Monitoring Of Events; Monitoring Events; Viewing Real-Time Event List - ABB COM600F ANSI Operator's Manual

Com600 5.0 series goose analyzer
Hide thumbs Also See for COM600F ANSI:
Table of Contents

Advertisement

5.
5.1.
5.2.
22
COM600 series 5.0
GOOSE Analyzer Operator's Manual

Monitoring of events

Monitoring events

GOOSE provides fast and reliable system-wide distribution of substation events over
the switched networks. GOOSE Analyzer enables you to monitor these substation events
transmitted over the subnetwork.
GOOSE Analyzer monitors the transmission reliability of GOOSE messages and provides
you with diagnostic events to verify the health of GOOSE with comparison to its config-
uration.
GOOSE Analyzer provides a continuous list view of real-time events, and you can query
the historical database for information.

Viewing real-time event list

You can check the real-time event list on the status bar at the bottom of the GOOSE
Connection Viewer screen.
Figure 5.2-1 Real-time event indication bar
To expand the real-time event indication bar, click the
list view is displayed.
Events are grouped into two categories, GOOSE events and GOOSE diagnosis events.
Each GOOSE event record has the following properties:
Arrival Time: date and time of received events in the UTC format
Object Text: descriptive text for data
Reference: reference of data attribute
Event: specific event of reference transmitted by the GOOSE message
Quality: attribute q of Data Object Instance (DOI)
Timestamp: attribute t of DOI
Subnetwork: subnetwork name
IED: IED name
GOOSE Control Block: reference of GOOSE control block
StNum: GOOSE state number
SqNum: GOOSE sequence number
1MRS757546