...7.1.5 Divert Page
Note.
nd
– the hot product temperature can be measured by a single or dual RTD. For the dual RTD, the primary
2
RT and RT Deviation
input is always the one displayed as 'Hot Product'.
The secondary RTD enables a self-check facility which can be used to maintain the integrity of primary and secondary
resistance thermometer devices. Any imbalance between the first and second RTD greater than the trip level entered in the
appropriate scroll automatically causes the flow to divert, regardless of the primary temperature measurement.
SEtUP
dIVErt
2nd rt
Enbl y
n
Single
2nd rt
RT
----
rt-dEV
----
rt-dVt
EnbL-Y
N
1952/3
PANL-2
OFF
2nd-rt
UNItS
COLD P
d-OdE
-ULtI
SINGLE
Single
Multi
Divert
Divert
dIVErt
----
OP-LEV
EnbL-Y
n
2d-SrC
----
CIP. S rc
----
Page Header – Set Up Divert Page
Second RT Enable
Enables dual RTD selection (provided the auxiliary input module is fitted).
Second RT Value
If dual RTD values have been selected, the temperature value for the second RTD is displayed.
RT Deviation Trip Value
st
Set the deviation level (1
rt–deV
>
the deviation trip condition is true.
RT Divert Enable
Enables diversion if the above condition is true.
Panel 2 (Record Faceplate) Set Up (displayed with model 1951 only – see fig. 2.3)
Panel 2 Upper Display
OFF
2nd-rt
Second RT value
UNItS
Hot product units
COLD P
Cold product value
Divert Mode
The instrument can be configured to operate in one of two divert modes:
MULtI
Up to eight divert set points can be set.
SINGLE
One divert set point can be set.
Divert Number
Select the divert setting required:
1, 2, 3, 4, 5, 6, 7 or 8 (used with associated
and
displays).
Set Point Source
Caution. Do not change divert numbers during a process (only before or after).
Operator Level (Enable Divert Number Selection)
Allows the divert number to be selected at Operator level.
Secondary Divert Alarm Source
Diverts event pen on any assigned digital condition.
Cleaning in Place
Set digital source for CIP event.
continued on next page...
7 BASIC CONFIGURATION LEVEL...
nd
– 2
RTD value) required for difference condition. If (1
Panel 2 Lower Display
Blank
(1st RT – 2nd RT) value
Divert Set Point
Blank
Divert temp. units
Blank
,
Hot Water Set Temperature
st
nd
– 2
RTD)
13