Panasonic 2WAY Multi Technical & Service Manual page 166

Troubleshooting. gas heat pump, air conditioner.
Hide thumbs Also See for 2WAY Multi:
Table of Contents

Advertisement

5) Make the correction
Correction example a)
The adjustment value is 10° BTDC, but the observed value was 8° BTDC. Press the UP (S005) or DOWN
(S006) key to set a correction of +2 in relation to the current "   " (ignition timing offset) value.
i)
Display the current "   " (ignition timing
offset) value, and check it. The current value is
zero (0).
The display for "    " will be as shown at
right.
ii) With "   " (ignition timing offset)
displayed, press the SET key (S007) for one
second or more.
The TEST/WARNING LED (D052) will light,
and LEVEL LED (D053) will fl ash.
iii) Press the UP (S005) or DOWN (S006) key to
set a correction of +2 in relation to the current
value checked in "ii)."
The display will show "    " (right
fi gure).
Caution: The display example at right is
an example for when the current
value checked in "i)" is zero (0). If
the current value is "1" and a +2
correction is set in relation to that
value, the value will become "3" after
the setting is made. The display will
show "    " (fi gure below right).
iv) With "    " (right fi gure) displayed, press
the SET key (S007) for one second or more.
The TEST/WARNING LED (D052) will go
out, and LEVEL LED (D053) will light. The
ignition timing offset mode will be cancelled,
and the setting process will be ended.
V–47