Example 3 - ABB Relion REC670 Applications Manual

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

Section 4
Analog inputs
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
IEC05000460 V2 EN-US
Figure 8:
Example how to set CTStarPoint parameters in the IED
This example is similar to example 1, but here the transformer is feeding just one line and the
line protection uses the same CT as the transformer protection does. The CT direction is set
with different reference objects for the two IEDs though it is the same current from the same
CT that is feeding the two IEDs. With these settings the directional functions of the line
protection shall be set to
4.2.2.3

Example 3

One IED used to protect two objects.
54
Transformer
Transformer
protection
IED
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Forward to look towards the line.
Line
Reverse
Definition of direction
for directional functions
Line protection
IED
Setting of current input:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
1MRK 511 358-UEN A
Forward
SEMOD55055-35 v5