ABB REL650 Product Manual

Line distance protection
Hide thumbs Also See for REL650:

Advertisement

®
Relion
650 series
Line distance protection REL650 ANSI
Product guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB REL650

  • Page 1 ® Relion 650 series Line distance protection REL650 ANSI Product guide...
  • Page 2: Table Of Contents

    Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
  • Page 3: Series Overview

    • Minimized rule based parameter settings based on default Three packages of configured solution have been defined for values and ABB's global base value concept. You only need to following applications: set those parameters specific to your own installed and activated application.
  • Page 4 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 132 kV Bus BUS1 REL650 A01A – 5 Distance Zones, Single Breaker 10AI (4I+1I+5U) BUS2 132kV/110V 132kV/110V 0->1 1->0 SYNC 289G SMB RREC SMP PTRC SES RSYN Meter.
  • Page 5 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 REL650 B01A – 5 Distance Zones, Double Breaker Ring Bus 10AI (4I+1I+5U) + 10AI (4I+1I+5U) 0->1 1->0 SYNC SMB RREC SMP PTRC SES RSYN 132kV/ 0->1 1->0 SYNC...
  • Page 6 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 132 kV Bus BUS1 REL650A11A-5 DistanceZones, 1PH/3 PH Tripping Single Breaker 10AI(4I+1I+5U) BUS2 132kV/110V 132kV/110V 289G 0->1 1->0 25 SYNC STB RREC STP PTRC SES RSYN Meter. Meter.
  • Page 7 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3...
  • Page 8: Available Functions

    Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 3. Available functions Main protection functions IEC 61850 or ANSI Function description Line Distance Function name Impedance protection ZQMPDIS Five zone distance protection, quadrilateral and mho characteristic FDPSPDIS...
  • Page 9: Voltage Protection

    Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Back-up protection functions IEC 61850 or ANSI Function description Line Distance Function name Current protection PHPIOC Instantaneous phase overcurrent protection, 3–phase output 0–1 SPTPIOC Instantaneous phase overcurrent protection, phase segregated output 0–1...
  • Page 10: Secondary System Supervision

    Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Control and monitoring functions IEC 61850 or ANSI Function description Line Distance Function name Control SESRSYN Synchrocheck, energizing check, and synchronizing 0–2 SMBRREC Autorecloser for 3–phase operation 0–2 STBRREC Autorecloser for 1/3–phase operation...
  • Page 11 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 IEC 61850 or ANSI Function description Line Distance Function name INVERTER Configurable logic blocks PULSETIMER Configurable logic blocks GATE Configurable logic blocks Configurable logic blocks LOOPDELAY Configurable logic blocks...
  • Page 12 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 IEC 61850 or ANSI Function description Line Distance Function name VMMXU Phase-phase voltage measurement CMSQI Current sequence component measurement VMSQI Voltage sequence measurement VNMMXU Phase-neutral voltage measurement AISVBAS...
  • Page 13 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 IEC 61850 or ANSI Function description Line Distance Function name I103SUPERV Supervison status for IEC60870-5-103 I103USRDEF Status for user defined signals for IEC60870-5-103 Metering PCGGIO Pulse counter ETPMMTR...
  • Page 14 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Station communication IEC 61850 or Function ANSI Function description Line Distance name Station communication IEC61850-8-1 IEC 61850 communication protocol DNPGEN DNP3.0 communication general protocol RS485DNP DNP3.0 for RS-485 communication protocol CH1TCP DNP3.0 for TCP/IP communication protocol...
  • Page 15: Scheme Communication

    Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 IEC 61850 or Function ANSI Function description Line Distance name AGSAL Generic security application component GOOSEDPRCV GOOSE function block to receive a double point value GOOSEINTRCV GOOSE function block to receive an integer value...
  • Page 16 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Basic IED functions IEC 61850/Function Function description block name Basic functions included in all products INTERRSIG Self supervision with internal event list SELFSUPEVLST Self supervision with internal event list...
  • Page 17 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Five zone distance protection, quadrilateral and mho Build-in adaptive load compensation algorithm prevents characteristic ZQMPDIS (21) is designed to operate in the overreaching of Zone 1 at phase-to-ground faults on heavily following modes for phase-to-ground and phase-to-phase loops: loaded power lines.
  • Page 18 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Phase preference logic inhibits tripping for single phase-to- Faulty phase identification with load encroachment FMPSPDIS ground faults in isolated and high impedance grounded networks, (21) where such faults are not to be cleared by distance protection.
  • Page 19 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 The directional function is voltage polarized with memory. The IDir, VPol and IPol can be independently selected to be either zero function can be set to be directional or non-directional sequence or negative sequence.
  • Page 20 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 An alarm pickup gives early warning to allow operators to take tripping of surrounding breakers at an incorrect initiation due to action well before the line is tripped.
  • Page 21 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 sequence source is weak or open, the forward source impedance Two step residual overvoltage protection ROV2PTOV (59N) is strong and it is desired to detect forward ground faults.
  • Page 22 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 SAPFRC (81) measures frequency with high accuracy, and can be For better adaptation to system requirements, an operation mode used for generation shedding, load shedding and remedial action setting has been introduced which makes it possible to select the schemes.
  • Page 23 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 • Direct with normal security Autorecloser for 3-phase operation SMBRREC (79) • SBO (Select-Before-Operate) with enhanced security The autorecloser SMBRREC (79) function provides high-speed and/or delayed auto-reclosing for single or multi-breaker Direct commands are received with no prior select command.
  • Page 24 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 The switch controller SCSWI initializes and supervises all conditions are generated in separate function blocks functions to properly select and operate switching primary containing the interlocking logic. apparatuses. Each of the 8 switch controllers SCSWI may handle •...
  • Page 25 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 The logic can be controlled either by the autorecloser (zone Function commands for IEC60870-5-103, I103CMD, extension) or by the loss-of-load current (loss-of-load I103IEDCMD, I103URSCMD, I103GENCMD, I103POSCMD acceleration). IEC60870–5–103 function and command logic blocks are available for configuration of the IED.
  • Page 26: Logic

    Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 IED. To overcome these conditions, weak-end infeed (WEI) echo • XOR function block. Each block has two outputs where one is logic is used. The weak-end infeed echo is limited to 200 ms to inverted.
  • Page 27: Monitoring

    Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 • ANDQT AND function block. The function also propagates Integer to Boolean 16 conversion IB16A timestamp and quality of input signals. Each block has four Integer to boolean 16 conversion function IB16A is used to inputs and two outputs where one is inverted.
  • Page 28 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Event counter CNTGGIO Sequential of events DRPRDRE Event counter CNTGGIO has six counters which are used for Continuous event-logging is useful for monitoring the system from storing the number of times each counter input has been an overview perspective and is a complement to specific activated.
  • Page 29 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 The trip value recorder information is an integrated part of the for load current and for the mutual zero-sequence effect on disturbance record (Comtrade file). double circuit lines.
  • Page 30: Metering

    Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 The function contains a block alarm functionality. character size may vary depending on selected language. The amount of characters and rows fitting the view depends on the The supervised and presented breaker functions include character size and the view that is shown.
  • Page 31 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 User denied attempt to log-on and user successful log-on are Parameter setting groups ACTVGRP reported. Use the four different groups of settings to optimize the IED operation for different power system conditions. Creating and...
  • Page 32: Station Communication

    Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 communication functions, for example, horizontal communication If normal FTP is required to read out (GOOSE) between the IEDs, is only enabled by the IEC 61850-8-1 disturbance recordings, create a specific account for this purpose with rights only to do communication protocol.
  • Page 33: Hardware Description

    Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 1. Supported station communication interfaces and protocols Protocol Ethernet Serial 100BASE-FX LC Glass fibre (ST connector) EIA-485 IEC 61850–8–1 ● DNP3 ● ● ● IEC 60870-5-103 ●...
  • Page 34 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Rack mounting a single 3U IED ANSI11000248 V1 EN Figure 12. Rack mounted 3U IED A 8.82 inches (224 mm) + 0.47 inches (12 mm) with ring-lug connectors B 1 inches (22.5 mm)
  • Page 35: Connection Diagrams

