Requirements To Match Emc Directives; Emc Directives - Mitsubishi Electric A960GOT User Manual

Human machine interface, graphical operator terminal
Table of Contents

Advertisement

1 OVERVIEW

1.2 Requirements to match EMC Directives

1.2.1 EMC Directives

1 - 4
EMC Directives which are among European Directives become forced.
EMC Directives are those which require "any strong electromagnetic force is not output
to the external.: Emission (electromagnetic interference)" and "It is influenced by the
electromagnetic wave from the external.: Immunity (electromagnetic sensitivity)".
Items 1.2.1 thru 1.2.3 summarize the precautions to use GOT and configure the
mechanical unit in order to match the EMC directives.
Though the data described herein are produced with our best on the basis of the
requirement items and standards of the restrictions gathered by Mitsubishi, they do not
completely guaranteed that all mechanical unit manufactured according to the data do
not always match the above directives. The manufacturer itself which manufactures
the mechanical unit must finally judge the method and others to match the EMC
directives.
The standards of the EMC Directives are shown below.
Specifications
Test Item
EN55011
Radiated noise
EN50081-2:
1995
EN55011
Conduction noise
EN61000-4-2
Static electricity immunity
EN61000-4-4
First transient burst noise
ENV50140
Radiated electromagnetic
EN50082-2:
1995
field AM modulation
ENV50204
Radiated electromagnetic
field Pulse modulation
ENV50141
Conduction noise
1 QP: Quasi-peak value, Mean: Average value
2 The GOT is an open type device (device installed to another device) and must be
installed in a conductive control pauel or cabinet.
About these test items, install the control panel, combine with a PLC from this
company, and run a test.
Test Description
Measure the emission released by
2
the product.
Measure the emission released by
2
the product to the power line.
Immunity test by applying static
2
electricity to the module enclosure.
Immunity test by applying burst
noise to the power line and signal
2
cable., 2kV
Immunity test by applying
aradiated electric field to the
2
product.
Immunity test by applying
aradiated electric field to the
2
product.
Immunity test by inducting an
electromagnetic field in the power
2
line signal cable.
MELSEC-GOT
Standard Values
30M-230MHz QP :
30dBµ V/m (30m
1
measurement)
230M-1000MHz QP :
37dBµ V/m (30 m
measurement)
150K-500kHzQP:
1
79dB, Mean : 66dB
500K-30MHz QP :
73dB, Mean: 60dB
±4kV contact discharge
±8kV air discharge
±2kV
10V/m, 80-1000MHz,
80% AM modulation @
1kHz
10V/m, 900MHz, 200Hz
pulse modulation, 50%
duty
10Vrms, 0.15-80MHz,
80% modulation @ 1kHz
1 - 4