Advanced commissioning

6.8 Switchover between different settings

6.8
Switchover between different settings
There are applications that require different inverter settings.
Example:
You connect different motors to one inverter. Depending on the particular motor, the inverter
must operate with the associated motor data and the appropriate ramp-function generator.
Drive data sets (DDS)
Your can set several inverter functions differently and then switch over between the different
settings.
The associated parameters are indexed (index 0, 1, 2, or 3). Using control commands select
one of the four indexes and therefore one of the four saved settings.
The settings in the inverter with the same index are called the drive data set.
Figure 6-54
Using parameter p0180 you can define the number of drive data sets (1 ... 4).
306
Switching over between different settings using drive data sets (DDS)
Converter with CU230P-2 Control Units