4.9.
42
Station Automation COM600 3.4
Logic Processor User's Manual
Making cross-references
After logging out from the device, you can close the CoDeSys programming environment
and launch the Cross-References tool to build a cross reference between the COM600
communication structure and Logic Processor variables.
To make cross-references:
1.
In SAB600, right-click on Logic Processor IED and select Cross References.
2.
The Cross References tool reads all the symbols defined in Logic Processor.
The variable selected from the CoDeSys symbol configuration is shown in the PLC
Server Path column.
Figure 4.9-1 Importing Logic Processor variables
The Import button is used for fetching another symbol file.
3.
From the communication structure, select a data object and drag and drop it to the
proper row in the Cross References tool.
4.
Select a DPC data object to map the breaker's Trip variable. The default data
attribute of DPC is 'stVal'.
5.
Select the whole row and click Edit Row to open the Data attribute selection
dialog.
1MRS756738
Example_cross_reference.bmp