Property
Degree of protection ac-
cording to EN 60529
Ambient temperature for
Ambient conditions accord-
ing to EN 60721-3-3
Temperature during stor-
age according to EN
60721-3-3
Cooling air
Relative humidity
Pollution according to EN
61800-5-1
Shocks and vibration ac-
cording to EN 60721-3-1
Installation altitude
Approvals
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Version
Chassis de-
IP20
vices
IP20, IP54
PT devices
LO base load power without derating:
HO base load power without derating:
LO/HO base load power with derating:
Details see Section Restrictions for special ambient conditions (Page 428).
For the maximum permissible ambient temperature, also observe the permissible ambient
temperatures for the Control Unit and possibly operator panel (IOP or BOP-2) .
FSA ... FSC
Protected against damaging chemical substance, according to environmental
Class 3C2
FSD ... FSE
Protected against damaging chemical substance, according to environmental
Class 3C3
-40 °C ... +70 °C
clean and dry air
< 95% - condensation not permissible
suitable for environments with degree of pollution 2
Long-term storage in the transport packaging according to Class 1M2
Transport in the transport packaging according to Class 2M3
Vibration in operation according to Class 3M2
without derating
with derating
Details see Section Restrictions for special ambient conditions (Page 428).
FSA ... FSC
cULus, CE, C-tick, KCC
FSD ... FSE
cULus, CE, C-tick, SEMI F47, KCC,WEEE, RoHS, EAC
10.2 Technical data, Power Modules
Must be installed in a control cabinet
Must be installed in a control cabinet at the control cabinet panel
-20 °C ... +40 °C
-20 °C ... +50 °C
-20 °C ... + 60° C
up to 1000 m above sea level
up to 4000 m above sea level
Technical data