Mitsubishi Electric MELSEC iQ-R Series User Manual page 140

Cc-link ie field network remote head module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

No.
Name
SW004B
Module status of own
station
SW004E
Network No. set for
diagnostics
SW004F
Station No. set for
diagnostics
SW0064
Connection status of
own station
SW0074
PORT1 cable
disconnection detection
count
SW0075
PORT1 receive error
detection count
SW0076
PORT1 total no. of
received data (lower 1
word)
SW0077
PORT1 total no. of
received data (upper 1
word)
SW007C
PORT2 cable
disconnection detection
count
SW007D
PORT2 receive error
detection count
SW007E
PORT2 total no. of
received data (lower 1
word)
SW007F
PORT2 total no. of
received data (upper 1
word)
SW01E9
Inter-module
synchronization cycle
over count
SW1000
Areas for the CC-Link
to
master/local module
SW1FFF
APPX
138
Appendix 2 List of Link Special Register (SW) Areas
Description
Stores the status of the own station.
No value is stored for offline mode.
01H: STOP (normal)
02H: STOP (moderate/major error)
03H: STOP (minor error)
04H: RUN (normal)
05H: RUN (minor error)
0FH: Initial processing
Stores the network number set in the CC-Link IE Field Network diagnostics.
Range: 1 to 239, 65535 (not set)
Stores the station number set in the CC-Link IE Field Network diagnostics.
Range: 1 to 120, 65535 (not set)
Stores the connection status of the own station.
00H: Normal (communication in progress on P1 and P2)
01H: Normal (communication in progress on P1, cable disconnected on P2)
04H: Normal (loopback communication in progress on P1, cable disconnected on P2)
10H: Normal (cable disconnected on P1, communication in progress on P2)
11H: Disconnecting (cable disconnected on P1 and P2)
12H: Disconnecting (cable disconnected on P1, establishing line on P2)
21H: Disconnecting (establishing line on P1, cable disconnected on P2)
22H: Disconnecting (establishing line on P1 and P2)
40H: Normal (cable disconnected on P1, loopback communication in progress on P2)
Stores the cumulative count that was detected for cable disconnections at the P1 side.
When 'Clear communication error count' (SB0006) is turned on, the stored value for the number of errors is cleared.
When FFFFH (maximum value 65535) is counted, the value returns to 0 and the module continues to count.
Stores the cumulative count that error data was received at the P1 side.
The count stores only error data that is not transmitted to all stations.
When 'Clear communication error count' (SB0006) is turned on, the stored value for the number of errors is cleared.
When FFFFH (maximum value 65535) is counted, counting stops.
Stores the cumulative count that data was received at the P1 side.
When 'Clear communication error count' (SB0006) is turned on, the stored value for the number of errors is cleared.
When FFFFFFFFH (maximum value 4294967295) is counted, counting stops.
Stores the cumulative count that was detected for cable disconnections at the P2 side.
When 'Clear communication error count' (SB0006) is turned on, the stored value for the number of errors is cleared.
When FFFFH (maximum value 65535) is counted, the value returns to 0 and the module continues to count.
Stores the cumulative count that error data was received at the P2 side.
The count stores only error data that is not transmitted to all stations.
When 'Clear communication error count' (SB0006) is turned on, the stored value for the number of errors is cleared.
When FFFFH (maximum value 65535) is counted, counting stops.
Stores the cumulative count that data was received at the P2 side.
When 'Clear communication error count' (SB0006) is turned on, the stored value for the number of errors is cleared.
When FFFFFFFFH (maximum value 4294967295) is counted, counting stops.
Stores the cumulative count that a link scan could not complete an Inter-module synchronization cycle.
The stored count is cleared by turning off and on the power supply or resetting the remote head module.
When FFFFH (maximum value 65535) is counted, counting stops.
By setting these areas as the refresh target device of the link special register (SW) of the CC-Link master/local
module, the data link status of CC-Link can be checked.