4.6

Menu commissioning / service

4.6.1

Drive commissioning

Selecting this option enables you to re-commission the drive from the main menu.
● If the operation screen of the "current drive" is focused on an infeed, you will go directly to
the screen "First commissioning: infeed".
● If the operation screen is focused on a VECTOR which has not yet been commissioned,
you will go directly to the screen for basic motor commissioning.
If commissioning is already finished, the following menu options will be displayed for
selection.
Basic commissioning
Only the basic commissioning parameters are interrogated and stored permanently.
Complete commissioning
Complete commissioning with motor and encoder data entry is carried out. Following this,
key motor parameters are recalculated from the motor data. The parameter values
calculated during previous commissioning are lost.
In a subsequent motor identification procedure, the calculated values are overwritten.
Motor identification
The selection screen for motor identification appears.
Reset fan operating time
The actual operating hours of the fan in the power unit are displayed.
After a fan replacement, the time counter for monitoring the fan runtime must be reset.
4.6.2

Device commissioning

In this menu, you can enter the device commissioning status directly. This is the only way
that you can reset parameters to the factory setting for example.
Cabinet Modules Operator Panel AOP30
Operating Instructions, 04/2014, A5E03263551A
Control via the operator panel
4.6 Menu commissioning / service
43