseRotation Normal=L1L2L3 Normal=L1L2L3 System phase rotation Inverse=L3L2L1 Line distance protection REL650 2.2 IEC Technical manual...
Section 20 IED hardware 20.1 Overview IP14270-1 v1 20.1.1 Variants of case size with local HMI display M15024-3 v5 IEC04000458-2-en.psd IEC04000458 V2 EN-US Figure 395: 1/2 19” case with local HMI display. Line distance protection REL650 2.2 IEC Technical manual...
2 fast signalling outputs. Serial SPA/LON/IEC 60870-5-103 Used for SPA/LON/IEC 60870–5–103 communication modules (SLM) communication Optical Ethernet SFP Small form factor pluggable for Ethernet communication Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Up to four SFP transceivers for optical 100BASE-FX or galvanic RJ45 100BASE- TX communication can be mounted in the SFP cages. Only SPF transceivers approved by ABB (1MRK005500) are compatible with the SFP cages. Application code and configuration data are stored in flash memory, and non- volatile RAM is used to store log data.
IP14278-1 v1 M6377-3 v2 There are two types of the power supply module. They are designed for different DC input voltage ranges see table 632. The power supply module contains a built- Line distance protection REL650 2.2 IEC Technical manual...
The module has twelve inputs in different combinations of currents and voltage inputs. Alternative connectors of Ring lug or Compression type can be ordered. Line distance protection REL650 2.2 IEC Technical manual...
The TRM is connected to the ADM and NUM. For configuration of the input and output signals, refer to section "Signal matrix for analog inputs SMAI". 1MRK006501-AF-TRM-IEC-6502P1 V1 EN-US Figure 397: TRM connection diagram Line distance protection REL650 2.2 IEC Technical manual...
PMC cards as described in Table 634. The SLM card should always be mounted on the first ADM module. Table 634: PC-MIP cards and PMC cards PC-MIP cards PMC cards SR-LDCM MR-LDCM IRIG-B RS485 Line distance protection REL650 2.2 IEC Technical manual...
The A\D converted signals goes through a filter with a cut off frequency of 500 Hz and are reported to the numerical module (NUM) with 1 kHz at 50 Hz system frequency and 1,2 kHz at 60 Hz system frequency. Line distance protection REL650 2.2 IEC Technical manual...
Inputs are debounced by software. I/O events are time stamped locally on each module for minimum time deviance and stored by the event recorder if present. Line distance protection REL650 2.2 IEC Technical manual...
Page 848
The design of all binary inputs enables the burn off of the oxide of the relay contact connected to the input, despite the low, steady-state power consumption, which is shown in figure and 401. Line distance protection REL650 2.2 IEC Technical manual...
Page 849
Approximate binary input inrush current for the standard version of BIM. [mA] [ms] en07000105-1.vsd IEC07000105 V2 EN-US Figure 401: Approximate binary input inrush current for the BIM version with enhanced pulse counting capabilities. Line distance protection REL650 2.2 IEC Technical manual...
Binary input 1 value BOOLEAN Binary input 2 value BOOLEAN Binary input 3 value BOOLEAN Binary input 4 value BOOLEAN Binary input 5 value BOOLEAN Binary input 6 value Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Settable 1-20 ms 20.2.8 Binary output modules (BOM) IP14536-1 v1 20.2.8.1 Introduction M6938-3 v4 The binary output module has 24 independent output relays and is used for trip output or any signaling purpose. Line distance protection REL650 2.2 IEC Technical manual...
Continued activation is possible with respect to current consumption but after 5 minutes the temperature rise will adversely affect the hardware life. Maximum two relays per BOM/IOM should be activated continuously due to power dissipation. Line distance protection REL650 2.2 IEC Technical manual...
For configuration of the input and output signals, refer to sections "Signal matrix for binary inputs SMBI" "Signal matrix for binary outputs SMBO". The making capacity of the reed relays are limited. Line distance protection REL650 2.2 IEC Technical manual...
Page 861
The test voltage across open contact is lower for this version of the binary input/output module. Line distance protection REL650 2.2 IEC Technical manual...
