Siemens SCALANCE X-100 Commissioning Manual

Siemens SCALANCE X-100 Commissioning Manual

Scalance industrial ethernet product line
Hide thumbs Also See for SCALANCE X-100:
Table of Contents

Advertisement

Quick Links

SIMATIC NET
SCALANCE
Industrial Ethernet SCALANCE X-
100 and SCALANCE X-200 Product
Line
Commissioning Manual
1
Preface
Introduction
Network Topologies
Product Characteristics
Installation and Maintenance
Diagnostics over Industrial
Ethernet
PROFINET IO Functionality
Notes on the CE Mark
References
Dimension Drawings
1
2
3
4
5
6
7
8
9
10

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SCALANCE X-100

  • Page 1 SIMATIC NET SCALANCE Industrial Ethernet SCALANCE X- 100 and SCALANCE X-200 Product Line Commissioning Manual Preface Introduction Network Topologies Product Characteristics Installation and Maintenance Diagnostics over Industrial Ethernet PROFINET IO Functionality Notes on the CE Mark References Dimension Drawings...
  • Page 2 Trademarks All designations marked with ® are registered trademarks of Siemens AG. Other designations in this documentation might be trademarks which, if used by third parties for their purposes, might infringe upon the rights of the proprietors.
  • Page 3: Table Of Contents

    SCALANCE X206-1 Product Properties ... 4-26 4.4.4 SCALANCE X206-1 TP Ports ... 4-27 4.4.5 SCALANCE X206-1 FO Ports... 4-28 4.4.6 SCALANCE X206-1 Power Supply and Signaling Contact ... 4-29 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 4 6.2.4.12 The "Agent Configuration" WBM Menu... 6-20 6.2.4.13 The "Agent Event Configuration" WBM Menu ... 6-21 6.2.4.14 The "Agent E-Mail Configuration" WBM Menu ... 6-23 6.2.4.15 The "Agent SNMP Configuration" WBM Menu ... 6-24 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 5 Notes on the CE Mark ... 8-1 Notes on the CE Mark... 8-1 References ... 9-1 References... 9-1 Dimension Drawings... 10-1 10.1 Dimension Drawing... 10-1 Index Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Table of contents...
  • Page 7: Preface

    The "SIMATIC NET Industrial Ethernet Twisted Pair and Fiber Optic Networks“ manual contains additional information on other SIMATIC NET products that you can operate along with the devices of the SCALANCE X-100 and X-200 product lines in an Industrial Ethernet network.
  • Page 8 Preface 1.1 Preface Standards and Approvals The devices of the SCALANCE X-100 and X-200 product lines meet the requirements for the CE mark. You will find detailed information in the section "Notes on CE Marking" in this commissioning manual. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line...
  • Page 9: Introduction

    SIMATIC STEP 7 engineering tool increasing the plant availability. Devices with a high degree of protection allow installation without a cabinet. What Is Possible? The devices of the SCALANCE X-100 or SCALANCE X-200 product lines, allow the cost- effective installation of Industrial Ethernet bus, star, or ring structures with switching functionality.
  • Page 10 2.1 Introduction Warning When used under hazardous conditions (zone 2), the devices of the SCALANCE X-100 and SCALANCE X-200 product lines must be installed in an enclosure. To comply with ATEX100a (EN 50021), this enclosure must meet the requirements of at least IP54 in compliance with EN 60529.
  • Page 11: Network Topologies

    Switching technology allows extensive networks to be set up with numerous nodes and simplifies network expansion. Which topologies can be implemented? Bus, ring, or star topologies can be implemented with the devices of the SCALANCE X-100 or SCALANCE X-200 product lines. Bus Topology...
  • Page 12: Star Topology

    Network Topologies 3.1 Network Topologies Star Topology Figure 3-2 Figure 3-3 Electrical Star Topology, Example with SCALANCE X108 Optical Star Topology, Example with SCALANCE X-400 and SCALANCE X206-1 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 13 As soon as the problem has been eliminated, the original topology is restored; in other words, the ring ports in the redundancy manager are once again disconnected from each other. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Ring Topology, Example with SCALANCE X204-2 and SCALANCE X-400 as...
  • Page 15: Product Characteristics

