Toshiba TOSVERT VF-S15 Instruction Manual page 44

My function-s
Hide thumbs Also See for TOSVERT VF-S15:
Table of Contents

Advertisement

 Input function command 21: CLR (clear)
 Input function command 22: CLRN (clear (inversion))
The CLR command turns off the input signal setted by the My function-S when the clear signal is
turned on, as shown in the figure below. The CLRN command turns off the input signal when the
clear signal is turned off.
Clear signal
Specify the input function to which clear
command is performed.
CLR(CLRN)
Input
<Example> Turn off the input signal from Terminal F by the clear command from Terminal R.
Prior setting
–
Step 1
Step 2
Unit 1
Step 3
Step 4
–
Output
Fig. 8-6 Processing by clear
Title
Parameter setting
a977  (Default)
f111 
f112 
f130 
a900 
a901 
a902 
a903  (Default)
a904  (Default)
a905 
a977 
Input
Clear signal
Output
Set to "Disabled" of the My function-S.
Assign the "no function" to the Terminal F.
Assign the "no function" to the Terminal R.
Assign the My function-S output 1 to the Terminal
RY-RC.
Read F input terminal signal. (LD F)
CLR command for the Terminal F.
Assing the CLR command to the Terminal R
NOP command (no operation)
Transfer the result to the My function-S output 1.
Set to "My function-S always ON".
- 43 -
E6581865
Description