ADDENDUM FOR COMETER OR INDICATOR WITH HART PROGRAMMING CAPABILITY
AND PROMETER - PROGRAMMABLE INDICATOR
COMETER ONLY
ConF
METER
ENTER
ESC
NEXT
ConF
PREV
AUTO
ENTER
ESC
. . . *
LOADING
NEXT
PREV
ConF
ESC
UPDATE?
ENTER
ConF
ESC
OK
ENTER
ESC
UPDATE ZERO,
FULL-SCALE
AND UNIT
ESC
The other options under ConF METER menu are:
ConF AUTO
By selecting this option, the CoMeter is automatically updated
with the LRV, URV and Unit of the HART transmitter connected.
Before accepting the transmitter configuration by pressing
ENTER at the request "ConF UPDATE?", it is possible to view
the LRV (ZERO), the URV (FULL SC) and the UNIT.
If the output transfer function of the transmitter is not linear,
ProMeter and CoMeter show the message: ConF NO_LIN and
the user cannot update the configuration.
It is necessary to change the output transfer function of the
transmitter to linear.
See Fig. 4 - "ConF METER" menu, for ConF AUTO procedure.
ConF
NEXT PREV
MANUAL
ESC
NEXT
PREV
OUTPUT
ESC
ConF
LINEAR
VIEW ?
SQR
ENTER
ENTER
0.000
ZERO
NEXT
PREV
40.000
FULL SC
NEXT
PREV
KPA
NEXT
PREV
NEXT
PREV
ESC
Fig. 4 - ConF METER menu
COMETER and PROMETER
ENTER
NEXT
NEXT
4000
PREV
PREV
ZERO
ENTER
ENTER
ESC
04000
04000
04000
00000
00000
ZERO
ENTER
NEXT
PREV
ConF
CURRENT
ENTER
ESC
ConF
UPDATE?
ENTER
ESC
SET 4÷20 mA
INDICATION
ConF MANUAL
The selection of MANUAL configuration allows the user to
define manually CoMeter and ProMeter configuration, i.e.
define the LRV (ZERO), the URV (FULL SC), and the UNIT, as
well as to decide for a LINEAR on SQR output function. LRV
and URV can have a value between -99999 and +99999.
Refer to Fig. 4 - ConF METER menu for detail on the procedure.
For having the CoMeter to display the analog output current or
the output percentage, select respectively:
ConF CURRENT and ConF PERCENT
NEXT PREV
NEXT
20000
PREV
FULL SC
UNITS
ENTER
ESC
ESC
20000
20000
20000
TORR
20000
20000
FULL SC
IN H2O
ENTER
KG / CM2
NEXT
PREV
ConF
PERCENT
ENTER
ESC
LINEAR
SQR
ENTER
ConF
UPDATE ?
ESC
ENTER
SET 0÷100% INDICATION
(WITH OR WITHOUT
SQUARE ROOT)
NEXT
PREV
ENTER
KPA
ATM
MPA
ENTER
NEXT
PREV
ConF
PASSWD
ENTER
00000
01000
01200
01230
01234
PASSWD
ENTER
UPDATE?
ENTER
UPDATE NEW
PASSWORD
- 27 -