4 SETUP AND PREPARATION BEFORE OPERATION
(From the previous page)
[Correct example]
[Wrong example]
[Correct example]
[Wrong example]
(Wiring completed)
4 - 22
Latches
Latch
Clearance
1 When using a cabtyre cable:
Strip the cable 2cm or more.
If the electric wire lengths are not even, trim their ends with a nipper to the same
length so as to insert them neatly into a connector.
Trim the wire ends to the same length
6) Check the press-fit condition (viewing from the wiring side).
Viewing from the wiring side, check that the plug surface is
flush with the plug cover.
Set the plug cover so that it protrudes 0.2mm or less from the
plug surface.
Note: The condition where the plug cover is tilted or protrudes
0.2mm or more from the plug surface as shown in [Wrong
example] is an improper press-fit condition.
Press the plug cover firmly with pliers until it looks like
[Correct example] condition illustrated on the left.
7) Check the press-fit condition (viewing from the top).
Viewing from the top, check that there is no clearance between
the plug body and plug cover.
Note: Clearance may occur between the plug body and plug
cover when the latches do not engage securely as shown
in [Wrong example].
Press the plug cover firmly with pliers until it looks like
[Correct example] condition illustrated on the left.
2cm or more