    Unpacking, Checking 1. Make sure that the package is complete. 2. Check all the parts for transport damage. Warning Do not use any parts that show evidence of damage! Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 16: Scalance X108 Product Characteristics

    4.1.3 SCALANCE X108 Product Characteristics Possible Attachments The SCALANCE X108 has eight RJ-45 jacks for the connection of end devices or other network segments. Figure 4-1 SCALANCE X108 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 17: Scalance X108 Tp Ports

    This makes installation much easier for the user. The devices of the SCALANCE X-100 and X-200 product lines all support the MDI / MDIX autocrossover function. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line...
  • Page 18: Scalance X108 Power Supply And Signaling Contact

    The signaling contact remains activated until the error/fault is eliminated or until the current status is applied as the new desired status using the button. SCALANCE X108 Power Supply Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 19: Scalance X108 Button

    SCALANCE X108 LEDs Fault indicator (red LED) Status lit red not lit Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Signaling Contact SCALANCE X108 Meaning The SCALANCE X108 detects an error. At the same time, the signaling contact opens.
  • Page 20: Scalance X108 Technical Specifications

    + 10 m TP cord IE FC marine/trailing cable with IE FC RJ-45 plug 0 - 75 m IE FC marine/trailing cable + 10 m TP Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 21 IE FC RJ-45 Plug 180 pack of 1 IE FC RJ-45 Plug 180 pack of 10 IE FC RJ-45 Plug 180 pack of 50 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Product Characteristics 4.1 SCALANCE X108...
  • Page 22: Scalance X208

    The number of connected SCALANCE X Industrial Ethernet Switches influences the frame propagation time. When a frame passes through the devices of the SCALANCE X-100 and/or SCALANCE X- 200 product lines, it is delayed by the store and forward function of the switch: - with a 64 byte frame length by approx.
  • Page 23: Scalance X208 Product Properties

    Possible Attachments The SCALANCE X208 has eight RJ-45 jacks for the connection of end devices or other network segments. Figure 4-4 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, SCALANCE X208 Product Characteristics 4.2 SCALANCE X208...
  • Page 24: Scalance X208 Tp Ports

    Ethernet cables are unnecessary. This prevents malfunctions resulting from mismatching send and receive wires. This makes installation much easier for the user. The devices of the SCALANCE X-100 and X-200 product lines all support the MDI / MDIX autocrossover function. 4-10...
  • Page 25: Scalance X208 Power Supply And Signaling Contact

    Signaling Contact The signaling contact is connected to a 2-pin plug-in terminal block. The signaling contact (relay contact) is a floating switch with which error/fault states can be signaled by breaking the contact. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line...
  • Page 26: Scalance X208 Button

    If the button is pressed longer (15 seconds), the device is reset to "factory defaults". This is indicated by all the Port LEDs flashing. During this activity, the device must not be turned off. 4-12 SCALANCE X208 Signaling Contact Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 27: C-Plug Configuration Memory

    The slot for the C-PLUG is located on the back of the device. To insert the C-PLUG, remove the screw cover. The C-PLUG is inserted in the receptacle. The screw cover must then be closed correctly. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Product Characteristics 4.2 SCALANCE X208...
  • Page 28: Scalance X208 Displays

    Power supply L1 or L2 is connected. Power supply L1 and/or L2 not connected or <14 V. Meaning TP link exists, no data reception TP link exists, data received at TP port Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 29: Scalance X208 Technical Specifications

    Network span parameter/TP cable length 0 – 100 m 0 – 85 m Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Device startup, the LED is lit for approx. 6s. Setting or display of the fault mask PST tool).
  • Page 30 25.56 years 60 x 125 x 124 DIN rail S7-300 standard rail Wall Mounting 6GK5208-0BA00-2AA3 6GK1970-1BA10-0AA0 6GK1901-1GA00 6GK1901-1GB00 6XV1840 2AH10 6XV1840-3AH10 6XV1840-4AH10 6GK1 901-1BB10-2AA0 6GK1 901-1BB10-2AB0 6GK1 901-1BB10-2AE0 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 31: Scalance X208Pro

    The number of connected SCALANCE X Industrial Ethernet Switches influences the frame propagation time. When a frame passes through devices of the SCALANCE X-100 and/or SCALANCE X-200 product lines, it is delayed by the store and forward function of the switch: - with a 64 byte frame length by approx.
  • Page 32: Scalance X208Pro Product Properties

    The SCALANCE X208PRO has eight RJ-45 jacks designed as push pull for the connection of end devices or other network segments. Figure 4-7 4-18 SCALANCE X208PRO without Protective Covers Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 33: Scalance X208Pro Tp Ports

    This makes installation much easier for the user. The devices of the SCALANCE X-100 and X-200 product lines all support the MDI / MDIX autocrossover function. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line...
  • Page 34: Scalance X208Pro Power Supply And Signaling Contact

    Never connect the SCALANCE X208PRO to AC voltage or DC voltage higher than 32 V DC. Signaling Contact The signaling contact is connected over one 5-pin M12 connector (b-coded). The signaling contact (relay contact) is a floating switch with which error/fault states can be signaled by breaking the contact. Figure 4-9...
  • Page 35: C-Plug Configuration Memory

    Inserting a C-PLUG that does not contain the configuration of a compatible device type, inadvertently removing the C-PLUG, or general malfunctions of the C-PLUG are indicated by the diagnostic mechanisms of the switch (LEDs, PROFINET, SNMP, WBM, etc.). Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Product Characteristics 4.3 SCALANCE X208PRO...
  • Page 36: Scalance X208Pro Displays

    No fault detected by the SCALANCE X208PRO. Meaning Power supply L1 or L2 is connected. Power supply L1 and/or L2 not connected or <14 V. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 37: Scalance X208Pro Technical Specifications

    Permitted Cable Lengths Network span parameter/TP cable length 0 -100 m 0 - 85 m Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Meaning TP link exists, no data reception TP link exists, data received at TP port Device startup, the LED is lit for approx.
  • Page 38 90 x 125 x 124 Wall mounting DIN rail S7-300 sta ndard rail 6GK5208-0CA00-2AA6 6GK1970-1BA10-0AA0 6GK1901-1GA00 6GK1901-1GB00 6XV1840 2AH10 6XV1840-3AH10 6XV1840-4AH10 6GK1 900-0AB00 6GK1 907-0DC10-6AA3 6GK1 908-0DC10-6AA3 6GK5 791-1PS00-0AA6 6GK1 907-0AF00-0AA0 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 39: Scalance X206-1

    The number of connected SCALANCE X Industrial Ethernet Switches influences the frame propagation time. When a frame passes through the devices of the SCALANCE X-100 and/or SCALANCE X- 200 product lines, it is delayed by the store and forward function of the switch: - with a 64 byte frame length by approx.
  • Page 40: Unpacking And Checking

    The SCALANCE X206-1 has six RJ-45 jacks and a BFOC port for the connection of end devices or other network segments. Note The BFOC socket corresponds to the ST socket. 4-26 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 41: Scalance X206-1 Tp Ports

    Using autonegotiation, repeaters or DTEs can detect the functionality available at the port of a partner device allowing automatic configuration of different types of device. With Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, SCALANCE X206-1 Product Characteristics 4.4 SCALANCE X206-1...
  • Page 42: Scalance X206-1 Fo Ports

    Ethernet cables are unnecessary. This prevents malfunctions resulting from mismatching send and receive wires. This makes installation much easier for the user. The devices of the SCALANCE X-100 and X-200 product lines all support the MDI / MDIX autocrossover function. 4.4.5...
  • Page 43: Scalance X206-1 Power Supply And Signaling Contact

    Signaling Contact The signaling contact is connected to a 2-pin plug-in terminal block. The signaling contact (relay contact) is a floating switch with which error/fault states can be signaled by breaking the contact. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line...
  • Page 44: Scalance X206-1 Button

    If the button is pressed longer (15 seconds), the device is reset to "factory defaults". This is indicated by all the Port LEDs flashing. During this activity, the device must not be turned off. 4-30 SCALANCE X206-1 Signaling Contact Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 45: C-Plug Configuration Memory

    The slot for the C-PLUG is located on the back of the device. To insert the C-PLUG, remove the screw cover. The C-PLUG is inserted in the receptacle. The screw cover must then be closed correctly. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Product Characteristics 4.4 SCALANCE X206-1...
  • Page 46: Scalance X206-1 Displays

    Power supply L1 or L2 is connected. Power supply L1 and/or L2 not connected or <14 V. Meaning TP link exists, no data reception TP link exists, data received at TP port Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 47: Scalance X206-1 Technical Specifications

    Permitted Cable Lengths Network span parameter/TP cable length 0 – 100 m Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Device startup, the LED is lit for approx. 6s. Setting or display of the fault mask PST tool).
  • Page 48 UL 1604, UL 2279Pt.15 FM 3611 AS/NZS 2064 (Class A). EN 50081-2, EN 50082-2 EN50021 42.56 years 60 x 125 x 124 Standard rail S7-300 standard rail Wall Mounting 6GK5206-1BB00-2AA3 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 49: Scalance X204-2

    The number of connected SCALANCE X Industrial Ethernet Switches influences the frame propagation time. When a frame passes through the devices of the SCALANCE X-100 and/or SCALANCE X- 200 product lines, it is delayed by the store and forward function of the switch: - with a 64 byte frame length by approx.
  • Page 50: Unpacking And Checking

    The SCALANCE X204-2 has four RJ-45 jacks and two BFOC ports for the connection of end devices or other network segments. Note The BFOC socket corresponds to the ST socket. 4-36 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 51: Scalance X204-2 Tp Ports

    Autonegotiation means the automatic detection of the functionality of the port at the opposite end. Using autonegotiation, repeaters or DTEs can detect the functionality available at the Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, SCALANCE X204-2 Product Characteristics 4.5 SCALANCE X204-2...
  • Page 52: Scalance X204-2 Fo Ports

    Ethernet cables are unnecessary. This prevents malfunctions resulting from mismatching send and receive wires. This makes installation much easier for the user. The devices of the SCALANCE X-100 and X-200 product lines all support the MDI / MDIX autocrossover function. 4.5.5...
  • Page 53: Scalance X204-2 Power Supply And Signaling Contact

    The signaling contact can be subjected to a maximum load of 100 mA (safety extra-low voltage (SELV), DC 24 V). Never connect the SCALANCE X204-2 to AC voltage or DC voltage higher than 32 V DC. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, SCALANCE 204-2 Power Supply Product Characteristics 4.5 SCALANCE X204-2...
  • Page 54: Scalance X204-2 Button

    4.5 SCALANCE X204-2 Signaling Contact The signaling contact is connected to a 2-pin plug-in terminal block. The signaling contact (relay contact) is a floating switch with which error/fault states can be signaled by breaking the contact. Figure 4-15 The following errors/faults can be signaled by the signaling contact: •...
  • Page 55: C-Plug Configuration Memory

    The slot for the C-PLUG is located on the back of the device. To insert the C-PLUG, remove the screw cover. The C-PLUG is inserted in the receptacle. The screw cover must then be closed correctly. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Product Characteristics 4.5 SCALANCE X204-2...
  • Page 56: Scalance X204-2 Displays

    Power supply L1 or L2 is connected. Power supply L1 and/or L2 not connected or <14 V. Meaning TP link exists, no data reception TP link exists, data received at TP port Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 57: Scalance X204-2 Technical Specifications