800 V DC 1 min Current carrying capacity Per relay, continuous Per relay, 1 s 10 A 10 A Per process connector pin, 12 A 12 A continuous Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
Page 866
48 V/1 A 48 V/1 A L/R < 40 ms 110 V/0.4 A 110 V/0.4 A 220 V/0.2 A 220 V/0.2 A 250 V/0.15 A 250 V/0.15 A Maximum capacitive load 10 nF Line distance protection REL650 2.2 IEC Technical manual...
I E C 0 5 0 0 7 6 0 = 1 = e n = O r i g i n a l . p s d IEC05000760 V2 EN-US Figure 407: SLM variants, component side view Receiver, LON Transmitter, LON Receiver, SPA/IEC 60870-5-103/DNP3 Transmitter, SPA/IEC 60870-5-103/DNP3 Snap-in connector for plastic fiber ST connector for glass fiber Line distance protection REL650 2.2 IEC Technical manual...
The 4-wire connection has separated signals for RX and TX multidrop communication with a dedicated Master and the rest are slaves. No special control signal is needed in this case. Line distance protection REL650 2.2 IEC Technical manual...
(also called sine wave modulated). The other is an optical input type ST for optical pulse-width modulated signal (IRIG-B 00X). The IRIG-B module is mounted as a mezzanine card on the Analog digital conversion module (ADM). Line distance protection REL650 2.2 IEC Technical manual...
SEMOD141132-1 v1 SEMOD141136-2 v8 Table 658: IRIG-B Quantity Rated value Number of channels IRIG-B Number of optical channels Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Table continues on next page Line distance protection REL650 2.2 IEC Technical manual...
62.5/125 μm multimode fibre Supported formats IRIG-B 00x Accuracy +/- 1μs 20.3 Dimensions IP11490-1 v3 20.3.1 Case with rear cover SEMOD53199-1 v1 M11985-110 v4 IEC05000501 V2 EN-US Figure 410: Case with rear cover Line distance protection REL650 2.2 IEC Technical manual...
Page 873
M11985-120 v4 Case size (mm) 6U, 1/2 x 19” 265.9 223.7 242.1 255.8 205.7 190.5 203.7 465.1 228.6 482.6 The H and K dimensions are defined by the 19” rack mounting kit. Line distance protection REL650 2.2 IEC Technical manual...
Flush mounting Cut-out dimensions (mm) Case size Tolerance +/-1 +/-1 6U, 1/2 x 19" 210.1 254.3 4.0-10.0 13.5 E = 191.1 mm without rear protection cover, 231.8 mm with rear protection cover Line distance protection REL650 2.2 IEC Technical manual...
IED. Flush mounting cannot be used for side-by-side mounted IEDs when IP54 class must be fulfilled. Only IP20 class can be obtained when mounting two cases side-by-side in one (1) cut-out. Line distance protection REL650 2.2 IEC Technical manual...
19” panel rack mounting IP10313-1 v1 20.4.2.1 Overview SEMOD127656-5 v4 The IED can be mounted in a standard 19” cubicle rack by using a mounting kit consisting of two mounting angles and their fastening screws. Line distance protection REL650 2.2 IEC Technical manual...
PCBs inside the IED. If fiber cables are bent too much, the signal can be weakened. Wall mounting is therefore not recommended for any communication modules with fiber connection. Line distance protection REL650 2.2 IEC Technical manual...
The IED can be equipped with a rear protection cover recommended to be used with this type of mounting. See figure 422. To reach the rear side of the IED, a free space of 80 mm is required on the unhinged side. Line distance protection REL650 2.2 IEC Technical manual...
Use only the screws included in the mounting kit when mounting the plates and the angles on the IED. Screws with wrong dimension may damage the PCBs inside the IED. Line distance protection REL650 2.2 IEC Technical manual...
RTXP 24. It also has enough space for a terminal base of RX 2 type for mounting of, for example, a DC-switch or two auxiliary relays. Line distance protection REL650 2.2 IEC Technical manual...
