5.8.5 Time of day timers

SETTINGS  CONTROL ELEMENTS  TIME OF DAY TIMERS  TIME OF DAY TIMER 1(5)
 TIME OF DAY TIMER 1
The time of day timer function provides the ability to program control actions based on real time. There are five identical
timers, each with an independent start and stop time setting. Each timer is on when the C70 real-time clock/calendar
value is later than its programmed start time, and earlier than its programmed stop time. The timers wrap around 24
hours, as the figure shows.
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Figure 5-139: Selector switch logic
TIME OF DAY TIMER 1
FUNCTION: Disabled
TIME OF DAY TIMER 1
START TIME: 00:00
TIME OF DAY TIMER 1
STOP TIME: 23:59
TIME OF DAY TIMER 1
TARGETS: Disabled
TIME OF DAY TIMER 1
EVENTS: Disabled
Range: Disabled, Enabled
Range: 00:00 to 23:59 in steps of 00:01
Range: 00:00 to 23:59 in steps of 00:01
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled