Certification
6.1.14 Other Approvals
6.1.14
Other Approvals
This device meets the requirements of the following additional standards:
•
•
•
•
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RX1400 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Tests per IEC 61850-3
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
Burst (Fast Transient)
IEC 61000-4-5
IEC 61000-4-6
Induced (Conducted) RFI
IEC 61000-4-8
54
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
IEC 61850-3
General Requirements
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
NEMA TS-2
Traffic Controller Assemblies with NTCIP Requirements
Description
ESD
Radiated RFI
Surge Immunity
Magnetic Field
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Enclosure Ports
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV
± 4 kV @ 2.5 kHz, 5 kHz
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
± 2 kV Line-to-Earth
± 1 kV Line-to-Line
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
10 V
100 A/m Continuous
Installation Manual, 09/2019, C79000-G8976-1103-13
Severi-
ty Levels
4
a
Note
4
3
4
3
5
RUGGEDCOM RX1400