P20 Alarm; P22 Fan Motor Trouble - Panasonic U-8ME1E81 Service Manual

2way vrf system
Hide thumbs Also See for U-8ME1E81:
Table of Contents

Advertisement

4. 2WAY Alarm Codes

P20 Alarm

Alarm code
P20
Alarm meaning
High load alarm
Alarm conditions
The high pressure increases rapidly for a short time.
Probable cause
(1) The service valve in closed
(2) Operation failure of mechanical valve
(3) Outdoor fan motor trouble
Check
Check the service valve, mechanical valve and outdoor fan motor.
Correction
Example
Notes
P22 Alarm
Alarm code
P22
Alarm meaning
Fan motor trouble
Alarm conditions
Fan motor start failure, fan motor Hall IC input failure
Probable cause
Possible causes are a Hall IC input circuit failure and a fan HIC failure.
Check
Check the fan motor wiring, the Hall IC wiring, and the connector connections.
If the wiring and connectors are normal, then check that the capacitor of the Hall IC input circuit
is securely soldered on the outdoor unit control PCB. Also use a tester and measure the
resistance between fan HIC power (HIC+) and ground (HIC–).
If there is a short-circuit, there is an HIC malfunction.
HIC PCB for 8HP to 16HP
(A747038)
HIC PCB for 18HP and 20HP
(A747036)
Correction
If the fan does not start, the below corrections may be effective.
(1) If there is a fan HIC failure or circuit failure, replace the PCB.
(2) If the fan motor is locked, replace the fan motor.
Example
Notes
Turn OFF the power, and check the continuity of "+" and "–" on the fan circuit PCB.
HIC -
(NV)
HIC +
(P)
HIC -
(NV)
HIC +
(P)
3-27
2WAY SYSTEM
Trouble Diagnosis