Binary Counter Reading (Bcr) - ABB COM600 3.4 User Manual

Station automation
Hide thumbs Also See for COM600 3.4:
Table of Contents

Advertisement

3.4.5.7.
38
Station Automation COM600 3.4
IEC 60870-5-101 Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Over Write
True = 1
False = 0
Default: False = 0
Priority
0...3
End of queue = 0
Middle = 1, 2
Beginning of queue = 3
Update Rate
0...60000
Default: 0
Data Class Spe-
cific
Send as Double
True = 1
Point
False = 0
Send as Inverse
True = 1
Point
False = 0
Time Tag Handling
Do not Send Time Tag = 0
Send Short Format Time Tag
= 1
Send Long Format Time Tag =
2

Binary counter reading (BCR)

Table 3.4.5.7-1 Configurable BCR properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
BCR
Class
Addresses
Indication Address
0...16777215
Default:0
Common
Description
Defines whether a new indication value
overwrites an older one in the queue.
Priority of ASDU. This property defines
how the ASDU sent is placed in the class
1 and class 2 queues.
Maximum update rate of indication
changes between OPC server and client
in milliseconds. 0 means that server sends
all the changes to the client.
Specifies if a value of indication signal is
sent as double point.
Specifies if a value of indication signal is
sent as inverse value.
Specifies the format of timestamp if one
is used: none, short, or long. Long time
tag format cannot be used with a scaled
value.
Description
Common data class according to IEC
61850.
IEC Address for indication.
1MRS755382