    Permitted Cable Lengths Network span parameter/TP cable length 0 – 100 m Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Device startup, the LED is lit for approx. 6s. Setting or display of the fault mask PST tool).
  • Page 58 FM 3611 AS/NZS 2064 (Class A). EN 50081-2, EN 50082-2 EN50021 37.56 years 60 x 125 x 124 DIN rail S7-300 standard rail Wall Mounting 6GK5204-2BB00-2AA3 6GK1970-1BA10-0AA0 6GK1901-1GA00 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 59 The number of connected SCALANCE X Industrial Ethernet Switches influences the frame propagation time. When a frame passes through the devices of the SCALANCE X-100 and/or SCALANCE X- 200 product lines, it is delayed by the store and forward function of the switch: - with a 64 byte frame length by approx.
  • Page 61: Installation And Maintenance

    Installation and Maintenance Installation Types of Installation The Industrial Ethernet switches of the SCALANCE X-100 and X-200 product lines can be mounted in different ways: • Installation on a 35 mm DIN rail • Installation on a SIMATIC S7-300 Standard Rail •...
  • Page 62 5.2 Installation on a DIN Rail Figure 5-1 Uninstalling To remove the Industrial Ethernet switches of the SCALANCE X-100 and X-200 product lines from the standard rail: 1. First disconnect the TP cables and pull out the terminal blocks for the power supply and the signaling contact.
  • Page 63: Installation On A Standard Rail

    Installation on a SIMATIC S7-300 Standard Rail 1. Place the upper guide at the top of the SCALANCE housing in the S7 standard rail. 2. Screw the Industrial Ethernet switches of the SCALANCE X-100 and X-200 product lines to the underside of the standard rail.
  • Page 64: Dimension Drawings

    Figure 5-3 Uninstalling To remove the Industrial Ethernet switches of the SCALANCE X-100 and X-200 product lines from the SIMATIC S7-300 standard rail: 1. First disconnect the TP cables and pull out the terminal blocks for the power supply and the signaling contact.
  • Page 65: Grounding

    For information on assembling an IE FC RJ-45 Plug 180 on a SIMATIC NET Industrial Ethernet FastConnect cable, please refer to the instructions supplied with the IE FC RJ-45 Plug. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Installation and Maintenance...
  • Page 66 5.6 Fitting the IE FC RJ-45 Plug 180 Figure 5-4 Inserting the IE FC RJ-45 Plug 180 1. Insert the IE FC RJ-45 Plug 180 into the devices of the SCALANCE X-100 or X-200 product line until it locks in place. Figure 5-5...
  • Page 67 If there is not enough space to release the lock with your hand, you can also use a 2.5 mm screwdriver. You can then remove the IE FC RJ-45 Plug 180 from the twisted pair socket. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 68: Maintenance

    Figure 5-7 Maintenance Maintenance If a fault develops, please send the device to your SIEMENS service center for repair. Repairs on-site are not possible. Releasing the RJ-45 Plug with a Screwdriver Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line...
  • Page 69: Diagnostics Over Industrial Ethernet

    Before the IP address can be assigned with the setup tool, the SCALANCE X-200 must be accessible over Ethernet. • The initial assignment of an IP address for an Industrial Ethernet switch of the SCALANCE X-200 product line is not possible with Web Based Management because this configuration tool requires that an IP address is already available.
  • Page 70: The Dlc Protocol

    4. The dialog box for selecting the installation folder appears. Click on the Next but if you want to accept the default C:\Program Files\Siemens\Primary Setup Tool\ . If you want to specify a different folder, you can open a dialog box for selecting a folder by clicking the Browse button.
  • Page 71: Installing The Dlc Protocol

    1. Select the menu Start > Settings > Control Panel > Network and Dial-up Connections. 2. Select the connection to your Ethernet communications module. 3. Open the Properties dialog using the context-sensitive menu (right mouse button). Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Properties of Local Area Connection-1 Diagnostics over Industrial Ethernet 6.1 Configuration with the Primary Setup Tool...
  • Page 72: Working With The Primary Setup Tool

