Plug-In Modules
4.2 Communication Modules
[dwethsw3-090713-01.tif, 2, en_US]
Figure 4-9
4.2.5.2

ETH-BA-2EL

Description
Product code
Figure
Connector type
Baud rate
Protocol
Max. line length
148
Operation of Ethernet Modules Without Integrated Switch Function with Single or Redundant
Connection to the Switch
Communication module for the transmission of Ethernet protocols via
2 electrical interfaces
P1Zxxxxxxxxxx
2 x RJ45
100 Mbit/s
DIGSI 5 protocol (secure Web service protocol)
IEC 61850 (MMS and GOOSE)
DNP3
Modbus
IEC 60870-5-104
PROFINET IO
Synchrophasor protocol
You can switch other network services like SNMP, RSTP, PRP, HSR, SNTP,
and SUP Ethernet on and off.
20 m with Ethernet patch cable CAT 5
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-C, Edition 10.2017