ABB ControlMaster CM10 Manual page 16

Universal process controllers, 1/8, 1/4, 1/2 din and fieldmount
Hide thumbs Also See for ControlMaster CM10:
Table of Contents

Advertisement

ControlMaster CM10, CM15, CM30, CM50, CMF160 and CMF310
Universal process controllers and indicator,
Warning.
ControlMaster controllers and indicator are not fitted with a switch therefore a disconnecting device such as a switch or circuit breaker
conforming to local safety standards must be fitted to the final installation.
It must be mounted in close proximity to the ControlMaster within easy reach of the operator and must be marked clearly as the
disconnection device for the instrument.
Remove all power from supply, relay and any powered control circuits and high common mode voltages before accessing or making any
connections.
Use cable appropriate for the load currents. The terminals accept cables from 18 to 14 AWG (0.8 to 2.5mm
Always route signal leads and power cables separately, preferably in earthed (grounded) metal conduit.
It is strongly recommended that screened cable is used for signal inputs and relay connections.
ControlMaster CM10, CM30 and CM50 controllers and CM15 indicator conform to Mains Power Input Overvoltage Category 2, Pollution
Degree 2 (EN601010–1) and are protected through double insulation – Class II.
ControlMaster CMF160 and CMF310 conform to Overvoltage Class III on mains, Class II on inputs and outputs and Pollution degree 2,
Insulation class 1.
Analog / digital inputs and outputs, transmitter power supply and DC power supply are SELV (Safety Extra Low Voltage) circuits.
All connections to secondary circuits must have basic insulation.
After installation, there must be no access to live parts, e.g. terminals.
Terminals for external circuits are for use only with equipment with no accessible live parts.
If a ControlMaster is used in a manner not specified by the Company, the protection provided by the equipment may be impaired.
All equipment connected to the instrument's terminals must comply with local safety standards (IEC 60950, EN601010–1).
Note. Terminal screws must be tightened to a torque of 0.1 Nm (0.9 lbf/in.).
14
1
1
1
/
,
/
,
/
DIN and fieldmount
8
4
2
5 MODBUS Communications
2
).
IM/CM/C–EN Rev. H