IED. Screws with wrong dimension may damage the PCBs inside the IED. Please contact factory for special add on plates for mounting FT switches on the side (for 1/2 19" case) or bottom of the relay. Line distance protection REL650 2.2 IEC Technical manual...
Maximum conductor area Screw compression type 250 V AC 2.5 mm (AWG14) 2 × 1 mm (2 x AWG18) Terminal blocks suitable for 300 V AC 3 mm (AWG14) ring lug terminals Line distance protection REL650 2.2 IEC Technical manual...
±3.0 Hz for 60 Hz Harmonic frequency ±1.0% and 5 harmonic of f dependence (20% content) Harmonic frequency ±10.0% and 5 harmonic of f dependence for distance protection (10% content) Line distance protection REL650 2.2 IEC Technical manual...
IEC 60255-27 (SFP galvanic RJ45: 1.0 kV, ANSI C37.90 IEEE 802.3-2015, 1 min.) Environment A Impulse voltage test 5 kV, 1.2/50 ms, 0.5 J Insulation resistance > 100 MW at 500 VDC Line distance protection REL650 2.2 IEC Technical manual...
Page 889
Vibration endurance test Class I IEC 60255-21-1 Shock response test Class I IEC 60255-21-2 Shock withstand test Class I IEC 60255-21-2 Bump test Class I IEC 60255-21-2 Seismic test Class II IEC 60255-21-3 Line distance protection REL650 2.2 IEC Technical manual...
Ordering and serial number Manufacturer Transformer designations Transformer input module, rated currents and voltages Optional, customer specific information Order number, dc supply voltage and rated frequency Product type, description and serial number Product type Line distance protection REL650 2.2 IEC Technical manual...
Page 892
IEC15000573=2=en=Original.wsdx IEC15000573 V2 EN-US Warning label Caution label Class 1 laser product label It is used when an optical SFP or an MR LDCM is configured in the product. IEC06000575 V1 EN-US Line distance protection REL650 2.2 IEC Technical manual...
Three overcurrent protections operating in series Stage 3 Time Stage 2 Stage 2 Stage 1 Stage 1 Stage 1 Fault point position en05000130.vsd IEC05000130 V1 EN-US Figure 428: Definite time overcurrent characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 896
Opening time of the breaker closest to the studied fault • Reset times of the protections • Margin dependent of the time delay inaccuracy of the protections Assume we have the following network case. Line distance protection REL650 2.2 IEC Technical manual...
Page 897
In some applications it is however beneficial to have some type of delayed reset time of the overcurrent function. This can be the case in the following applications: Line distance protection REL650 2.2 IEC Technical manual...
A, B, C are constants defined for each curve type, in> is the set start current for step n, is set time multiplier for step n and is the measured current. Line distance protection REL650 2.2 IEC Technical manual...
Page 899
For inverse time operation, the inverse time characteristic is selectable. Both the IEC and ANSI/IEEE standardized inverse time characteristics are supported. For the IEC curves there is also a setting of the minimum time-lag of operation, see figure 431. Line distance protection REL650 2.2 IEC Technical manual...
Page 900
÷ × 0.339 0.235 è ø (Equation 98) EQUATION1194 V1 EN-US where: in> is the set start current for step n is set time multiplier for step n is the measured current Line distance protection REL650 2.2 IEC Technical manual...
Page 901
If ANSI reset time is chosen the reset time will be dependent of the current after fault clearance (when the current drops below the start current level minus the hysteresis). The timer will reset according to equation 101. Line distance protection REL650 2.2 IEC Technical manual...
Page 902
Thus, if only the inverse time delay is required, it is important to set the definite time delay for that stage to zero. Line distance protection REL650 2.2 IEC Technical manual...
ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02, tr=4.85 ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0, tr=30 ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0, tr=13.46 ANSI Long Time Inverse A=0.086, B=0.185, P=0.02, tr=4.6 Line distance protection REL650 2.2 IEC Technical manual...
Page 904
±40 ms whichever is greater × 0.236 0.339 EQUATION1137-SMALL V1 EN-US I = I measured RD type logarithmic inverse characteristic æ ö ç × ÷ 1.35 è ø EQUATION1138-SMALL V1 EN-US I = I measured Line distance protection REL650 2.2 IEC Technical manual...