    Product version: 1.3 18. Connection diagrams Connection diagrams for Configured products Connection diagrams Connection diagram, REL650 1.3, (3Ph/1CB) A01A The connection diagrams are delivered on the IED Connectivity 1MRK006502-HD package DVD as part of the product delivery. Connection diagram, REL650 1.3, (1Ph/1CB) A11A...
  • Page 36: Technical Data

    Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 19. Technical data General Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified...
  • Page 37 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Analog inputs Table 2. TRM — Energizing quantities, rated values and limits for transformer inputs Description Value Frequency Rated frequency f 50 or 60 Hz Operating range ± 10%...
  • Page 38 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Auxiliary AC and DC voltage Table 3. Power supply Description 600PSM01 600PSM02 600PSM03 24, 30 V DC 48, 60, 110, 125 V DC 100, 110, 120, 220, 240 V AC, 50...
  • Page 39 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 6. Power output relays without TCM function Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s 30 A Breaking capacity when the control-circuit time constant L/R<40 ms, at V<...
  • Page 40 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 11. IRIG-B Type Value Accuracy Input impedance 430 Ohm Minimum input voltage HIGH 4.3 V Maximum input voltage LOW 0.8 V Table 12. EIA-485 interface Type Value...
  • Page 41 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Ingress protection Table 15. Ingress protection Description Value IED front IP 54 IED rear IP 20 IED sides IP 40 IED top IP 40 IED bottom IP 20 Table 16.
  • Page 42 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Type tests according to standards Table 18. Electromagnetic compatibility tests Description Type test value Reference 100 kHz and 1 MHz burst disturbance test IEC 61000-4-18, level 3 IEC 60255-22-1 ANSI C37.90.1-2012...
  • Page 43 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 18. Electromagnetic compatibility tests, continued Description Type test value Reference Voltage dips and short interruptionsc on DC Dips: IEC 60255-11 power supply 40%/200 ms IEC 61000-4-11 70%/500 ms...
  • Page 44 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 19. Insulation tests Description Type test value Reference Dielectric tests: IEC 60255-5 ANSI C37.90-2005 • Test voltage 2 kV, 50 Hz, 1 min 1 kV, 50 Hz, 1 min, communication...
  • Page 45 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Impedance protection Table 23. Distance measuring zone, Quad ZQMPDIS (21) Function Range or value Accuracy Number of zones 5 with selectable direction Minimum operate current, phase- (10-30)% of IBase ±...
  • Page 46 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 24. Full-scheme distance protection, Mho characteristic ZQMPDIS (21) Function Range or value Accuracy Number of zones with selectable 5 with selectable direction directions Minimum operate current, phase- (10–30)% of I...
  • Page 47 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 26. Faulty phase identification with load encroachment FMPSPDIS (21) Function Range or value Accuracy Load encroachment criteria: Load (1.00–3000) W/phase ± 5.0% static accuracy resistance, forward and reverse (5–70) degrees...
  • Page 48 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 30. Automatic switch onto fault logic, voltage and current based ZCVPSOF Parameter Range or value Accuracy Operate voltage, detection of dead line (1–100)% of ± 0.5% of V VBase IBase ±...
  • Page 49 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 33. Four step phase overcurrent protection, 3-phase output OC4PTOC (51/67) Function Setting range Accuracy lBase Operate current (5-2500)% of ± 1.0% of I at I ≤ I ±...
  • Page 50 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 34. Four step phase overcurrent protection, phase segregated output OC4SPTOC (51_67) Function Setting range Accuracy lBase Operate current (5-2500)% of ± 1.0% of I at I £ I ±...
  • Page 51 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 36. Four step residual overcurrent protection EF4PTOC (51N/67N) Function Range or value Accuracy lBase Operate current (1-2500)% of ± 1.0% of I at I < I ± 1.0% of I at I > I Reset ratio >...
  • Page 52 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 37. Sensitive directional residual overcurrent and power protection SDEPSDE (67N) Function Range or value Accuracy lBase Operate level for 3I ·cosj (0.25-200.00)% of ± 1.0% of I at I £...
  • Page 53 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 37. Sensitive directional residual overcurrent and power protection SDEPSDE (67N) , continued Function Range or value Accuracy Operate time, non-directional 60 ms typically at 0 to 2 x I...
  • Page 54 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 39. Thermal overload protection, one time constant LFPTTR/LCPTTR (26) Function Range or value Accuracy IBase Reference current (0-400)% of ± 1.0% of I Reference temperature (0-600) °F, (0 - 300)°C ±...
