Diagnostic alarm
Invalid transition of A/B
signals
RS422/TTL error
SSI encoder error
Overtemperature
No longer available as of module version V1.3. This case is then taken into account by the diagnostic interrupt "Supply
1
voltage missing".
Technology module TM PosInput 2 (6ES7551-1AB00-0AB0)
Manual, 06/2018, A5E03982218-AB
Error
Meaning
code
500
Time profile of signals A and B of the
•
H
incremental encoder does not meet
certain requirements (relative phase
shift of the two signals is too small)
Possible causes:
•
–
Signal frequency too high
–
Encoder faulty
–
Process wiring faulty
502
Error at connection of the RS422 en-
•
H
coder, TTL encoder or SSI absolute
encoder
Possible causes:
•
–
Wire break
–
No encoder connected
–
Cable too long
–
Short circuit
–
Overload
–
External voltage
–
Overtemperature
–
Parameter assignment error
503
Error at SSI absolute encoder connec-
•
H
tion
Possible causes:
•
–
Wire break
–
Cable too long
–
Frame error (error of the start bit or
stop bit)
–
Parity error
–
Parameter assignment error
506
Short-circuit or overload at the digital
•
H
outputs or outputs of the encoder sup-
ply
Ambient temperature outside specifi-
•
cations
Contamination in the module prevents
•
cooling
Interrupts/diagnostic messages
5.2 Diagnostic alarms
Remedy
Check process wiring
•
Check encoder/sensor
•
Check parameter assignment
•
Check process wiring
•
Check encoder/sensor
•
Check parameter assignment
•
Check process wiring
•
Check SSI absolute encoder
•
Check parameter assignment
•
Check process wiring
•
Improve cooling
•
Check connected loads
•
79