Page 905
ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02, tr=4.85 ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0, tr=30 ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0, tr=13.46 ANSI Long Time Inverse A=0.086, B=0.185, P=0.02, tr=4.6 Line distance protection REL650 2.2 IEC Technical manual...
Page 906
PR=(0.005-3.000) in steps of 0.001 EQUATION1253-SMALL V1 EN-US I = I measured The parameter setting Characterist1 and 4/Reserved shall not be used, since this parameter setting is for future use and not implemented yet. Line distance protection REL650 2.2 IEC Technical manual...
Page 907
ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02, tr=4.85 ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0, tr=30 ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0, tr=13.46 ANSI Long Time Inverse A=0.086, B=0.185, P=0.02, tr=4.6 Line distance protection REL650 2.2 IEC Technical manual...
Page 908
× ÷ steps of 0.01 è ø > C = (0.0-1.0) in steps EQUATION1439-SMALL V1 EN-US of 0.1 D = (0.000-60.000) in steps of 0.001 P = (0.000-3.000) in steps of 0.001 Line distance protection REL650 2.2 IEC Technical manual...
Page 909
ë è ø û < steps of 0.1 D = (0.000-60.000) EQUATION1433-SMALL V1 EN-US U< = U in steps of 0.001 U = U P = (0.000-3.000) in measured steps of 0.001 Line distance protection REL650 2.2 IEC Technical manual...
Page 910
ç × ÷ steps of 0.01 è ø > C = (0.0-1.0) in steps of EQUATION1439-SMALL V1 EN-US D = (0.000-60.000) in steps of 0.001 P = (0.000-3.000) in steps of 0.001 Line distance protection REL650 2.2 IEC Technical manual...
Page 911
Section 23 1MRK 506 382-UEN A Inverse time characteristics SEMOD118114-4 v4 A070750 V2 EN-US Figure 432: ANSI Extremely inverse time characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 912
Section 23 1MRK 506 382-UEN A Inverse time characteristics A070751 V2 EN-US Figure 433: ANSI Very inverse time characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 913
Section 23 1MRK 506 382-UEN A Inverse time characteristics A070752 V2 EN-US Figure 434: ANSI Normal inverse time characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 914
Section 23 1MRK 506 382-UEN A Inverse time characteristics A070753 V2 EN-US Figure 435: ANSI Moderately inverse time characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 915
Section 23 1MRK 506 382-UEN A Inverse time characteristics A070817 V2 EN-US Figure 436: ANSI Long time extremely inverse time characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 916
Section 23 1MRK 506 382-UEN A Inverse time characteristics A070818 V2 EN-US Figure 437: ANSI Long time very inverse time characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 917
Section 23 1MRK 506 382-UEN A Inverse time characteristics A070819 V2 EN-US Figure 438: ANSI Long time inverse time characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 918
Section 23 1MRK 506 382-UEN A Inverse time characteristics A070820 V2 EN-US Figure 439: IEC Normal inverse time characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 919
Section 23 1MRK 506 382-UEN A Inverse time characteristics A070821 V2 EN-US Figure 440: IEC Very inverse time characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 920
Section 23 1MRK 506 382-UEN A Inverse time characteristics A070822 V2 EN-US Figure 441: IEC Inverse time characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 921
Section 23 1MRK 506 382-UEN A Inverse time characteristics A070823 V2 EN-US Figure 442: IEC Extremely inverse time characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 922
Section 23 1MRK 506 382-UEN A Inverse time characteristics A070824 V2 EN-US Figure 443: IEC Short time inverse time characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 923
Section 23 1MRK 506 382-UEN A Inverse time characteristics A070825 V2 EN-US Figure 444: IEC Long time inverse time characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 924
Section 23 1MRK 506 382-UEN A Inverse time characteristics A070826 V2 EN-US Figure 445: RI-type inverse time characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 925
Section 23 1MRK 506 382-UEN A Inverse time characteristics A070827 V2 EN-US Figure 446: RD-type inverse time characteristics Line distance protection REL650 2.2 IEC Technical manual...
