Error
Error name
code
2400H
Module
verification
error
2401H
Module
verification
error
2420H
Fuse blown
error
2440H
Module major
error
2442H
Module major
error
2443H
Module major
error
2450H
Module major
error
4 TROUBLESHOOTING
112
4.7 Error Codes
Error details and cause
• The module information at power-on
differs from the information of
modules actually mounted.
• The I/O module or intelligent function
module is not mounted properly or
was removed during operation.
A CPU module, remote head module, I/
O module, or intelligent function module
was mounted on the base unit during
operation.
The output module with a blown fuse
has been detected.
An error has been detected in the I/O
module or intelligent function module
during the initial processing.
An error has been detected in the I/O
module or intelligent function module.
An error has been detected in the I/O
module or intelligent function module.
• A major error has been notified from
the intelligent function module
connected.
• The I/O module or intelligent function
module is not mounted properly or
was removed during operation.
Action
• Check the detailed information (system
configuration information) of the error by
executing module diagnostics using the
engineering tool, and check the module
corresponding to the displayed number.
• Take measures to reduce noise.
• Reset the remote head module, and run it again.
If the same error code is displayed again, the
possible cause is a hardware failure of the error
module. Please consult your local Mitsubishi
representative.
• Check the detailed information (system
configuration information) of the error by
executing module diagnostics using the
engineering tool, and check the module
corresponding to the displayed number.
• Do not mount a CPU module, remote head
module, I/O module, nor intelligent function
module during operation.
• Take measures to reduce noise.
• Reset the remote head module, and run it again.
If the same error code is displayed again, the
possible cause is a hardware failure of the error
module. Please consult your local Mitsubishi
representative.
• Check the FUSE LED of each output module,
and replace the one with the FUSE LED on.
• Check the detailed information (system
configuration information) of the error by
executing module diagnostics using the
engineering tool, and replace the module
corresponding to the displayed slot number.
• Take measures to reduce noise.
• Reset the remote head module, and run it again.
If the same error code is displayed again, the
possible cause is a hardware failure of the error
module. Please consult your local Mitsubishi
representative.
• Take measures to reduce noise.
• Reset the remote head module, and run it again.
If the same error code is displayed again, the
possible cause is a hardware failure of the error
module. Please consult your local Mitsubishi
representative.
• Take measures to reduce noise.
• Reset the remote head module, and run it again.
If the same error code is displayed again, the
possible cause is a hardware failure of the error
module. Please consult your local Mitsubishi
representative.
• Take measures to reduce noise.
• Check the connection of an extension cable.
• Check the detailed information (system
configuration information) of the error by
executing module diagnostics using the
engineering tool, and check the module
corresponding to the displayed number.
• Reset the remote head module, and run it again.
If the same error code is displayed again, the
possible cause is a hardware failure of the error
module. Please consult your local Mitsubishi
representative.
Detailed
Diagnostic
information
timing
System
Always
configuration
information
System
Always
configuration
information
System
Always
configuration
information
System
At power-on,
configuration
at RESET
information
System
At module
configuration
access
information
System
At module
configuration
access
information
System
Always
configuration
information

Advertisement

Table of Contents
loading

Table of Contents