Determining The System Parameters For Purely Cooling Controllers (When Control Byte 1, Bit 0 = 0 And Bit 2 = 1) - Siemens SIMATIC S5 Manual

Ip 244 temperature controller with function block fb 162
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

4.7 Determining the System Parameters for Purely Cooling
Controllers (when Control Byte 1, Bit 0 = 0 and Bit 2 = 1)
The cooling response of the temperature-controlled system is plotted with a recorder (see also
Fig. 4.8/1).
The procedure is as follows:
enter non-critical control parameters:
T
A
K
R
T
, T
N
D
Upper limit of the control zone = 30 C
Lower limit of the control zone = 30 C
– Enter setpoint temperature = 0 C
– Allow the temperature to settle to the operating temperature, dependent on external heating
energy supply (e.g. by neighboring heating zones).
– Enter setpoint temperature = 1 C
The module switches the cooling on.
Caution:
during the cooling process the external supply of heating energy must remain
constant (i.e. neighboring heating zones must heat with a constant manipulated
variable).
Fig. 4.8/1 Recorded cooling curve
The parameters can then be determined from the curve:
T
=
U
S
=
K
T
=
sta
– The temperature T
COOL
IP244
C79000–B8576–C860–02
= 0.8 s
(numerical value 800)
= 1
(numerical value 100)
= 0
.
delay time (in s)
maximum slope of the cooling curve (in C/s)
start temperature (in C).
(in C) of the cooling medium must also be determined.