Page 926
Section 23 1MRK 506 382-UEN A Inverse time characteristics GUID-ACF4044C-052E-4CBD-8247-C6ABE3796FA6 V1 EN-US Figure 447: Inverse curve A characteristic of overvoltage protection Line distance protection REL650 2.2 IEC Technical manual...
Page 927
Section 23 1MRK 506 382-UEN A Inverse time characteristics GUID-F5E0E1C2-48C8-4DC7-A84B-174544C09142 V1 EN-US Figure 448: Inverse curve B characteristic of overvoltage protection Line distance protection REL650 2.2 IEC Technical manual...
Page 928
Section 23 1MRK 506 382-UEN A Inverse time characteristics GUID-A9898DB7-90A3-47F2-AEF9-45FF148CB679 V1 EN-US Figure 449: Inverse curve C characteristic of overvoltage protection Line distance protection REL650 2.2 IEC Technical manual...
Page 929
Section 23 1MRK 506 382-UEN A Inverse time characteristics GUID-35F40C3B-B483-40E6-9767-69C1536E3CBC V1 EN-US Figure 450: Inverse curve A characteristic of undervoltage protection Line distance protection REL650 2.2 IEC Technical manual...
Page 930
Section 23 1MRK 506 382-UEN A Inverse time characteristics GUID-B55D0F5F-9265-4D9A-A7C0-E274AA3A6BB1 V1 EN-US Figure 451: Inverse curve B characteristic of undervoltage protection Line distance protection REL650 2.2 IEC Technical manual...
Binary signal transfer function, receiver blocks Binary signal transfer function, transmit blocks C37.94 IEEE/ANSI protocol used when sending binary signals between IEDs Controller Area Network. ISO standard (ISO 11898) for serial communication Circuit breaker Combined backplane module Line distance protection REL650 2.2 IEC Technical manual...
Page 932
DARPA Defense Advanced Research Projects Agency (The US developer of the TCP/IP protocol etc.) DBDL Dead bus dead line DBLL Dead bus live line Direct current Data flow control Discrete Fourier transform Line distance protection REL650 2.2 IEC Technical manual...
Page 933
Function type G.703 Electrical and functional description for digital lines used by local telephone companies. Can be transported over balanced and unbalanced lines Communication interface module with carrier of GPS receiver module Line distance protection REL650 2.2 IEC Technical manual...
Page 934
PCI specifications from the PCI SIG (Special Interest Group) for the electrical EMF (Electromotive force). IEEE 1686 Standard for Substation Intelligent Electronic Devices (IEDs) Cyber Security Capabilities Intelligent electronic device IET600 Integrated engineering tool Line distance protection REL650 2.2 IEC Technical manual...
Page 935
LON network tool Local operating network Miniature circuit breaker Mezzanine carrier module Main processing module MVAL Value of measurement Multifunction vehicle bus. Standardized serial bus originally developed for use in trains. National Control Centre Line distance protection REL650 2.2 IEC Technical manual...
Page 936
Reduced instruction set computer RMS value Root mean square value RS422 A balanced serial interface for the transmission of digital data in point-to-point connections RS485 Serial link according to EIA standard RS485 Real-time clock Line distance protection REL650 2.2 IEC Technical manual...
Page 937
Ethernet and the Internet. TCP/IP Transmission control protocol over Internet Protocol. The de facto standard Ethernet protocols incorporated into 4.2BSD Unix. TCP/IP was developed by DARPA for Internet working and encompasses both network layer and Line distance protection REL650 2.2 IEC Technical manual...
Page 938
"Zulu time." "Zulu" in the phonetic alphabet stands for "Z", which stands for longitude zero. Undervoltage Weak end infeed logic Voltage transformer Line distance protection REL650 2.2 IEC Technical manual...
Page 939
Glossary Three times zero-sequence current.Often referred to as the residual or the earth-fault current Three times the zero sequence voltage. Often referred to as the residual voltage or the neutral point voltage Line distance protection REL650 2.2 IEC Technical manual...