    7. In the Install from Disk dialog box, click the Browse button. . 8. In the file selection dialog, change to the installation folder of the Primary Setup Tool (default C:\Program Files\Siemens\Primary Setup Tool\) and open the DLC Protocol subfolder.
  • Page 73 The information on the router is necessary if the computer with which you are creating the configuration is not in the same subnet as the device you are configuring. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Diagnostics over Industrial Ethernet...
  • Page 74 – Select the Module > Download menu command. – Click on the second button from the left in the toolbar (S7 modules with yellow arrow). Configuring a Module Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 75 Module > Remove Module menu command. Using this menu has no effect on the existence of a module in the network, after browsing the network again, all modules would be displayed again. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Downloading the Module...
  • Page 76: Web Based Management (Wbm)

    You require a PC with an Internet browser. We recommend that you use a Microsoft Internet Explorer, version 5.5 or higher or a Netscape Browser, version 6.1 or higher. To execute the script, Java script must be activated in the browser. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 77: Access Over Wbm

    How to Access Industrial Ethernet Switches of the SCALANCE X-200 Product Line over WBM 1. Open the Internet browser. 2. Enter the IP address or the URL of the Industrial Ethernet switch of the SCALANCE X- 200 product line in the address box of the Internet browser as follows: for example http://141.73.10.89...
  • Page 78: Wbm Menus

    The Start Dialog The following start the dialog appears after you start the WBM. Select the required function from the menu on the left-hand side. 6-10 Logon Screenshot Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 79: The "System Configuration" Wbm Menu

    The first three text boxes are read-only and display general information on the device. You can specify parameters in the lower three fields. You can change the System Contact, System Location, and System Name. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Start Dialog Diagnostics over Industrial Ethernet 6.2 Web Based Management (WBM)
  • Page 80 In this box, you enter a location for the device, for example a room number. System Name Text Box Enter a description of the device in this box. You apply your settings with Set Values. 6-12 "System Configuration" Dialog Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 81: The "System Restart & Defaults" Wbm Menu

    • IP address of the default router • DHCP flag • System name • System location Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, "System Restart & Defaults" Dialog Diagnostics over Industrial Ethernet 6.2 Web Based Management (WBM)
  • Page 82: The "System Save & Load Http" Wbm Menu

    Name and possibly also folder path of the file (maximum 32 characters) from which you want to load the new firmware. 6-14 "System Save & Load via HTTP" Dialog Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 83: The "System Save & Load Tftp" Wbm Menu

    Name and possibly also folder path of the file (maximum 32 characters) from which you want to load the new firmware. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, "System Save & Load via TFTP" Dialog Diagnostics over Industrial Ethernet 6.2 Web Based Management (WBM)
  • Page 84: The "System Version Numbers" Wbm Menu

    Displays the MAC address of the device. MLFB Number Text Box Displays the MLFB number of the device. Serial number Text Box Displays the serial number of the device. 6-16 "System Version Numbers" Dialog Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 85: The "System Passwords" Wbm Menu

    6.2.4.8 The "Status" WBM Menu Status This page provides information on operating states such as power supply and fault status. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, "System Passwords" Dialog Diagnostics over Industrial Ethernet 6.2 Web Based Management (WBM)
  • Page 86: The "Fault Mask" Wbm Menu

    Here, the monitoring of the redundant power supply can be activated/deactivated. Ports enabled List Box Here, the monitoring of the link status of the individual ports can be activated/deactivated. 6-18 "Status" Dialog "Fault Mask" Dialog Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 87: The "Ring Redundancy" Wbm Menu

    Enable Ringports Text Box Enables/disables ring redundancy. Ringports Text Box Here, you can set the Ethernet ports with which the switch is connected to the redundant ring. Note SCALANCE X-200 devices can be operated in a redundant ring if one of the following...
  • Page 88: The "C-Plug Information" Wbm Menu

