Assigning The Shielding Diameter To Shielding Terminals - Siemens CPU 313C Hardware And Installation Manual

S7-300 automation system
Hide thumbs Also See for CPU 313C:
Table of Contents

Advertisement

:LULQJ

&RQQHFWLQJ 6KLHOGHG &DEOHV WR WKH 6KLHOGLQJ &RQWDFW (OHPHQW
$SSOLFDWLRQ
Using the shielding contact element, you can easily ground all shielded cables of
S7 modules, due to the direct contact of the shielding contact element to the rail.
'HVLJQ RI WKH VKLHOGLQJ FRQWDFW HOHPHQW
The shielding contact element consists of:
• a bracket for screw-mounting (with two screws) it onto the rail
(Order No.: 6ES5 390-5AA00-0AA0) and
• the shielding terminals.
You must use the following shielding terminals, depending on the shielding
diameter of your cables:
Table 7-8
2 cables each one with a shielding diameter of 2 to 6
mm
1 cable with a shielding diameter of 3 to 8 mm
1 cable with a shielding diameter of 4 to 13 mm
The shielding contact element width is 80 mm. It provides termination space in two
rows, each one for 4 shielding terminals.
0RXQWLQJ WKH VKLHOGLQJ FRQWDFW HOHPHQW
1. Push the two screw bolts of the fixing bracket into the guide on the underside of
the rail.
2. Position the bracket underneath the modules whose shielded cables are to be
terminated.
3. Screw-tighten the bracket onto the rail.
4. The shielding terminal is equipped with a slotted web underneath. Place the
shielding terminal at this position onto the edge of the bracket (see figure
below). Push the shield terminal down and swing it into the desired position.
7-14

Assigning the shielding diameter to shielding terminals

&DEOH ZLWK VKLHOGLQJ GLDPHWHU
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
6KLHOGLQJ WHUPLQDO 2UGHU 1R
6ES7 390-5AB00-0AA0
6ES7 390-5BA00-0AA0
6ES7 390-5CA00-0AA0
A5E00105492-03