ABB DNP 670 Series Communication Protocol Manual page 52

Relion 670 series
Hide thumbs Also See for DNP 670 Series:
Table of Contents

Advertisement

Section 4
DNP3 parameters
Name
Values (Range)
ConfMultFrag
No
Yes
UREnable
No
Yes
UREvClassMask
Disabled
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
UROfflineRetry
0 - 10
tVRRetryDelay
0.00 - 60.00
tVROfflRtryDel
0.00 - 60.00
UREvCntThold1
1 - 100
tVREvBufTout1
0.00 - 60.00
UREvCntThold2
1 - 100
tVREvBufTout2
0.00 - 60.00
UREvCntThold3
1 - 100
tVREvBufTout3
0.00 - 60.00
DelOldBufFull
No
Yes
ExtTimeFormat
DNPToSetTime
tSynchTimeout
TSyncReqAfTout
Averag3TimeReq
PairedPoint
tSelectTimeout
tBrokenConTout
tKeepAliveT
46
Unit
-
-
-
-
s
s
-
s
-
s
-
s
-
LocalTime
-
UTC
No
-
Yes
30 - 3600
s
No
-
Yes
No
-
Yes
No
-
Yes
1.0 - 60.0
s
0 - 3600
s
0 - 3600
s
Step
Default
-
Yes
-
Yes
-
Disabled
1
5
0.01
5.00
0.01
30.00
1
5
0.01
5.00
1
5
0.01
5.00
1
5
0.01
5.00
-
No
-
UTC
-
No
1
1800
-
No
-
No
-
Yes
0.1
30.0
1
0
1
10
1MRK 511 391-UUS A
Description
Confirm each multiple fragment
Unsolicited response enabled
Unsolicited response, event class mask
Unsolicited response retries before off-line
retry mode
Unsolicited response retry delay in s
Unsolicited response off-line retry delay in s
Unsolicited response class 1 event count
report treshold
Unsolicited response class 1 event buffer
timeout
Unsolicited response class 2 event count
report treshold
Unsolicited response class 2 event buffer
timeout
Unsolicited response class 3 event count
report treshold
Unsolicited response class 3 event buffer
timeout
Delete oldest event when buffer is full
External time format
Allow DNP to set time in IED
Time synch timeout before error status is
generated
Time synchronization request after timeout
Use average of 3 time requests
Enable paired point
Select timeout
Broken connection timeout
Keep-Alive timer
670 series 2.2 ANSI
Communication protocol manual

Advertisement

Table of Contents
loading

Table of Contents