    SCALANCE X-200 obtains its IP address dynamically or has a fixed address. You can also enable options for accessing the device such as TELNET or SNMP. 6-20 "C-PLUG Information" Dialog Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 89: The "Agent Event Configuration" Wbm Menu

    The following options are available: • The SCALANCE X-200 sends an E-mail. • The SCALANCE X-200 triggers an SNMP trap. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, "Agent Configuration" Dialog Diagnostics over Industrial Ethernet 6.2 Web Based Management (WBM)
  • Page 90 The fault status has changed. The fault status can relate to the activated port monitoring, the response of the signaling contact or the power supply monitoring. 6-22 "Agent Event Configuration" Dialog Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 91: The "Agent E-Mail Configuration" Wbm Menu

    Here, you enter the E-mail address to which the SCALANCE X-200 sends an E-mail if a fault occurs. SMTP Server IP Address Text Box Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, "Agent E-Mail Configuration" Dialog Diagnostics over Industrial Ethernet 6.2 Web Based Management (WBM)
  • Page 92: The "Agent Snmp Configuration" Wbm Menu

    Enables/disables write protection for SNMP variables. Read Community String Text Box Displays the user name for read access to SNMP variables. Write Community String Text Box 6-24 "Agent SNMP Configuration" Dialog Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 93: The "Agent Trap Configuration" Wbm Menu

    Enable Trap Check Box Click on the check box next to the IP addresses to enable the sending of traps to the corresponding stations. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, "Agent Trap Configuration" Dialog Diagnostics over Industrial Ethernet 6.2 Web Based Management (WBM)
  • Page 94: The "Switch Configuration (Port Mirroring)" Wbm Menu

    You apply your settings with Set Value. 6.2.4.18 The "Switch Ports Status" WBM Menu Switch Ports Status This dialog informs you about the current status of the ports. 6-26 "Switch Configuration" Dialog Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 95 The port has a valid link to the network, a link integrity signal is being received. • down The link is down, for example because the connected device is turned off. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, "Switch Ports Status" Dialog Diagnostics over Industrial Ethernet 6.2 Web Based Management (WBM)
  • Page 96: The "Switch Port Diagnostics" Wbm Menu

    Figure 6-24 Port Text Box The port to be tested is specified here. Run Test Button This button activates the test. Pair Information Box 6-28 "Switch Port Diagnostics" Dialog Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 97: The "Statistics" Wbm Menu

    • Bad frames This information provides you with an overview of the data traffic and any problems on the network. Figure 6-25 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, "Statistics" Dialog Diagnostics over Industrial Ethernet 6.2 Web Based Management (WBM)
  • Page 98: The "Packet Size Statistic" Wbm Menu

    If you click on an entry in the Port column, the Packet Size Statistics graphic is displayed for the selected port. You then see a graphical representation of the counter value. 6-30 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 99: The "Packet Type Statistic" Wbm Menu

    The Packet Type Statistics page displays how many frames of the type unicast, multicast, and broadcast were received at each port. If you click the Reset Counters button, you reset the counters for all ports. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, "Packet Size Statistics" Dialog Diagnostics over Industrial Ethernet 6.2 Web Based Management (WBM)
  • Page 100: The "Packet Error Statistic" Wbm Menu

    If you click on an entry in the Port column, the Packet Error Statistics graphic is displayed for the selected port. You then see a graphical representation of the counter value. 6-32 "Packet Type Statistics" Dialog Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 101 Jabbers Packets too long without valid checksum. Collisions Indicates the number of collisions that have occurred. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, "Packet Error Statistics" Dialog Diagnostics over Industrial Ethernet 6.2 Web Based Management (WBM)
  • Page 103: Profinet Io Functionality