  • Page 55 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 41. Breaker failure protection, phase segregated activation and output CSPRBRF (50BF) Function Range or value Accuracy lBase Operate phase current (5-200)% of ± 1.0% of I at I £ I ±...
  • Page 56 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 44. Broken conductor check BRCPTOC (46) Function Range or value Accuracy IBase Minimum phase current for operation (5–100)% of ± 1.0% of I Unbalance current operation (50-90)% of maximum current ±...
  • Page 57 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Voltage protection Table 47. Two step undervoltage protection UV2PTUV (27) Function Range or value Accuracy VBase Operate voltage, low and high step (1–100)% of ± 0.5% of V Reset ratio <102%...
  • Page 58 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 49. Two step residual overvoltage protection ROV2PTOV (59N) Function Range or value Accuracy VBase Operate voltage, step 1 (1-200)% of ± 0.5% of V at V < V ±...
  • Page 59 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Frequency protection Table 51. Under frequency protection SAPTUF (81) Function Range or value Accuracy Operate value, pickup function (35.00-75.00) Hz ± 2.0 mHz at symmetrical three- phase voltage...
  • Page 60 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Secondary system supervision Table 54. Current circuit supervision CCSRDIF (87) Function Range or value Accuracy Operate current (5-200)% of I ± 10.0% of I at I £ I ±...
  • Page 61 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Control Table 57. Synchronizing, synchronism check and energizing check SESRSYN (25) Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage ratio, V 0.500 - 2.000...
  • Page 62 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 58. Autorecloser for 3-phase operation SMBRREC (79) Function Range or value Accuracy Number of autoreclosing shots 1 - 5 Autoreclosing open time: shot 1 - t1 3Ph (0.000-60.000) s...
  • Page 63 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Scheme communication Table 60. Scheme communication logic for distance or overcurrent protection ZCPSCH (85) Function Range or value Accuracy Scheme type Disabled Intertrip Permissive UR Permissive OR Blocking...
  • Page 64 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 62. Current reversal and WEI logic for distance protection, phase segregated ZCWSPSCH (85) Function Range or value Accuracy Operating mode of WEI logic Disablee Echo Echo & Trip...
  • Page 65 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Logic Table 66. Tripping logic common 3-phase output SMPPTRC (94) Function Range or value Accuracy Trip action 3-ph Timers (0.000-60.000) s ± 0.5% ± 10 ms Table 67. Tripping logic phase segregated output SPTPTRC (94)
  • Page 66 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 69. Configurable logic Q/T Logic block Quantity Range or value Accuracy with cycle time 20 ms 100 ms ANDQT ORQT XORQT INVERTERQT RSMEMORYQT SRMEMORYQT PULSETIMERQT (0.000– ± 0.5% ± 25 ms for 20 ms cycle time 90000.000) s...
  • Page 67 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Monitoring Table 71. Technical data covering measurement functions: CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU Function Range or value Accuracy Voltage (0.1-1.5) ×V ± 0.5% of V at V£V ±...
  • Page 68 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 74. Disturbance report DRPRDRE Function Range or value Accuracy Current recording ± 1,0% of I at I ≤ I ± 1,0% of I at I > Ir Voltage recording ±...
  • Page 69 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 76. Event list DRPRDRE Function Value Buffer capacity Maximum number of events in the list 1000 Resolution 1 ms Accuracy Depending on time synchronizing Table 77. Indications DRPRDRE...
  • Page 70 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 81. Station battery supervision SPVNZBAT Function Range or value Accuracy Lower limit for the battery terminal voltage (60-140) % of Vbat ± 1.0% of set battery voltage Reset ratio, lower limit <105 %...
  • Page 71 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Station communication Table 87. Communication protocol Function Value Protocol TCP/IP Ethernet Communication speed for the IEDs 100 Mbit/s Protocol IEC 61850–8–1 Communication speed for the IEDs 100BASE-FX Protocol DNP3.0/TCP...
  • Page 72 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Inverse time characteristics Table 89. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 æ ö ç ÷ ×...
  • Page 73 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 91. RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic td = (0.05-999) in steps of 0.01 × 0.236 0.339...
  • Page 74 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Table 93. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps of 0.01 ±5% +60 ms æ ö...
  • Page 75: Ordering For Customized Ied

    Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 20. Ordering for Customized IED Guidelines Carefully read and follow the set of rules to ensure order management. Be aware that certain functions can only be ordered in combination with other functions and that some functions require specific hardware selections.
  • Page 76 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Logic Rule: One tripping logic type only must be ordered Note: Selection of Tripping Logic type rules the selection of Instantaneous phase Overcurrent protection, Four step phase Overcurrent protection, Breaker Failure protection, Autorecloser and Current reversal and WEI logic.
  • Page 77 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Current protection Rule: Only one Instantaneous phase overcurrent protection can be ordered Rule: If 3 ph tripping logic has been selected only PHPIOC can be selected. If Phase segregated tripping logic has been selected only SPTPIOC can be selected .
  • Page 78 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Frequency protection Underfrequency protection SAPTUF, 81 Qty: 1MRK 004 912-AA Overfrequency protection SAPTOF, 81 Qty: 1MRK 004 912-BA Rate-of-change frequency protection SAPFRC, 81 Qty: 1MRK 004 912-CA Secondary system supervision...
  • Page 79 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Logic Configurable logic blocks Q/T 1MRK 002 917-MK Monitoring Station battery supervision SPVNZBAT Qty: 1MRK 004 925-HB Insulation gas monitoring function SSIMG, 63 Qty: 1MRK 004 925-KA Insulation liquid monitoring function SSIML, 71...
  • Page 80 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Binary input/output modules Note: If analog input module AIM is ordered only 2 BIO modules can be ordered Binary input/output module BIO01 Qty: 1KHL178074R0001 Rack mounting kit Rack mounting kit for 3U 1/1 x 19” case...
  • Page 81: Ordering For Configured Ied

    Please refer to the available functions table for included application functions. To obtain the complete ordering code, please combine code from the tables, as given in the example below. Example code: REL650*1.3-A01AX00-X00-B1XO-D-H-SA-E-SA3-AAXX-F. Using the code of each position #1-11 specified as REL650*1-2 2-3-4 4-5-6-7 7-8-9 9 9-10 10 10 10-11...
  • Page 82 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Mounting details Notes and Rules No mounting kit included Rack mounting kit for 3U 1/1 x 19" Selection for position #6. Connection type for Power supply, Input/output and Communication modules...
  • Page 83 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Communication and processing module Notes and Rules Slot position (rear view) 12BI, IRIG-B, RS485, Ethernet, LC optical, ST serial Selection for position #11.
  • Page 84: Ordering For Accessories

    Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 22. Ordering for Accessories Configuration and monitoring tools Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA...
  • Page 85 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Rule: Specify the number of printed manuals requested Operation manual ANSI Quantity: 1MRK 500 096-UUS Technical manual ANSI Quantity: 1MRK 506 335-UUS Commissioning manual ANSI Quantity: 1MRK 506 336-UUS...
  • Page 86 Line distance protection REL650 ANSI 1MRK 506 337-BUS B Product version: 1.3 Related documents Documents related to REL650 Identity number Application manual 1MRK 506 334-UUS Technical manual 1MRK 506 335-UUS Commissioning manual 1MRK 506 336-UUS Product Guide 1MRK 506 337-BUS...
  • Page 88 For more information please contact: Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. ABB AB does not ABB AB accept any responsibility whatsoever for potential errors or Grid Automation Products possible lack of information in this document.

Table of Contents