ADDENDUM FOR COMETER OR INDICATOR WITH HART PROGRAMMING CAPABILITY
AND PROMETER - PROGRAMMABLE INDICATOR
Under ConF PERCENT option, the user can decide for linear
or SQR output. When SQR output is selected, the output is
linear from 0 to 20% (to 4% of input).
Refer to Fig. 4 - ConF METER for details on the procedures.
ConF XMTR - TRANSMITTER CONFIGURATION
(CoMeter only)
Four are the operations under the ConF XMTR menu:
CONF, TRIM, REVIEW and PV.
By pressing ENTER on the ConF XMTR menu, the string
LOADING appears on the display, with the blinking star (*)
indicating communication activity, i.e. the CoMeter is reading
the transmitter information.
See below a list of the available operation under the selected option:
CONF menu
TRIM menu
Change LRV
Reranging (RERANG.)
Change URV
Loop test (LOOPTST)
Change DAMPING
Output trim (OUTTRIM)
Change UNITS
Zero adjustment (SNSZERO)
Change OUTPUT
Use PREV or NEXT key to scroll through the options and ENTER key to change or view the values.
The procedure to change the numeric value remains the one already explained for PASSWORD operation, i.e., the cursor starts
blinking on the most significant digit, then use the NEXT and PREV key to increase or decrease the value of the single digit (the
minus sign(-)automatically appears or disappears when the value increases above 9 or decreases below 0, as well as for the
decimal point(.). Use the ENTER key to move the cursor to the next digit, use the ESC key to move back to the previous digit.
An ENTER on the last digit will cause the value to be sent to the transmitter.
Refer to figures 5, 6, 7 and 8 for details.
CONF
ENTER
ESC
LOOP
IN_MAN.
ENTER
ESC
NEXT
NEXT PREV
0.000
PREV
LRV
ESC
ENTER
00.000
01.000
01.000
01.000
01.000
LRV
ENTER
NEXT PREV
TO MODIFY DIGIT,
DECIMAL POINT,
MINUS SIGN
- 28 -
NEXT PREV
20.000
DAMPING
URV
ENTER
ESC
ESC
20.000
25.000
25.000
25.000
25.000
DMP SEC
URV
ENTER
NEXT PREV
TO MODIFY DIGIT,
DECIMAL POINT,
MINUS SIGN
Fig. 5 - CONF menu
Then the CONF option appears.
Using PREV or NEXT key, the user can select CONF, TRIM,
REVIEW or PV option, and with the ENTER key he moves into
the menu.
When entering CONF and TRIM menu a message "LOOP
IN_MAN" appears to remind that a modification can change
the transmitter output, so for security the loop should be put in
Manual.
REVIEW menu
TAG 8
Final Assembly Nr. (XMTR N.)
Sensor Serial Nr. (SENS N.)
Up/Down scale (UP/DOWN)
UNITS
LRV
URV
LRL (See Sensor Units)
URL (See Sensor Units)
DAMPING
OUTPUT
NEXT PREV
0.0000
UNITS
ESC
ENTER
0.0000
KPA
0.2000
0.2000
TORR
0.2000
ATM
MPA
0.2000
IN H2O
ENTER
NEXT PREV
KG/CM2
TO MODIFY DIGIT,
DECIMAL POINT,
MINUS SIGN
PV menu
Primary variable (PRIMARY)
Secondary variable (2ND)
Tertiary variable (3RD)
Fourth variable (4TH)
NEXT PREV
OUTPUT
ENTER
ENTER
ESC
LINEAR
SQR
ENTER
NEXT
PREV