DOK-INDRV*-FCS01******-IT01-EN-P
Rexroth IndraDrive Fc Drive Controllers Frequency Converters FCS01
Overview of standards applying as test methods and measuring methods in accordance with the product standard EN
Noise emission
Conducted emission (interference voltage)
Radiated emission (interference-field strength)
Noise immunity EN 61000-6-1, EN 61000-6-2
ESD, discharge of static electricity
EMF, high-frequency electromagnetic fields
Burst on control lines
Burst on mains lines and motor lines
Surge (phase-phase / ground)
Conducted disturbance by high-frequency fields
Voltage fluctuations and voltage dips
Voltage asymmetries and frequency changes
5.1.4

Wiring Recommendations for Power Connections

LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01
61800-3 for adjustable speed electrical power drive systems:
Fig.5-1:
Noise Immunity
Connect the cable shield on both sides, i.e. at the shield angle of
the frequency converter housing and at the motor terminal box.
Fig.5-2:
Wiring
EN 55011
EN 55011
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-2-1
EN 61000-2-4
Bosch Rexroth AG
35/69
Instructions for Use
A 1 or C2
B 1 or C1
A 1 or C2
-
6kV (CD), 8kV (AD)
10 V/m; 80 - 1000 MHz
1 kV
2 kV
1 kV / 2 kV
10 V, 0.15 - 80 MHz
+10%, -15%; 90%