3. Detailed Settings Function
Item
code
Automatic drain pump
Ventilation fan operation
Wired remote controller sensor
"Operation change control in
progress" display
OFF reminder function for
when weekly timer is used
Discharge temperature control
1
Heat exchanger temperature
for cold air discharge
(Heat exchanger control point
for control to prevent cold air)
2
Fan output switching
3
Drain pump delayed start time
4
Humidifier setting
5
Flap operation mode
6
Flap swing mode
7
8
Item
No.
0000
0001
operation
0060
0000
0001
0000
0001
0000
0001
0000
0001
0000
0001
0013
0014
0025
0026
0000
0001
0000
0001
0002
0058
0059
0060
0000
0001
0002
0003
0000
0001
0000
0001
0002
Setting data
Description
No forced operation
Forced operation for 1 minute
Continuous operation
None
Ventilation fan operated by remote controller.
Not used. (Body sensor is used.)
Remote control sensor is used.
Normal (displayed)
Not displayed
None
Only stop time setting is enabled.
Discharge temperature control OFF
Discharge temperature control ON
Control temperature 13°C
Control temperature 14°C
Control temperature 25°C
Control temperature 26°C
Output linked with fan. (ON when indoor unit fan is
operating.)
Fan mode operation output
No delayed start
1 second delayed start
Except
2 seconds delayed start
Indoor unit
Type
58 seconds delayed start
U1, F2,
59 seconds delayed start
T1, E1
60 seconds delayed start
Humidifier output OFF. Drain pump stopped.
Humidifier output ON. Drain pump operates.
Humidifier output ON. Drain pump operates for 1 minute
when total humidifier operating time reaches 60 minutes.
Humidifier output ON. Drain pump stopped.
Standard setting
Draft reduction mode (Flap swing lower-limit position is shifted
upwards.)
Smudging reduction mode (Flap swing upper-limit position
is shifted downwards.)
Normal mode
Draft reduction mode (Flap lower-limit position is
shifted upwards.)
2-12
2WAY SYSTEM
Remote Controller Functions
1 minute delayed start
2 minutes delayed start
Indoor unit
Type
58 minutes delayed start
U1, F2,
T1, E1
59 minutes delayed start
60 minutes delayed start