A02 Engine Oil Error - Panasonic 2WAY Multi Technical & Service Manual

Troubleshooting. gas heat pump, air conditioner.
Hide thumbs Also See for 2WAY Multi:
Table of Contents

Advertisement

A02 Engine Oil Error

This function is used to advise the user that the time for changing the engine oil has arrived (or is close.) It is not
a function for detecting and displaying equipment malfunctions (or suspected malfunctions) in the same way as
normal error detection.
Oil Change Notifi cation Conditions and Display Method
The fact that the time for changing the engine oil has arrived (or is close) is displayed on the remote controller
and on the main circuit board on the outdoor unit.
Notifi cation
Notifi cation Conditions
(Time to Change Oil *1)
Oil Inspection 9,800 or more hours
A02 Alarm
(a) 10,000 to 10,300 hours
• Alarm triggered every
50 hours
(b) 10,300+ hours
• Alarm triggered every
4 hours
*1) Oil change time: Engine operation times since the previous oil-change and time reset
Method for resetting oil change hours timer
1) Select Menu No. 2 "Oil change hours display". The oil change hours are displayed as shown below.

2) By holding down the set key while displaying the oil change hours, the display changes to the following.
Also, if an operation error results in this display, simply wait for about one second to return to the previous
oil change hours display.

3) When the CLr display appears, release the set key momentarily, then quickly press and hold down the set key
again.
When the following display appears, the oil change hours are reset to 0 hours.
When this display does not appear, and the previous oil change hours are displayed, repeat the process as
described above.

Display method
Remote controller
Outdoor Unit
Circuit Board
"Oil Change" blinks 
"A02" blinks


(Displayed
alternately)
(See
below for details on how to reset the oil change time.)
• (o10100)
Oil change hours (10100 hours)
Displays "o" for oil change hours
• (CLr )
• (End )