Redundant function (other system remote head module information)
The following table lists the special relay areas relating to the redundant function. The remote head module information of the
other system is stored.
All relays are turned off when a redundant system is not used.
: Can be set, : Cannot be set
No.
Name
SM1679
Error reset (the other
system)
SM1680
Error of the other
system monitoring
SM1681
Latest self-diagnostic
error
SM1682
Latest self-diagnostic
error
SM1683
Detailed information
1 in use flag (the
other system)
SM1684
Detailed information
2 in use flag (the
other system)
Data stored
Details
OffOn: Standby
This relay is turned off and on to clear the
system error reset
minor error occurred in the standby system.
requested
This relay is turned off when the error clear of
OnOff: Standby
the standby system has been completed.
system error reset
The initial value is off.
completed
Off: No error
This relay is turned on if an error occurs on
On: Error
communications with the other system when
an initial processing (including when the
system is determined while waiting for the
other system starts up) or an END
processing is performed. (This relay is turned
on when any of 'Cause of the other system
monitoring error' (SD1648) bits turns on.)
This relay is turned off when an error is
cleared.
Off: No error
This relay is turned on if a diagnostic error
On: Error
occurs in the other system remote head
module.
The status of 'Latest self-diagnostic error'
(SM0) for the other system remote head
module is reflected.
Off: No error
This relay is turned on if a self-diagnostic
On: Error
error occurs in the other system remote head
module.
The status of 'Latest self-diagnostic error'
(SM1) of the other system remote head
module is reflected.
Off: Not used
This relay is turned on when there is detailed
On: In use
information 1 for an error occurred in the
other system remote head module.
The status of 'Detailed information 1 in use
flag' (SM80) of the other system remote head
module is reflected.
Off: Not used
This relay is turned on when there is detailed
On: In use
information 2 for an error occurred in the
other system remote head module.
The status of 'Detailed information 2 in use
flag' (SM112) of the other system remote
head module is reflected.
Set by (setting
Effective system
timing)
Control
system
U/S (Status change)
S (Every END/system
switching)
S (Every END)
S (Every END)
S (Every END)
S (Every END)
Appendix 3 List of Special Relay (SM) Areas
Standby
system