Siemens SIPROTEC 5 Series Hardware Description page 124

Table of Contents

Advertisement

Electronic Modules
3.4 Input and Output Modules of the Non-Modular Devices (7xx82)
[dw_example_temp_sensor_2phase, 1, en_US]
Figure 3-81
[dw_temperature_sensor, 1, en_US]
Figure 3-82
Connecting the Lines
When connecting the lines, please proceed as follows:
Use shielded lines with shielding braid (3-core AWG 24).
²
Prepare the cable as shown in the following figure.
²
The dimensions in the drawing are specified to allow insertion of the plug with the shielding plate
screwed on.
[dw_shielded_line, 1, en_US]
Figure 3-83
Connect the lines with bootlace ferrules.
²
Use the included clamps and cable ties to provide contact for the shield and strain relief for the cable.
²
[sc_ shielding_plate _mounting-cutout, 1, --_--]
Figure 3-84
124
Example: Connecting Temperature Sensors RTD 1 (2-Line Terminal) and RTD 2 (2-Line
Terminal) to Terminals M1 to M5
Example: Connecting Temperature Sensors RTD 1 (3-Line Terminal) and RTD 2 (2-Line
Terminal) to Terminals M1 to M5
Preparing the Cable
Using Clips and Cable Ties
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-C, Edition 10.2017