Technical information
7.5 Technical specifications
Climatic ambient conditions
The following table shows the climatic ambient conditions for operation of the device.
Ambient conditions
Temperature for IFP1200 /
IFP1500 / IFP 1900 Basic:
Temperature for IFP2200
Basic:
Relative humidity
Atmospheric pressure,
operation elevation
Note the information in section "Notes about usage (Page 14)" .
7.5.2.3
Electromagnetic compatibility
Pulse-shaped interference
The following table shows the electromagnetic compatibility of modules with regard to pulse-
shaped interference. This requires the device to meet the specifications and directives for
electrical installation.
Pulse-shaped interference Test voltage
Electrostatic discharge
in accordance with IEC
61000-4-2
Bursts
(high-speed transient
interference)
in accordance with
IEC 61000-4-4
Surge in accordance with
IEC 61000-4-5
Asymmetrical coupling
Symmetrical coupling
62
Permitted range
horizontal mounting
•
0 to 45 °C
Vertical mounting
•
0 to 45 °C
horizontal mounting
•
0 to 40 °C
Vertical mounting
•
0 to 40 °C
10 to 85% at 30 °C, no condensa-
tion
1080 to 689 hPa
Air discharge: ± 8 kV
Contact discharge: ± 4 kV
± 2 kV power supply cable
± 1 kV signal cable, < 30 m
1 kV line-to-line of DC port
2 kV line-to-earth of DC port
± 2 kV power supply cable
DC voltage with protective elements
1 kV power supply cable
DC voltage with protective elements
Comments
Tilt angle max. 45°
Tilt angle max. 45°
Corresponds to an elevation
of -1000 to 3000 m
Operating Instructions, 03/2019, A5E46178354 - AB
Degree of
severity
3
2
3
3
3
IFP Basic