5.8.2

Viewing and Clearing the Local Log Table

The only way to view and clear the data in the Local Log table of the PROFINET Controller is via the Command
Line Interface (CLI). As discussed above, CLI may only be used with the PNC001-Ax module.
Log data can be viewed via the CLI log or show log commands.
The Local Log table can only be cleared via the CLI clear log command, which requires Modify level access.
Clearing the PACSystems CPU Fault Tables or restarting the PROFINET Controller module does NOT clear
the Local Log table.
If the PROFINET Controller Local Log table overflows, new entries overwrite the oldest entries, which are lost. If
that happens, the CLI log or show log command indicates the number of entries that have been lost. The count
of lost entries is cleared whenever the Local Log table is cleared.
5.8.2.1
PROFINET Controller Local Log Display
Figure 95 shows a typical display using the log command. The Loc column identifies the device associated with
the log entry by its Device Number. Proficy Machine Edition assigns a unique Device Number for each Remote IO
Device. The Device Number 000 identifies the PNC001 module itself.
GFK-2571N
Figure 95: Local Log Display
May 2018
Chapter 5. Diagnostics
113