Hydraulic Soft Start And Separate Acceleration Ramp - Bosch Rexroth Sytronix FcP 5020 Quick Start Manual

Frequency-controlled pump drive system
Hide thumbs Also See for Rexroth Sytronix FcP 5020:
Table of Contents

Advertisement

Bosch Rexroth AG
Block Diagram of Main Functions

7.9.6 Hydraulic Soft Start and Separate Acceleration Ramp

Code
Name
F4.20 p/Q command soft start delay 0.0...1,000.0 s
Minimum pressure command
F4.21
limit
F4.23 Minimum flow command limit 0...[F4.24] rpm
Acceleration time hydraulic
F4.25
soft start
Tab. 7-19: Parameter list of hydraulic soft start
Soft start function is designed to reduce the p/Q command and acceleration
during start up period to minimize the too high of acceleration or potential over
current condition during start up. Once this function is active (set F4.20 > 0),
the p/Q commands and acceleration time will be switched to F4.21, F4.23 and
F4.25, in a time period of F4.20 after every run command.
Only when p/Q command soft start is active will the acceleration
time hydraulic soft start function be activated.
Fig. 7-17: Hydraulic soft start
40/75
Setting range
0.0...[F4.22] bar
0.1...6,000.0 s
Default
Min.
0.0
0.1
5.0
0.1
200
1
5.0
0.1
DOK-RCON03-FCP5020****-QU02-EN-P
FcP 5020
Attri.
Stop
Stop
Stop
Run