Monitoring Goose Bus Status - ABB COM600F ANSI Operator's Manual

Com600 5.0 series goose analyzer
Hide thumbs Also See for COM600F ANSI:
Table of Contents

Advertisement

1MRS757546
4.2.4.
COM600 series 5.0
GOOSE Analyzer Operator's Manual
Figure 4.2.3-1 Exploring GOOSE configuration

Monitoring GOOSE bus status

You can analyze the GOOSE bus status and mark it with different colors using GOOSE
Analyzer (see Figure 4.2.4-1).
GOOSE bus has four possible statuses:
Normal: transmission of GOOSE packets is according to its configuration and thus
treated as normal (marked with green).
Partial timeout: partial unavailability of intended GOOSE messages, which means
that the subscriber might not be able to receive all GOOSE messages in a defined
time interval. A GOOSE receiving error might be reported by the subscribing IEDs.
All timeout: unavailability of intended GOOSE messages, which means that the
subscriber might not be able to receive all GOOSE messages in a defined time
interval. A GOOSE receiving error might be reported by the subscribing IEDs.
Unknown: unknown status, which might mean problems have been found with
GOOSE Analyzer in COM600.
For a more detailed explanation of GOOSE bus statuses, see 9.3.2, GOOSE bus analyzer.
ExploringGOOSEconfiguration.png
17