ABB Relion REC670 Applications Manual page 81

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

1MRK 511 358-UEN A
In case of a solid earth fault in high impedance earthed or unearthed systems the primary
value of Uo voltage will be equal to:
U
Ph
=
U
0
EQUATION1931 V2 EN-US
Figure
24
available to the built-in protection and control functions within the IED as well.
Protected Object
L1
L2
R
IEC06000603 V4 EN-US
Figure 24: Neutral point connected VT
Application manual
-
Ph
=
U
-
Ph
E
3
gives an overview of required actions by the user in order to make this measurement
L3
1
Uo
6.6
kV
3
100
V
IED
2
3
# Not Used
# Not Used
# Not Used
Analog inputs
(Equation 11)
5
SMAI2
BLOCK
AI3P
REVROT
AI1
^GRP2L1
AI2
^GRP2L2
AI3
^GRP2L3
AI4
^GRP2N
AIN
4
IEC06000603-4-en.vsdx
Section 4
75