    In the example, it is assumed that an S7 station is already configured with a PN IO chain (see also PN IO System Manual). An example of a hardware configuration with a PN IO chain is shown in the following figure. Figure 7-1 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Station Setup...
  • Page 104 1. In the dialog, select HW Config -> Options "Install GSD files". The following dialog opens: Figure 7-2 2. Use the browse function to locate the supplied xml file (for example gsdml-v1.0-Siemens- SCALANCE_X_2xx-20040729.xml). 3. Then adopt the file using the "Install" function.
  • Page 105 By double-clicking on slot=0, you can set the global parameters of the SCALANCE (substitute module) as shown in the figure. 2. Click on the slots of the ports and set the specific parameters. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Inserting a SCALANCE X208 PROFINET IO Functionality 7.1 Configuring with PROFINET IO...
  • Page 106 PROFINET IO Functionality 7.1 Configuring with PROFINET IO Figure 7-4 Setting Global Parameters Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 107 Figure 7-5 1. In HW Config, open the Properties - SCALANCE X-208 dialog and enter the device name for the IO device: Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Setting Specific Parameters PROFINET IO Functionality...
  • Page 108 To transfer the name to the SCALANCE X-208, you require an online connection from the PG to the IO device. 1. You transfer the device name to the SCALANCE X-208 with PLC > Ethernet > Assign Device Name. Assigning the Device Name Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 109 PROFINET IO Functionality 7.1 Configuring with PROFINET IO Figure 7-7 Assigning the Device Name Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 110 "Flashing On/Off" button (all the LEDs of the selected SCALANCE flash). 1. Click on the Assign Name button in the Device Names dialog box. The device name is stored permanently on the SCALANCE. Assign Device Name Dialog Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 111 After assigning the name, the device name you assigned appears in the dialog box. 1. Download the hardware configuration to the CPU317-2PN/DP. 2. Select PLC > Download to Module Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, Assign Device Name Dialog for Further Devices PROFINET IO Functionality 7.1 Configuring with PROFINET IO...
  • Page 113: Notes On The Ce Mark

    The EU declaration of conformity is available for the responsible authorities according to the above-mentioned EU directive at the following address: Siemens Aktiengesellschaft Bereich Automatisierungs- und Antriebstechnik Industrielle Kommunikation (A&D PT2) Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, SCALANCE X108 SCALANCE X208 SCALANCE X208PRO...
  • Page 114: Notes On The Ce Mark

    If the product is part of the equipment of a machine, it must be included in the procedure for the declaration of conformity by the manufacturer of the machine. Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 115: References

    1. SIMATIC NET Industrial Twisted Pair and Fiber-Optic Networks, Order numbers: 6GK1970-1BA10-0AA0 German 6GK1970-1BA10-0AA1 English 6GK1970-1BA10-0AA2 French 6GK1970-1BA10-0AA4 Italian 2. PROFINET Installation Guide Can be ordered from the PROFIBUS User Organization (PNO) Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 117: Dimension Drawings

    Dimension Drawings 10.1 Dimension Drawing Figure 10-1 Diemension Drawing SCALANCE X108, X208, X206-1, X204-2 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line 10-1 Commissioning Manual, 1,...
  • Page 118 Dimension Drawings 10.1 Dimension Drawing Figure 10-2 Dimension Drawing SCALANCE X208PRO Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line 10-2 Commissioning Manual, 1,...
  • Page 119: Index

    SCALANCE X204-2, 4-42 SCALANCE X206-1, 4-32 SCALANCE X208, 4-14 SCALANCE X208PRO, 4-22 IP address, 6-1 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1, MDI /MDIX Autocrossover Function, 4-3, 4-10, 4-19, 4- 28, 4-38 Network topology, 3-1...
  • Page 120 SCALANCE X108, 4-4 SCALANCE X204-3, 4-40 SCALANCE X206-1, 4-29 SCALANCE X208, 4-11 SCALANCE X208PRO, 4-20 ST socket BFOC socket, 4-36 STEP 7 V 5.3 plus SVP 1, 6-1 Index-2 Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Commissioning Manual, 1,...
  • Page 121 Index Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line Index-3 Commissioning Manual, 1,...

This manual is also suitable for:

Scalance x-200

Table of Contents