ABB HU Instruction Leaflet

Transformer differential relays
Hide thumbs Also See for HU:

Advertisement

Quick Links

Effective: February 1999
Supersedes I.L. 41-347.12B, Dated November 1998
( | ) Denotes Change Since Previous Issue
CAUTION
!
Before putting relays into service, remove all
blocking which may have been inserted for the
purpose of securing the parts during shipment,
make sure that all moving parts operate freely,
inspect the contacts to see that they are clean
and close properly, and operate the relay to
check the settings and electrical connections.
APPLICATION
These relays have been specially designed and
tested to establish their suitability for Class 1E appli-
cations. These relays have been specially designed
and tested to establish their suitability for Class 1E
applications in accordance with the ABB Power T&D
Company program for Class 1E Qualification Testing
as detailed in bulletin STR-1.
"Class 1E" is the safety classification of the electric
equipment and systems in nuclear power generating
stations that are essential to emergency shutdown of
the reactor, containment isolation, cooling of the
reactor, and heat removal from the containment and
reactor, or otherwise are essential in preventing sig-
nificant release of radioactive material to the environ-
ment.
The types HU and HU-1 relays are high-speed relays
used in the differential protection of transformers.
These relays can be applied where the magnetizing
inrush current to the transformers is severe.
All possible contingencies which may arise during installation, operation or maintenance, and all details and
variations of this equipment do not purport to be covered by these instructions. If further information is
desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the
local ABB Power T&D Company Inc. representative should be contacted.
Printed in U.S.A.
ABB Automation, Inc.
Substation Automation & Protection Division
Coral Springs, FL
Allentown, PA
Current transformer ratio error should not exceed
10% with maximum symmetrical external fault current
flowing and the maximum symmetrical error current
which is flowing in the differential circuit on external
faults should not exceed 10 times relay tap setting.
The HU-1 relay has three restraint transformers and
associated rows of taps; whereas, the HU relay has
one less restraint transformer and two rows of taps.
Otherwise the two relays are identical. Three-winding
banks normally require the HU-1 relay, although the
auto-transformer application uses the HU if the ter-
tiary is not loaded.
Both the HU or the HU-1 are available with a sensitiv-
ity of either 30% or 35% times tap. The 30%-sensitiv-
ity relay satisfactorily handles up to 15% mismatch
(e.g. ± 10% transformer tap changing plus 5% ct mis-
match). The 35%-sensitivity relay handles as much
as 20% mismatch. See figure 7 for a comparison of
the characteristics of the two sensitivities. Any of the
relays may be recalibrated
either
Ordinarily the 30%-sensitivity relay will suffice; how-
ever, where ct mismatch is abnormally high or where
the transformer tap-changing range exceeds
this calibration may be too sensitive.
CONSTRUCTION
The types HU and HU-1 relays consist of a differen-
tial unit (DU), a harmonic-restraint unit (HRU), an
indicating instantaneous trip unit (IIT) and an indicat-
ing contactor switch (ICS). The principal parts of the
relay and their locations are shown in figures 1, 2, 3,
and 4.
Type HU and HU-1
Transformer Differential Relays
(Class 1E Applications)
in the field to obtain
characteristic.
Instruction Leaflet
41-347.12C
10%,

Advertisement

Table of Contents
loading

Summary of Contents for ABB HU

  • Page 1 HU if the ter- check the settings and electrical connections. tiary is not loaded. Both the HU or the HU-1 are available with a sensitiv- APPLICATION ity of either 30% or 35% times tap. The 30%-sensitiv-...
  • Page 2 To restraint Transf. 3 (HU-1 only) Capacitor - 0.45 MFD HRU Restraint Filter Circuit To restraint Transf. 2 To restraint Transf. 1 Figure 1. Type HU, HU-1 Relays - Front View Photo Figure 2. Type HU, HU-1 Relays - Rear View Photo...
  • Page 3 *Sub 3 Sub 3 3520A49 3520A72 Figure 3. Internal Schematic of the Type HU Relay in FT-31 Case. Figure 4. Internal Schematic of the Type HU-1 Relay in FT-31 Case. Denotes Change since previous issue...
  • Page 4 Figure 5. Polar Unit Permanent Magnet Flux Paths (DU) IFFERENTIAL OLAR The differential unit of the HU relay consists of two The polar unit consists of a rectangular shaped mag- air-gap restraint transformers, three full-wave rectifi- netic frame, an electromagnet, a permanent magnet, ers, saturating operating-transformer, and a dc polar and an armature.
  • Page 5 Sub 20 407C536 Figure 6. External Schematic of the Type HU and HU-1 Relays.
  • Page 6: Operation

    OPERATION NTERNAL AULTS The types HU and HU-1 are connected to the pro- tected transformer as shown in figure 4. In such a In the case of an internal fault as shown in figure 9b, connection, the relays operate to protect the trans-...
  • Page 7 Figure 7. Differential Characteristic of the DU Unit of the HU and HU-1 Relays at smaller values of current. Operating Current Shown for 15 and 20% Mismatch. Sub 1 471050 Figure 8. Differential Characteristic of the Differential Unit (DU) of the HU and HU-1 Relays at larger values of current.
  • Page 8 (a) External Fault (b) Internal Fault Figure 9. Simplified Schematic of the Type HU Relay with Current Distribution for (a) External Fault (b) Internal Fault. The varistor connected across the dc side of the nents are fed into the filter circuits. The impedance...
  • Page 9 Figure 10. Differential Voltage Characteristic of the DU Figure 11. Differential voltage Characteristic of the DU Unit of the HU and HU-1 Relays with a pickup Unit of the HU and HU-1 Relays with a pickup of 0.30 times tap.
  • Page 10: Setting Calculations

    41-347.12C CHARACTERISTICS SETTING Taps are incorporated in the HU and HU-1 relays to compensate for main current transformer mismatch. CAUTION These taps are as follows: 2.9, 3.2, 3.5, 3.8, 4.2, 4.6, 5.0, 8.7. Since the tap block screw carries operating cur- To measure the effective unbalance, a sensitive low- rent, be sure that the screws are turned tight.
  • Page 11 5. Check IIT operation . The IIT pickup is ten times = are same as T except for the relay tap value for the HU and HU-1. There- high, low and intermediate voltage wind- fore, the maximum symmetrical error current ings, respectively which is flowing in the differential circuit on exter-...
  • Page 12: Installation

    0.15/T is an approximation. Use 2-way lead resistance for single phase-to-ground fault.) Sub 2 619583 For delta-connected ct: Figure 14. Typical Response of the HU and HU-1 50   ohms 0.15 Hertz Relays. 1.13 R ---------- - ...
  • Page 13 41-347.12C Sub 2 289B412 Figure 15. Example for Setting Calculations the relay is in proper working order. All checks can 2. Indicating Instantaneous Trip Pickup best be performed by connecting the relay per the test circuit of figure 16. RELAY MUST BE TESTED With switch open and relay set on 5 ampere tap, IN CASE.
  • Page 14 41-347.12C TWO-WINDING TRANSFORMER CALCULATIONS See figure 15 HIGH 1. Select ct Ratio: 200 000 20 000 ---------------------- - 930 amp. ------------------ - 167 amp. 12.4 3 69 3 --------------------- - = 1000/5 (N = 200) 500/5 (N = 40) ------------ - 1000 Select Ratio 4.65 amp.
  • Page 15 41-347.12C THREE-WINDING TRANSFORMER CALCULATIONS See figure 15 HIGH INTERMEDIATE 1. Select ct Ratio: 40 000 40 000 10 000 143 amp 334 amp 465 amp ------------------ - ------------------ - ------------------ - --------------------- - = 161 3 69 3 12.4 3 ------------ - 1000 Select Ratio...
  • Page 16: Routine Maintenance

    Table 2 is to be used as an in-service check of the between the following limits: HU or HU-1 relay using any tap combination. This 20 amperes test also checks against reversed tap connections. The relay should be connected as shown in figure 16 45 to 50 amperes with the SPDT switch in position 1.
  • Page 17 Sub 2 Sub 1 1477B71 471047 Figure 16. Test Circuit of the HU and HU-1 Relays Figure 17. Variation of Second Harmonic Content of Test Current All contacts should be periodically cleaned. A contact (front view) pole face and the armature. This...
  • Page 18 41-347.12C Table 2: Restraint Transformer Larger Smaller Current in Amperes (Min) 10.4 16.2 (Max) 10.0 11.6 17.9 (Min) 15.7 (Max) 10.6 17.3 10.5 10.5 10.5 10.5 10.5 (Min) 14.5 (Max) 16.1 11.4 11.4 11.4 11.4 (Min) 14.1 (Max) 16.0 12.6 12.6 12.6 (Min)
  • Page 19 41-347.12C b. After the dropout has been measured, the 3. Pickup - With switch open, pass I = 10 times unit should operate at 25% or higher of tap tap value current and adjust core of the instanta- value current without the polarization test. neous trip unit until it picks up.
  • Page 20 85% of rating. If necessary, the 5, 7, 9 (HU-1 only) in turn. The ac voltage across cover leaf springs may be adjusted. To lower the the appropriate restraint rectifier bridge using a...
  • Page 21: Renewal Parts

    41-347.12C B. Operating Circuit Diode Check Check for open or shorted diodes using the electrical Apply 30 percent tap-value current to terminal 3 checkpoints above. and a tap screw. Using a high-resistance voltme- ter, the ac voltage across the operating coil bridge and the ac voltage output of the operating RENEWAL PARTS transformer (top two coil terminals) should be...
  • Page 22 41-347.12C THIS PAGE RESERVED FOR NOTES...
  • Page 23 41-347.12C Sub 2 775B958 Figure 18. HU, HU-1 diode Board Module – Component Location...
  • Page 24 41-347.12C *Sub 4 3519A68 Figure 19. Outline and Drilling Plan of the Type HU and HU-1 Relays in the FT31 Case Denotes change since previous issue ABB Automation, Inc. ABB Automation, Inc. Substation Automation & Protection Division Substation Automation & Protection Division...

This manual is also suitable for:

Hu-1

Table of Contents